CMS OF COLORADO SPRINGS, INC. | B= | C | 01/18/2017 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 5391206 |
CMS OF COLORADO SPRINGS, INC. | B= | P | 01/17/2017 | Building final OK pending electrical, zoning, and fire. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet, External Agency Inspection Z= by WOODLAND PARK is not Completed yet (Contact: Deidra Arnold at 719-687-5202 or Lisa Parnell at 719-687-5209). | NICK | NICK | | B= | P | 5389777 |
CMS OF COLORADO SPRINGS, INC. | BIN | C | 01/17/2017 | | NICK | NICK | | BIN | C | 5389776 |
CMS OF COLORADO SPRINGS, INC. | BFR | C | 01/17/2017 | | NICK | NICK | | BFR | C | 5389775 |
CMS OF COLORADO SPRINGS, INC. | BIN | P | 11/08/2016 | Inspection of R38 ceiling insulation only.installed. Contractor to provide Com-check for bathroom at next inspection. | DAN | DAN | | BIN | P | 5339520 |
CMS OF COLORADO SPRINGS, INC. | BFR | P | 10/04/2016 | Partial trusses only OK. need electrical and plumbing and mechanical roughs. | DAN | DAN | | BFR | P | 5309922 |
CMS OF COLORADO SPRINGS, INC. | BBB | C | 09/09/2016 | beam top of wall, 8' OK completes beams. | DAN | DAN | | BBB | C | 5289133 |
CMS OF COLORADO SPRINGS, INC. | BBB | P | 09/07/2016 | bond beam at 6' OK to pour. Reviewed beam requirements above opening with contractor. | DAN | DAN | | BBB | P | 5286468 |
CMS OF COLORADO SPRINGS, INC. | BSP | R | 09/06/2016 | beam at 6'6" missing 2nd horz bar and missing verticals at openings and corners and "T" walls. Recall | DAN | DAN | | BSP | R | 5286113 |
CMS OF COLORADO SPRINGS, INC. | BBB | P | 08/30/2016 | Course 5 bond beam OK / Still need to see top of wall | NICK | NICK | | BBB | P | 5281163 |
CMS OF COLORADO SPRINGS, INC. | BSP | P | 08/11/2016 | slab strip footers and re-bar OK. CMU walls to be cut in slab when poured. | DAN | DAN | | BSP | P | 5267325 |
CMS OF COLORADO SPRINGS, INC. | BFN | C | 07/20/2016 | Foundation design already scanned in system. | DAN | DAN | | BFN | C | 5249580 |
CMS OF COLORADO SPRINGS, INC. | BFT | C | 07/14/2016 | open hole and compaction tests on file. will need bond beam inspection on course 5 and top of wall. | DAN | DAN | | BFT | C | 5245443 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | E= | C | 01/25/2017 | | JOHNN | JOHNN | | E= | C | 5398991 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | E= | P | 01/23/2017 | need AIC labeling on service equip and panels, | JOHNN | JOHNN | | E= | P | 5396238 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | ES | P | 11/17/2016 | Commercial Service: 400 amp,new commercial,ok to set meter-------------------notes:bond water,brass tag,bond neutral in MDP-1 | JOHNN | JOHNN | | ES | P | 5347922 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | ER | P | 11/17/2016 | need water bond,brass tag | JOHNN | JOHNN | | ER | P | 5347913 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | ES | R | 11/16/2016 | service needs bonding completed in north building | JOHNN | JOHNN | | ES | R | 5346592 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | ER | R | 11/16/2016 | service needs bonding completed in north building | JOHNN | JOHNN | | ER | R | 5346588 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | ER | P | 11/08/2016 | meeting with GC,electrician, | JOHNN | JOHNN | | ER | P | 5339730 |
AMPED UP ELECTRIC, LLC, DBA ACE ELECTRIC | ER | P | 11/04/2016 | north bath rm ceilings,ok | JOHNN | JOHNN | | ER | P | 5337149 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | H= | C | 01/05/2017 | CORRECTIONS VERIFIED BY PICTURE - ALL OK | JERRYF | JERRYF | | H= | C | 5383221 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | H= | P | 01/05/2017 | CANCELED BY INSPECTOR CONTRACTOR WILL SEND PICTURES OF CORRECTIONS | JERRYF | JERRYF | | H= | P | 5382811 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | H= | L | 12/30/2016 | COMPUTER CALL AHEAD DID NOT GO THROUGH. CALLED ON INSPECTOR PHONE ONLY ABLE TO LEAVE VOICE MAIL. | JON | JON | | H= | L | 5380070 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | H= | P | 12/30/2016 | TAB REPORT RECEIVED - NEED OTHER NOTES ADDRESSED | JERRYF | JERRYF | | H= | P | 5379729 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | H= | R | 12/23/2016 | NEED TEST AND BALANCE REPORT SHOWING ALL EXHAUST CFM'S PER PLAN - NOT A DUCT LEAKAGE REPORT - STILL NEED OTHER NOTES ADDRESSED FROM PREVIOUS COMMENTS | JERRYF | JERRYF | | H= | R | 5375629 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | HC | C | 11/02/2016 | RELEASE METER | JERRYF | JERRYF | | HC | C | 5334472 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | HI | C | 11/02/2016 | VERIFY FINAL CONNECTION AT FURNACE AT FINAL INSPECTION NOTES: 10# OK - PIPING PER PLAN | JERRYF | JERRYF | | HI | C | 5334458 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | HD | C | 11/02/2016 | BY FINAL CATWALK TO EXHAUST FAN AND LIGHT WITH SWITCH INSTALLED / FINAL FLUE CONNECTIONS AT FURNACE - ATTACH WATER HEATER TO PERMIT / TAB REPORT NOTES: ABOVE CEILING OK | JERRYF | JERRYF | | HD | C | 5334453 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | P= | C | 12/29/2016 | corrections made. | TAYLOR | TAYLOR | | P= | C | 5378676 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | P= | P | 12/28/2016 | still need to correct scope of work, rest ok. | TAYLOR | TAYLOR | | P= | P | 5378195 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | P= | P | 12/22/2016 | need check valve or vacuum breaker at water heater, need 16-18 inches from wall to center of toilet at mens restroom, correct scope of work as previously noted, install vacuum breaker at hose bib in mech room, note: no irrigation. | TAYLOR | TAYLOR | | P= | P | 5375215 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | PTO | C | 11/02/2016 | add water heater and 1 drinking fountain to scope of work and correct s- traps for lavs in mech room by final. | TAYLOR | TAYLOR | | PTO | C | 5334563 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | PB | C | 08/03/2016 | correction made, per plan. | TAYLOR | TAYLOR | | PB | C | 5260803 |
WOODLAND PLUMBING, HEATING & AIR CONDITIONING LLC | PB | P | 08/02/2016 | low test. | TAYLOR | TAYLOR | | PB | P | 5259687 |