Mechanical | Splice 06/30/22 | A | 7/1/2022 | JUSTINC | JUSTINC | Revised to paper plan | | Mechanical | 1707565 |
Mechanical | Splice 06/30/22 | D | 7/1/2022 | JUSTINC | JUSTINC | The proposed changes are okay, however the PDF is locked and will not allow the approval stamp to be added. Please resubmit with unlocked PDF.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1707440 |
Construction | Splice 05/27/22 | A | 6/17/2022 | CGIECK | CGIECK | Truss and shop drawings ok | | Construction | 1699985 |
Resubmittal 1 | Splice 05/27/22 | / | 6/17/2022 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1699960 |
Construction | Splice 05/27/22 | D | 5/27/2022 | LBENNETT | LBENNETT | Please provide a truss framing plan with shop drawing review stamp (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1689441 |
Scanned/Finished Bin | Splice 05/03/22 | / | 5/5/2022 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1677287 |
To Be Scanned Bin | Splice 05/03/22 | / | 5/3/2022 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1675425 |
Plan Coordinator | Splice 05/03/22 | / | 5/3/2022 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1675207 |
Plumbing | Splice 05/03/22 | A | 5/3/2022 | TCRIPPEN | TCRIPPEN | Approved new splice see clouds. | | Plumbing | 1675204 |
Plumbing | Splice 05/03/22 | / | 5/3/2022 | | BRITNEY | Location = Plumbing by BRITNEYP | | Plumbing | 1675163 |
Out to Review | Splice 05/03/22 | / | 5/3/2022 | BRITNEY | BRITNEY | Dan leaving P splice for Tim | | Out to Review | 1675161 |
Scanned/Finished Bin | Splice 11/16/21 | / | 11/17/2021 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1595214 |
To Be Scanned Bin | Splice 11/16/21 | / | 11/16/2021 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1595045 |
Plan Coordinator | Splice 11/16/21 | / | 11/16/2021 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1594920 |
Mechanical | Splice 11/16/21 | A | 11/16/2021 | TCRIPPEN | TCRIPPEN | Approved revised gas and mini slits | | Mechanical | 1594877 |
Mechanical | Splice 11/16/21 | / | 11/16/2021 | | RITA | Location = Mechanical by RITA | | Mechanical | 1594843 |
Out to Review | Splice 11/03/21 | / | 11/4/2021 | AMYP | AMYP | Dan has original splice plan | | Out to Review | 1589003 |
Scanned/Finished Bin | Splice 11/03/21 | / | 11/4/2021 | | SCANNING | Location = Scanned/Finished Bin by SCANNING, CUSTOMER TOOK ORIGINALS | | Scanned/Finished Bin | 1589004 |
Construction | Splice 11/03/21 | A | 11/3/2021 | GITA | GITA | | | Construction | 1588341 |
Mechanical | Splice 11/03/21 | A | 11/3/2021 | TCRIPPEN | TCRIPPEN | Approved new splice revised gas line. | | Mechanical | 1588315 |
Out to Review | Splice 11/03/21 | / | 11/3/2021 | VERONIKAP | VERONIKAP | dan | | Out to Review | 1588302 |
Mechanical | Splice 07/14/21 | A | 8/13/2021 | TCRIPPEN | TCRIPPEN | Approved. | | Mechanical | 1546829 |
Electrical | Splice 07/14/21 | A | 8/12/2021 | BERTHA | BERTHA | Added Panel C and Panel D to scope. | | Electrical | 1545888 |
Electronic Plan | Splice 07/14/21 | / | 8/12/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1545875 |
Resubmittal 3 | Splice 07/14/21 | / | 8/11/2021 | NICKH | NICKH | Resubmittal #3 | | Resubmittal 3 | 1545487 |
Electrical | Splice 07/14/21 | D | 8/3/2021 | BERTHA | BERTHA | Clarify Panel C and D buss rating - 60A, 100A or 125A
Paper plans sent to Plan Coordinator. - plans located in finish bin
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1540913 |
Electronic Plan | Splice 07/14/21 | / | 8/3/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1540793 |
Mechanical | Splice 07/14/21 | D | 8/3/2021 | TCRIPPEN | TCRIPPEN | Disapproved mechanical ventilation required for each room not having natural ventilation directly to the outdoors, show condensation line and sizes and termination locations, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1540791 |
Plumbing | Splice 07/14/21 | A | 7/29/2021 | TCRIPPEN | TCRIPPEN | Approved,See paper plan | | Plumbing | 1538653 |
Electronic Plan | Splice 07/14/21 | / | 7/29/2021 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1538551 |
Resubmittal 2 | Splice 07/14/21 | / | 7/29/2021 | SCANNING | SCANNING | Resubmittal #2 This is paper resubittal | | Resubmittal 2 | 1538550 |
Plumbing | Splice 07/14/21 | D | 7/29/2021 | TCRIPPEN | TCRIPPEN | This plan was disapproved and now is lock please resubmit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1538349 |
Mechanical | Splice 07/14/21 | D | 7/29/2021 | TCRIPPEN | TCRIPPEN | This plan was disapproved and now is lock please resubmit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1538348 |
Electrical | Splice 07/14/21 | D | 7/28/2021 | BERTHA | BERTHA | No new plans were submitted. Submit revised plans, comply with previous review comment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1538124 |
Electronic Plan | Splice 07/14/21 | / | 7/28/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1538120 |
Resubmittal 1 | Splice 07/14/21 | / | 7/28/2021 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1537872 |
Electrical | Splice 07/14/21 | D | 7/14/2021 | BERTHA | BERTHA | Provide complete revisions - one line, site plan, etc.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1530394 |
Plumbing | Splice 07/14/21 | D | 7/14/2021 | SHANEN | SHANEN | Remove all existing clouds and cloud only the revisions that pertain to this splice request per PPRBD plan review requirements. Revise water isometric to reflect the relocated water heater. Mechanical reviewer comments must be addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1530158 |
Electronic Plan | Splice 07/14/21 | / | 7/14/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1530147 |
Mechanical | Splice 07/14/21 | D | 7/14/2021 | TCRIPPEN | TCRIPPEN | Remove old clouds per splice policy, show water heater relocation and revised gas line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1530140 |
Electronic Plan | Splice 07/14/21 | / | 7/14/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1530120 |
Fountain Fire | Splice 03/10/21 | A | 3/19/2021 | FNTNFIRE | FNTNFIRE | Automatic Sprinkler Company will need to resubmit plans with calculations added for system requirements. Area too large for red line markings. | mgates | Fountain Fire | 1472886 |
Construction | Splice 03/10/21 | A | 3/12/2021 | MICHAELA | MICHAELA | | | Construction | 1470139 |
Out to Review | Original | / | 10/14/2019 | SCANNING | SCANNING | | | Out to Review | 1245483 |
To Be Scanned Bin | Original | / | 10/10/2019 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1244828 |
Fountain Fire | Original | A | 10/10/2019 | GITA | GITA | Per MFG see plan label | | Fountain Fire | 1244827 |
Health Dept. | Original | N | 10/10/2019 | HEALTHDEPT | HEALTHDEPT | Not applicable. | abrannon | Health Dept. | 1244787 |
Fountain Zoning | Original | A | 10/10/2019 | ZONINGF | ZONINGF | OK to approve. KM | KMartinez | Fountain Zoning | 1244729 |
Zoning/Planning | Original | / | 10/10/2019 | | ZONINGF | Location = Zoning/Planning by ZONINGF | KMartinez | Zoning/Planning | 1244723 |
Fountain Waste Water | Original | A | 10/10/2019 | RITA | RITA | Per Candy Cooper 10-08-19 | | Fountain Waste Water | 1244699 |
Fountain Water | Original | A | 10/10/2019 | RITA | RITA | Candy Cooper 10-08-19 | | Fountain Water | 1244698 |
Electrical | Original | A | 6/25/2019 | BERTHA | BERTHA | Re-approved - outdated RBD stamps | | Electrical | 1206227 |
Construction | Original | A | 6/25/2019 | LBENNETT | LBENNETT | re-stamped; under 2009 code cycle | | Construction | 1206205 |
Enumeration | Original | A | 6/25/2019 | BRENT | BRENT | | | Enumeration | 1206200 |
Plumbing | Original | A | 6/25/2019 | TCRIPPEN | TCRIPPEN | re stamp to the 2019 still under 2009 code okay | | Plumbing | 1206195 |
Mechanical | Original | A | 6/25/2019 | TCRIPPEN | TCRIPPEN | re stamp to the 2019 still under 2009 code okay | | Mechanical | 1206194 |
Out to Review | Original | / | 2/21/2018 | BECKYA | BECKYA | picked up by Dan 317-563-2579 - Dan walking to get restamped 6/25/2019 | | Out to Review | 1039431 |
Finished Bin | Original | / | 2/20/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1039290 |
Plan Coordinator | Original | / | 2/20/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1039186 |
Plumbing | Original | A | 2/20/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1039184 |
Plumbing | Original | / | 2/16/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1038590 |
Plan Coordinator | Original | / | 2/16/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1038466 |
Construction | Original | A | 2/16/2018 | MICHAELA | MICHAELA | | | Construction | 1038463 |
Construction | Original | / | 2/16/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1038458 |
Construction | Original | / | 2/16/2018 | | GITA | Location = Construction by GITA | | Construction | 1038380 |
Resubmittal 4 | Original | / | 2/16/2018 | GITA | GITA | Resubmittal #4 | | Resubmittal 4 | 1038378 |
Finished Bin | Original | / | 2/8/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1035949 |
Plan Coordinator | Original | / | 2/8/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1035941 |
Plumbing | Original | D | 2/8/2018 | TCRIPPEN | TCRIPPEN | missing Fixture schedule missing pipe material schedule. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1035940 |
Plumbing | Original | / | 2/7/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1035764 |
Plan Coordinator | Original | / | 2/7/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1035754 |
Mechanical | Original | A | 2/7/2018 | JUSTINC | JUSTINC | Provide radiation damper at supply air location in mechanical room. Protect all penetrations in mechanical room for type of construction. | | Mechanical | 1035753 |
Construction | Original | D | 2/7/2018 | MICHAELA | MICHAELA | Provide horsepower and PSI for boilers - see table 508.2.5 Provide trusses loaded for additional weight of mechanical equipment in attic Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1035743 |
Mechanical | Original | / | 2/7/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1035662 |
Mechanical | Original | / | 2/7/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1035621 |
Plan Coordinator | Original | / | 2/7/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1035610 |
Construction | Original | A | 2/7/2018 | MICHAELA | MICHAELA | | | Construction | 1035608 |
Construction | Original | / | 2/7/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1035572 |
Construction | Original | / | 2/7/2018 | | RITA | Location = Construction by RITA | | Construction | 1035548 |
Resubmittal 3 | Original | / | 2/7/2018 | RITA | RITA | Resubmittal #3 | | Resubmittal 3 | 1035547 |
Finished Bin | Original | / | 1/24/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1031484 |
Plan Coordinator | Original | / | 1/24/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1031478 |
Plumbing | Original | D | 1/24/2018 | TCRIPPEN | TCRIPPEN | Missing sizes on water lines missing pipe material schedule for this job what can be used,pipe size does not match calculation (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1031477 |
Plumbing | Original | / | 1/24/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1031244 |
Plan Coordinator | Original | / | 1/24/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1031220 |
Mechanical | Original | D | 1/24/2018 | JUSTINC | JUSTINC | Propane gas indicated in unit heater schedule? Gas plan indicates natural gas? No ventilation shown for kennel areas per 09' IMC 403.3 Specialty shops animal areas Indicate washer dryer locations, vent routing, termination, makeup air. Indicate condensate routing, pipe sizes, termination locations per 09' IMC 307 See sheet and general notes revise to correct PPRBD code years. and revise incorrect code references. Indicate on plan locations of boiler and water heater. Indicate vent routing and how providing required combustion air per 09' IFGC 304. Clarify intent at kennel areas it appears that the louvers and EF fans are not located on exterior walls? Only transfer air? Per 09' IMC 501.2 all mechanical exhaust is to discharge outdoors. Provide site plan indicating gas meter location and accurate pipe distance or accurately indicate gas meter distance for review. Provide typical gas connection detail Verify gas calculation indicated incorrect code reference indicated per your calculation. Indicate thermostat locations for in floor heat system.
MECHANICAL REVIEW PENDING DESIGNERS RESPONSES NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1031219 |
Mechanical | Original | / | 1/23/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1030945 |
Mechanical | Original | / | 1/23/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1030788 |
Plan Coordinator | Original | / | 1/23/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1030767 |
Construction | Original | D | 1/23/2018 | MICHAELA | MICHAELA | RETURN MARKED UP PAGES WITH NEXT REVIEW Occupant load must be accounted for in all areas - see page A-1 for requirements Provide a detail of fire wall intersection with exterior wall Provide a UL listing (or equal) for the fire rated wall assembly Indicate compliance with IBC sec 1210 for floor and wall finishes in the toilet rooms Provide structural plans without an X through the seal Provide a roof framing plan using the provided truss engineering - must be labeled accordingly No walk-through
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1030766 |
Construction | Original | / | 1/22/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1030727 |
Construction | Original | / | 1/22/2018 | | GITA | Location = Construction by GITA | | Construction | 1030545 |
Resubmittal 2 | Original | / | 1/22/2018 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 1030544 |
Electrical | Original | A | 1/22/2018 | BERTHA | BERTHA | | | Electrical | 1030540 |
Out to Review | Original | / | 11/16/2017 | BECKYA | BECKYA | picked up by Dan 317-563-2579 | | Out to Review | 1013677 |
Finished Bin | Original | / | 11/16/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1013640 |
Health Dept. | Original | N | 11/16/2017 | HEALTHDEPT | HEALTHDEPT | Not applicable. AP 719-578-3278 | Aparikh | Health Dept. | 1013534 |
Health Dept. | Original | / | 11/9/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1012000 |
Plan Coordinator | Original | / | 11/9/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1011918 |
Mechanical | Original | D | 11/9/2017 | JUSTINC | JUSTINC | Clarify return air paths Relocate all gas associated work to (M) sheets for review Clearly indicate interlocks. Tag each fan and louver with motorized damper to clearly indicate which louver is to interlock with associated fan. Provide louver schedule How exhausting bathroom? How providing makeup air to bathroom? Clarify equipment? Shown as RTU's indicated as split systems? If RTU clarify economizer duct?
MECHANICAL REVIEW STOPPED MECHANICAL REVIEW INCOMPLETE NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1011917 |
Mechanical | Original | / | 11/9/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1011870 |
Plumbing | Original | D | 11/9/2017 | TCRIPPEN | TCRIPPEN | need an approved occupant load for fixture count, gas piping and related items to be on the M -pages per our web site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1011797 |
Mechanical | Original | / | 11/8/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1011291 |
Plan Coordinator | Original | / | 11/8/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1011238 |
Electrical | Original | D | 11/8/2017 | SHELBY | SHELBY | Please address previous review comments 1, 2, and 3. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1011235 |
Electrical | Original | / | 11/8/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1011206 |
Electrical | Original | / | 11/7/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1011100 |
Plan Coordinator | Original | / | 11/7/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1010986 |
Construction | Original | D | 11/7/2017 | MICHAELA | MICHAELA | Provide occupant load calculations - include mezzanine Provide sq. footage of mezzanine and verify no more than 1/3 sq. footage of area served Provide elevations of toilet room showing accessible elements Provide details showing full compliance with sec. 706 for fire wall Provide details for sliding doors in fire wall - must be 90 minute and self closing Revise door schedule for rated doors Storage under stairs must have 1-hr. protection - provide assemblies Provide a roof framing page with layout labeled per truss engineering Truss engineering not compliant with current adopted code No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1010985 |
Construction | Original | / | 11/7/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1010861 |
Construction | Original | / | 11/6/2017 | | GITA | Location = Construction by GITA | | Construction | 1010417 |
Resubmittal 1 | Original | / | 11/6/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1010414 |
Out to Review | Original | / | 10/27/2017 | BECKYA | BECKYA | picked up by Dan 317-563-2579 | | Out to Review | 1007863 |
Finished Bin | Original | / | 10/26/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1007279 |
Plan Coordinator | Original | / | 10/26/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1007245 |
Construction | Original | D | 10/26/2017 | MICHAELA | MICHAELA | Review stopped - No Code Study form, no soils report, no IECC certificate FYI Look at allowable area calculations - sprinkler increase? No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1007244 |
Construction | Original | / | 10/25/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1006968 |
Construction | Original | / | 10/25/2017 | | RITA | Location = Construction by RITA | | Construction | 1006921 |
Electrical | Original | D | 10/4/2017 | SHELBY | SHELBY | 1. Remove parallel neutral( ground) from service lateral. 2. Configure service per Utility standards. 3. GEC for water sized incorrectly. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1001321 |
Enumeration | Original | A | 10/4/2017 | BRENT | BRENT | | | Enumeration | 1001284 |
Floodplain | Original | N | 10/4/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6536002004) | | Floodplain | 1001270 |