Electrical | Splice 12/07/18 | A | 12/7/2018 | BERTHA | BERTHA | Revised one-line diagram to address inspector's comments concerning AIC rating. Revised "keyplan" to indicate location of Panel H. | | Electrical | 1138950 |
Out to Review | Splice 12/07/18 | / | 12/7/2018 | BECKYA | BECKYA | | | Out to Review | 1138925 |
Electrical | Revise One Line | A | 12/4/2018 | SHELBY | SHELBY | | | Electrical | 1137460 |
Mechanical | Splice 10/25/18 | A | 10/25/2018 | JUSTINC | JUSTINC | Revised gas pipe to roof | | Mechanical | 1123899 |
Scanned/Finished Bin | Splice 8/14/18 | / | 8/31/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1105630 |
Mechanical | Splice 8/30/18 | A | 8/30/2018 | DALEH | DALEH | relocate gas lines | | Mechanical | 1105454 |
Out to Review | Splice 8/30/18 | / | 8/30/2018 | BECKYA | BECKYA | | | Out to Review | 1105440 |
Plumbing | Splice 8/14/18 | A | 8/30/2018 | TCRIPPEN | TCRIPPEN | new splice pages to install bathrooms and fixtures. | | Plumbing | 1105429 |
Resubmittal 1 | Splice 8/14/18 | / | 8/30/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1105409 |
Electrical | Splice 8/14/18 | A | 8/30/2018 | BERTHA | BERTHA | Removed Panel C from scope. | | Electrical | 1105258 |
Plumbing | Splice 8/14/18 | D | 8/30/2018 | TCRIPPEN | TCRIPPEN | need to fill out the Alternate variance. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1105253 |
Construction | Splice 8/14/18 | A | 8/30/2018 | MICHAELA | MICHAELA | Add toilet rooms and demising wall | | Construction | 1105241 |
Electrical | Splice 8/14/18 | D | 8/14/2018 | BERTHA | BERTHA | 1. Provide Panel C schedule. 2. Provide Panel C on one-line. 3. Provide clouding for current splice only.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1099723 |
Plumbing | Splice 8/14/18 | D | 8/14/2018 | TCRIPPEN | TCRIPPEN | Need Alternate for drinking fountain. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1099704 |
Out to Review | Splice 8/14/18 | / | 8/14/2018 | DANM | DANM | | | Out to Review | 1099678 |
Construction | Splice 8/14/18 | D | 8/14/2018 | DANM | DANM | Show wall at Column line 3 and note construction Provide interior elevations for restrooms showing accessibility compliance and surrounding materials Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1099677 |
Mechanical | Splice 8/14/18 | A | 8/14/2018 | JUSTINC | JUSTINC | Revised for added bathrooms | | Mechanical | 1099670 |
Scanned/Finished Bin | Splice 6/12/18 | / | 6/13/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1079227 |
To Be Scanned Bin | Splice 6/12/18 | / | 6/12/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1078608 |
CO Springs Fire | Splice 6/12/18 | A | 6/12/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1078594 |
Construction | Splice 6/12/18 | A | 6/12/2018 | DANM | DANM | Change type of construction to V-B from II-B and change proposed occupancy to A-2,B, M | | Construction | 1078578 |
Out to Review | Splice 6/12/18 | / | 6/12/2018 | BECKYA | BECKYA | | | Out to Review | 1078573 |
Mechanical | Splice 5/30/18 | A | 6/1/2018 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1075375 |
Plumbing | Splice 5/30/18 | A | 6/1/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1075299 |
Waste Water Div | Splice 5/30/18 | A | 5/30/2018 | CSUREVIEW | CSUREVIEW | Please confirm with CSU Utility Service Inspector on the need for revision or redline changes to the CSU Utility Service Plan. JPN | jnoble | Waste Water Div | 1074263 |
CO Springs Fire | Splice 5/30/18 | N | 5/30/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1074245 |
Plumbing | Splice 5/30/18 | D | 5/30/2018 | JUSTINC | JUSTINC | need engineers stamp (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1074219 |
Mechanical | Splice 5/30/18 | D | 5/30/2018 | JUSTINC | JUSTINC | all ok pending engineers stamp (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1074218 |
Construction | Splice 5/30/18 | A | 5/30/2018 | SHELLEY | SHELLEY | Revised sprinkler room location; windows and parapet details | | Construction | 1074187 |
Out to Review | Splice 5/30/18 | / | 5/30/2018 | BECKYA | BECKYA | Gwen Walking | | Out to Review | 1074179 |
Electrical | Splice 5/30/18 | A | 5/30/2018 | SHELBY | SHELBY | | | Electrical | 1074174 |
Out to Review | Original | / | 4/20/2018 | RITA | RITA | Kirk 719-233-5797 | | Out to Review | 1059945 |
Scanned/Finished Bin | Original | / | 4/17/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1058309 |
To Be Scanned Bin | Original | / | 4/17/2018 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1058295 |
Health Dept. | Original | N | 4/17/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable | Aparikh | Health Dept. | 1058235 |
Electrical | Original | A | 4/2/2018 | BERTHA | BERTHA | | | Electrical | 1053014 |
Resubmittal 1 | Original | / | 4/2/2018 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1053007 |
Electrical | Original | D | 3/28/2018 | BERTHA | BERTHA | Comply with previous review comments 1, 2 and 3.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1051262 |
CSU Contract Admin. | Original | N | 3/27/2018 | CSUAPPSPRM | CSUAPPSPRM | ** CORE/SHELL ONLY - NO SERVICES THIS PLAN/PERMIT.
NOTE: Approved Commercial Water Meter Sizing Form and paid utility receipt required at time of first tenant finish Plan or conversion to thru finish. Further, additional Commercial Water Meter Sizing Form(s) may be required for subsequent tenant finishes. ZJS | zshearer | CSU Contract Admin. | 1050715 |
Water Division | Original | A | 3/26/2018 | CSUREVIEW | CSUREVIEW | Items have been addressed. mjg | mgackle | Water Division | 1050480 |
Waste Water Div | Original | A | 3/26/2018 | CSUREVIEW | CSUREVIEW | Items have been addressed. mjg | mgackle | Waste Water Div | 1050479 |
City Engr | Original | A | 3/26/2018 | CSENGINEER | CSENGINEER | Walk thru approval. jad | csengineer | City Engr | 1050461 |
CO Springs Fire | Original | A | 3/23/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1050003 |
Enumeration | Original | A | 3/23/2018 | BRENT | BRENT | Final plat has been recorded. Secondary addressing now shown. | | Enumeration | 1049925 |
Out to Review | Original | / | 3/21/2018 | GITA | GITA | 7196323384 Ralph | | Out to Review | 1049279 |
Finished Bin | Original | / | 3/7/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1044426 |
Water Division | Original | D | 3/7/2018 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Water Division | 1044354 |
Waste Water Div | Original | D | 3/7/2018 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Waste Water Div | 1044352 |
CO Springs Fire | Original | D | 3/7/2018 | CSFIRE | CSFIRE | reference review report within plans for all comments needing to be addressed. (see full review) | csfdit | CO Springs Fire | 1044125 |
Fire | Original | / | 3/2/2018 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1042604 |
CO Springs DRE | Original | A | 3/2/2018 | RDCUSER | RDCUSER | Approved construction to comply with approved DP: City File AR DP 17-00511. See redline comments sheet A1.00 and E1.01, trash enclosure not shown in approved DP location. (see full review) | | CO Springs DRE | 1042603 |
Out to Review | Original | / | 2/28/2018 | MATTHEWM | MATTHEWM | Ralph 6323384 | | Out to Review | 1041754 |
Fire | Original | / | 2/23/2018 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1040548 |
CO Springs DRE | Original | D | 2/23/2018 | RDCUSER | RDCUSER | Disapproved. Sheet TS-1 has incorrect Legal Description, revise to current platted legal descrip. Update construction drawings with approved relevant Development Plan drawings. Note, have Final Landscaping and irrigation been submitted. Contact Chris Staley 719.385.5090 for details. (see full review) | | CO Springs DRE | 1040547 |
Construction | Original | A | 11/16/2017 | DANM | DANM | | | Construction | 1013754 |
Out to Review | Original | / | 10/13/2017 | MINDY | MINDY | Ralph 632 3384 | | Out to Review | 1004073 |
Finished Bin | Original | / | 10/12/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1003625 |
Health Dept. | Original | D | 10/12/2017 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required. Contact 578-3199 option #3 for more information regarding construction activity permits. AP 578-3278 | Aparikh | Health Dept. | 1003475 |
Health Dept. | Original | / | 10/9/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1002332 |
City Engr | Original | D | 10/9/2017 | CSENGINEER | CSENGINEER | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering approved Grading & Erosion Control Plan in the building permit set. Plan set routed to RBD. jad | csengineer | City Engr | 1002278 |
Hazmat | Original | N | 10/5/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1001640 |
CO Springs Fire | Original | D | 10/5/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1001633 |
Fire | Original | / | 9/29/2017 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1000106 |
CO Springs DRE | Original | D | 9/29/2017 | RDCUSER | RDCUSER | MRB per HVN. Provide the stamped approved development plan and variance. Provide the recorded and signed final plat. No review conducted at this time - no walk. (see full review) | | CO Springs DRE | 1000105 |
Zoning/Planning | Original | / | 9/29/2017 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | lmpope | Zoning/Planning | 1000065 |
CSU Contract Admin. | Original | D | 9/29/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form and payment of development charges/fees. Call Utilities Development Services at 719-668-8111 for more information. LMP | lmpope | CSU Contract Admin. | 1000064 |
Water Division | Original | D | 9/29/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Water Division | 999791 |
Waste Water Div | Original | D | 9/29/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Waste Water Div | 999790 |
Gas/Elec. Utils | Original | A | 9/29/2017 | CSUREVIEW | CSUREVIEW | No utility service with this permit, shell only. mjg | mgackle | Gas/Elec. Utils | 999789 |
CSU Contract Admin. | Original | / | 9/28/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 999518 |
Plan Coordinator | Original | / | 9/28/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 999453 |
Mechanical | Original | A | 9/28/2017 | DALEH | DALEH | | | Mechanical | 999452 |
Mechanical | Original | / | 9/28/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 999448 |
Mechanical | Original | / | 9/27/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 999207 |
Plan Coordinator | Original | / | 9/25/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 998220 |
Electrical | Original | D | 9/25/2017 | SHELBY | SHELBY | 1. Tap conductor 4T200 violates 250.122(G) NEC. 2. Indicate AIC rating of lowest rated breaker in all series rated panels. 3. Provide manufacturers specification for series rated breaker combinations. 4. Feeder schedule must appear on same page as one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 998219 |
Electrical | Original | / | 9/25/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 998201 |
Electrical | Original | / | 9/25/2017 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 998175 |
Plumbing | Original | A | 9/25/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 998174 |
Electrical | Original | / | 9/25/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electrical | 998116 |
Electrical | Original | / | 9/22/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 998054 |
Plan Coordinator | Original | / | 9/22/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 998046 |
Construction | Original | D | 9/22/2017 | DANM | DANM | Clarify if building is sprinklered or not - conflicting information on drawings and Code Study Form Clarify smaller area for scope of work on Code Study Form All plywood should be fire-resistance rated Provide Soils Report reference on Sheet S1.01 Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 998044 |
Construction | Original | / | 9/22/2017 | DANM | DANM | In Current Review by DANM | | Construction | 997983 |
Construction | Original | / | 9/22/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 997724 |
Plan Coordinator | Original | / | 9/22/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 997691 |
Enumeration | Original | D | 9/22/2017 | BRENT | BRENT | Final plat for this development has not yet been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. Show secondary addressing for the maximum number of tenant spaces the building will hold on page A2..01. Secondary addressing is available on our website www.pprbd.org ->addressing->secondary addressing guide. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 997690 |
Enumeration | Original | / | 9/22/2017 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 997685 |
Floodplain | Original | N | 9/20/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 997260 |