Mechanical | Splice 12/19/18 Mechanical A&m | A | 12/19/2018 | JUSTINC | JUSTINC | Splice if for A&M associated with refrigerant for walkins | | Mechanical | 1142988 |
Electrical | Splice 11/30/18 | A | 12/4/2018 | BERTHA | BERTHA | Added Panel E. | | Electrical | 1137589 |
Resubmittal 1 | Splice 11/30/18 | / | 12/4/2018 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1137550 |
Electrical | Splice 11/30/18 | D | 12/3/2018 | BERTHA | BERTHA | 1. Provide conductor size type and quantity for new panel E 2. Provide available fault current for new panel E 3. Provide model # for breakers in series rated combinations. 4. Provide location of new panel E.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1137117 |
Out to Review | Splice 11/30/18 | / | 11/30/2018 | BECKYA | BECKYA | | | Out to Review | 1136188 |
Construction | Splice 11/8/18 | A | 11/9/2018 | MICHAELA | MICHAELA | | | Construction | 1129446 |
Resubmittal 1 | Splice 11/8/18 | / | 11/9/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1129163 |
Mechanical | Splice 11/8/18 | A | 11/8/2018 | DALEH | DALEH | delta 12 | | Mechanical | 1128924 |
Out to Review | Splice 11/8/18 | / | 11/8/2018 | BECKYA | BECKYA | | | Out to Review | 1128885 |
Construction | Splice 10/17/18 Kitchen plans add to plan no review | A | 10/17/2018 | BECKYA | BECKYA | No review. Kitchen plans added to plan. | | Construction | 1120933 |
Electrical | Splice 10/3/18 | A | 10/3/2018 | SHELBY | SHELBY | | | Electrical | 1116178 |
Construction | Splice 10/3/18 | A | 10/3/2018 | DANM | DANM | Minor interior elevation revisions | | Construction | 1116035 |
Electronic Plan | Splice 10/3/18 | / | 10/3/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1116014 |
Mechanical | Splice 9/18/18 | A | 10/1/2018 | DALEH | DALEH | | | Mechanical | 1115194 |
Electrical | Splice 9/18/18 | A | 10/1/2018 | SHELBY | SHELBY | | | Electrical | 1115110 |
Plumbing | Splice 9/18/18 | A | 10/1/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1115102 |
Electronic Plan | Splice 9/18/18 | / | 10/1/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1115092 |
Resubmittal 1 | Splice 9/18/18 | / | 10/1/2018 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1115087 |
Mechanical | Splice 9/18/18 | A | 9/24/2018 | DALEH | DALEH | | | Mechanical | 1112812 |
Plumbing | Splice 9/18/18 | D | 9/19/2018 | TCRIPPEN | TCRIPPEN | back flow devices required on water lines before faucet provide detail drawing (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1111866 |
Electronic Plan | Splice 9/18/18 | / | 9/19/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1111802 |
Electrical | Splice 9/18/18 | A | 9/18/2018 | SHELBY | SHELBY | | | Electrical | 1111434 |
CO Springs DRE | Splice 9/17/18 | A | 9/18/2018 | BECKYA | BECKYA | Per MDS on 9/17/18 | | CO Springs DRE | 1110989 |
Water Division | Splice 9/17/18 | N | 9/18/2018 | BECKYA | BECKYA | N/A per AJ 9/17/18 | | Water Division | 1110988 |
Waste Water Div | Splice 9/17/18 | N | 9/18/2018 | BECKYA | BECKYA | N/A per AJ 9/17/18 | | Waste Water Div | 1110987 |
Gas/Elec. Utils | Splice 9/17/18 | N | 9/18/2018 | BECKYA | BECKYA | N/A - per AJ 9/17/18 | | Gas/Elec. Utils | 1110985 |
City Engr | Splice 9/17/18 | N | 9/17/2018 | CSENGINEER | CSENGINEER | Walk thru. jad | csengineer | City Engr | 1110852 |
Hazmat | Splice 9/17/18 | A | 9/17/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1110788 |
CO Springs Fire | Splice 9/17/18 | A | 9/17/2018 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1110786 |
Mechanical | Splice 9/17/18 | A | 9/17/2018 | DALEH | DALEH | re-approved paper splice no changes from last electronic splice | | Mechanical | 1110649 |
Construction | Splice 9/17/18 | A | 9/17/2018 | DANM | DANM | Drive thru canopy added | | Construction | 1110648 |
Electrical | Splice 9/17/18 | A | 9/17/2018 | SHELBY | SHELBY | | | Electrical | 1110635 |
Out to Review | Splice 9/17/18 | / | 9/17/2018 | BECKYA | BECKYA | | | Out to Review | 1110629 |
Floodplain | Splice 9/17/18 | N | 9/17/2018 | BECKYA | BECKYA | Per Keith 9/10/18 | | Floodplain | 1110628 |
Health Dept. | Original | A | 7/3/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | rnielsen | Health Dept. | 1086183 |
Health Dept. | Original | / | 7/3/2018 | HEALTHDEPT | HEALTHDEPT | | rnielsen | Health Dept. | 1086179 |
Health Dept. | Original | D | 6/22/2018 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions please contact 719-578-3199 option 3 | rnielsen | Health Dept. | 1082714 |
Health Dept. | Original | / | 6/20/2018 | HEALTHDEPT | HEALTHDEPT | | Aparikh | Health Dept. | 1081597 |
CSU Contract Admin. | Original | A | 6/15/2018 | CSUAPPSPRM | CSUAPPSPRM | Development Charges and Fees Paid 6/15/18.ZJS | zshearer | CSU Contract Admin. | 1080330 |
CSU Contract Admin. | Original | / | 6/15/2018 | CSUAPPSPRM | CSUAPPSPRM | | zshearer | CSU Contract Admin. | 1080326 |
Hazmat | Original | A | 5/24/2018 | CSFIRE | CSFIRE | Plan approved. Please read approval comments. (see full review) | smanning | Hazmat | 1072296 |
CO Springs Fire | Original | A | 5/23/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1071902 |
CSU Contract Admin. | Original | D | 5/23/2018 | CSUAPPSPRM | CSUAPPSPRM | CWMSF's approved. Requires irrigation service address assignment and payment of charges/fees. ZJS | zshearer | CSU Contract Admin. | 1071626 |
City Engr | Original | A | 5/21/2018 | JDAGNILLO | JDAGNILLO | | | City Engr | 1070991 |
CO Springs DRE | Original | A | 5/16/2018 | MSCHULTZ | MSCHULTZ | (see full review) | | CO Springs DRE | 1069288 |
Zoning/Planning | Original | / | 5/15/2018 | MSCHULTZ | MSCHULTZ | In Current Review by MSCHULTZ | | Zoning/Planning | 1068962 |
Water Division | Original | A | 5/14/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. RDS | rsolberg | Water Division | 1068205 |
Waste Water Div | Original | A | 5/14/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. RDS | rsolberg | Waste Water Div | 1068204 |
Plumbing | Original | A | 5/14/2018 | TCRIPPEN | TCRIPPEN | approved as noted on plans A separate line with back flow protection shall be required for this type of install , the mop sink shall not be use for chemical dispensing.
. | | Plumbing | 1068152 |
Electronic Plan | Original | / | 5/14/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1068130 |
Construction | Original | A | 5/14/2018 | MICHAELA | MICHAELA | | | Construction | 1067977 |
Enumeration | Original | A | 5/14/2018 | BRENT | BRENT | | | Enumeration | 1067922 |
Resubmittal 2 | Original | / | 5/14/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1067903 |
CO Springs DRE | Original | D | 4/1/2018 | MSCHULTZ | MSCHULTZ | Dublin Commons Filing No 4 has been recorded; however applicant needs to upload the approved development plan (DP) set with the construction plans. Approved DP can be downloaded from City website www.coloradosprings.gov/ldrs; enter file number AR DP 16-00821 (see full review) | | CO Springs DRE | 1052695 |
Health Dept. | Original | A | 3/29/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | rnielsen | Health Dept. | 1051804 |
Health Dept. | Original | / | 3/29/2018 | HEALTHDEPT | HEALTHDEPT | | rnielsen | Health Dept. | 1051797 |
Electrical | Original | A | 12/12/2017 | SHELBY | SHELBY | | | Electrical | 1020766 |
Hazmat | Original | D | 12/12/2017 | CSFIRE | CSFIRE | Hazmat disapproved. Please read disapproval comments; more details required for CO2 detection system. (see full review) | smanning | Hazmat | 1020582 |
City Engr | Original | D | 12/11/2017 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Water Resources Engineering Division approved Grading and Erosion Control Plan in the building permit set. jad | | City Engr | 1020301 |
CSU Contract Admin. | Original | D | 12/11/2017 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form has not yet been received. Payment of development charges/fees due. LMP | lmpope | CSU Contract Admin. | 1020032 |
CO Springs Fire | Original | D | 12/8/2017 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1019870 |
Health Dept. | Original | D | 12/7/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. RNielsen 575-8965 | rnielsen | Health Dept. | 1019493 |
Water Division | Original | D | 12/6/2017 | CSUREVIEW | CSUREVIEW | Previous comment has not been addressed: "Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions." Attach a copy of the approved plans into the plan set. JPN | jnoble | Water Division | 1019360 |
Waste Water Div | Original | D | 12/6/2017 | CSUREVIEW | CSUREVIEW | Previous comment has not been addressed: "Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions." Attach a copy of the approved plans into the plan set. JPN | jnoble | Waste Water Div | 1019359 |
Gas/Elec. Utils | Original | A | 12/6/2017 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service/transformer locations. Please submit the Electric Load Data Form, the Application for Gas & Electric Line Extension, and the Application for Gas Service Line Approval. The forms can be found at: https://www.csu.org/Pages/development-files-forms.aspx Contact the CSU Field Engineer, J. C. Butterfield (719-668-5618) to coordinate the gas and electric services. JPN | jnoble | Gas/Elec. Utils | 1019355 |
CO Springs DRE | Original | D | 12/6/2017 | MSCHULTZ | MSCHULTZ | The applicant needs to record the Dublin Commons Filing No 4 subdivision plat, that process should be started with Lois Ruggera (719-385-5056). Additionally, the applicant needs to include an APPROVED copy of the development plan, a copy has been provided to Ryan Robinson (on 12-7-17). If there are any questions please feel free to contact me at 719-385-5089. (see full review) | | CO Springs DRE | 1018981 |
Zoning/Planning | Original | / | 12/6/2017 | MSCHULTZ | MSCHULTZ | In Current Review by MSCHULTZ | | Zoning/Planning | 1018962 |
Plumbing | Original | D | 12/6/2017 | TCRIPPEN | TCRIPPEN | Need an water pipe size analysis data on plans can add it to a separate box marked plumbing, Review plans for added notes no changes required just a heads up thank you. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1018960 |
Mechanical | Original | A | 12/5/2017 | JUSTINC | JUSTINC | | | Mechanical | 1017752 |
Construction | Original | D | 12/5/2017 | MICHAELA | MICHAELA | Code study form is not in the tab - please resubmit (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1017674 |
Enumeration | Original | D | 12/4/2017 | BRENT | BRENT | the documents submitted as the code study form are not the code study form. The address shown on the first page of the architectural plans is incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1017449 |
Resubmittal 1 | Original | / | 12/4/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1017303 |
City Engr | Original | D | 10/6/2017 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering Division approved Grading and Erosion Control Plan in the building permit set. jad | | City Engr | 1001713 |
Hazmat | Original | D | 10/4/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1001086 |
CO Springs Fire | Original | D | 10/4/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1001084 |
Plumbing | Original | D | 10/2/2017 | TCRIPPEN | TCRIPPEN | The trash drain shall go to the grease interceptor and add freeze protection. or remove not required (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1000219 |
Electronic Plan | Original | / | 10/2/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1000175 |
Water Division | Original | D | 9/29/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Water Division | 999867 |
Waste Water Div | Original | D | 9/29/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Waste Water Div | 999866 |
Gas/Elec. Utils | Original | D | 9/29/2017 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views to make sure gas regulator vent is at least 3ft away from any electric meter socket and openings like windows, doors, and garage doors. Contact the CSU Field Engineer, J. C. Butterfield (719-668-5618) to coordinate the gas and electric services. mjg | mgackle | Gas/Elec. Utils | 999865 |
Electrical | Original | D | 9/29/2017 | SHELBY | SHELBY | Show service lateral size, type, and quantity on one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 999786 |
Health Dept. | Original | D | 9/28/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. RNielsen | rnielsen | Health Dept. | 999601 |
CO Springs DRE | Original | D | 9/28/2017 | MSCHULTZ | MSCHULTZ | Both the development plan and final plat have not been approved (nor the plat recorded); please complete these applications and add the approved development plan to this construction set. Reminder: A final irrigation plan needs to be submitted to Connie Perry, Landscape Architect by separate application. (see full review) | | CO Springs DRE | 999374 |
Zoning/Planning | Original | / | 9/27/2017 | MSCHULTZ | MSCHULTZ | In Current Review by MSCHULTZ | | Zoning/Planning | 999213 |
Mechanical | Original | D | 9/27/2017 | JUSTINC | JUSTINC | Provide ventilation schedule per 09' IMC 403.3 Appears only AC-1 is serving kitchen with 1380 CFM of OSA how providing remainder must be within 10% = or - of what is being exhausted. Provide additional interlock schedule associated with shutdown of hoods for fire or smoke No alternates are allowed in permit set drawings. Only indicate scope of work to be installed in this permit.
Mechanical review incomplete
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 999037 |
CSU Contract Admin. | Original | D | 9/27/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of utility charges and fees. Please contact Utilities Development Services at 719-668-8111 or questions, assistance or to request an estimate. MKL
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | mkluke | CSU Contract Admin. | 999036 |
Construction | Original | D | 9/26/2017 | MICHAELA | MICHAELA | Provide architectural site plan with dimensions to property lines. Add outdoor dining occupant load to total for plumbing fixture count Fill out description of exterior wall construction - Provide 18" clearance to combustibles at type 1 hood Kitchen and play area are not accessory use - correct code study form
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 998828 |
Electronic Plan | Original | / | 9/26/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 998752 |
Enumeration | Original | D | 9/25/2017 | BRENT | BRENT | The address for this parcel is 5905 Dublin Blvd. and this should be shown on the code study form. The tax schedule number shown on the code study form is incorrect. Final plat for this parcel has no yet been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. Tax schedule number and legal description to change after plat. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 998154 |
Floodplain | Original | N | 9/25/2017 | BRENT | BRENT | | | Floodplain | 998151 |
Construction | Original | / | 9/22/2017 | BECKYA | BECKYA | Overtime approved for Construction by per Carlos | | Construction | 997994 |
Plumbing | Original | / | 9/22/2017 | BECKYA | BECKYA | Overtime approved for Plumbing by per Carlos | | Plumbing | 997992 |
Mechanical | Original | / | 9/22/2017 | BECKYA | BECKYA | Overtime approved for Mechanical by per Carlos | | Mechanical | 997991 |
Electrical | Original | / | 9/22/2017 | BECKYA | BECKYA | Overtime approved for Electrical by per Carlos | | Electrical | 997990 |