Hazmat | Original | A | 1/17/2018 | CSFIRE | CSFIRE | Hazmat approved. No inspection required. However, separate submittal submitted for fuel tank and shall be inspected as part of that review. | smanning | Hazmat | 1029211 |
Electrical | Original | A | 1/10/2018 | SHELBY | SHELBY | | | Electrical | 1027459 |
Resubmittal 4 | Original | / | 1/10/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1027413 |
CO Springs DRE | Original | A | 1/9/2018 | RTEIXEIRA2 | RTEIXEIRA2 | APPROVED BY ZONING FOR THE INSTALLATION OF A BACKUP GENERATOR, BOLLARDS, AND FENCED ENCLOSURE FOR UNMANNED EQUIPMENT SHELTER. (see full review) | | CO Springs DRE | 1027223 |
Electrical | Original | D | 1/8/2018 | SHELBY | SHELBY | 1. Please address previous review comments. Panel B load summary shows 172 amps on a 100 amp panel. Provide site plan showing the location of electrical gear in this scope. 2. Consultation is available 719 659 1182 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1026928 |
Hazmat | Original | D | 1/8/2018 | CSFIRE | CSFIRE | SEPARATE HAZARDOUS MATERIAL PERMITS REQUIRED: The following Processes/Operations require separate permits through the Division of the Fire Marshal, 375 Printers Parkway, Colorado Springs, CO 80910:
AF- Aboveground fuel tank for generator
Please submit a separate permit application for the generator aboveground fuel tank directly to the Division of the Fire Marshal. This submittal must have two hardcopies and include all required information including tank location with distances, generator cutsheet and information, and any other related information.
Please contact the hazmat plan reviewer, Stefan Manning, at smanning@springsgov.com to notify that you understand this requirement and will submit a separate permit. The plan will remain disapproved until notification is received.
For submittal and permitting information regarding these permits, please visit http://bit.ly/OtherHazmat (see full review) | smanning | Hazmat | 1026724 |
Water Division | Original | N | 1/5/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Water Division | 1026218 |
Waste Water Div | Original | N | 1/5/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Waste Water Div | 1026217 |
Zoning/Planning | Original | / | 1/4/2018 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 1026067 |
Resubmittal 3 | Original | / | 1/4/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1026024 |
Hazmat | Original | D | 1/3/2018 | CSFIRE | CSFIRE | SEPARATE HAZARDOUS MATERIAL PERMITS REQUIRED: The following Processes/Operations require separate permits through the Division of the Fire Marshal, 375 Printers Parkway, Colorado Springs, CO 80910:
AF- Aboveground fuel tank for generator
Please submit a separate permit application for the generator aboveground fuel tank directly to the Division of the Fire Marshal. This submittal must include all required information including tank location with distances, generator cutsheet and information, and any other related information.
Please contact the hazmat plan reviewer, Stefan Manning, at smanning@springsgov.com to notify that you understand this requirement and will submit a separate permit. The plan will remain disapproved until notification is received.
For submittal and permitting information regarding these permits, please visit http://bit.ly/OtherHazmat | smanning | Hazmat | 1025533 |
CO Springs Fire | Original | N | 12/22/2017 | CSFIRE | CSFIRE | Submitted By: Withee, Doreen E | csfdit | CO Springs Fire | 1023751 |
CO Springs Fire | Original | N | 12/22/2017 | CSFIRE | CSFIRE | Submitted By: Withee, Doreen E | csfdit | CO Springs Fire | 1023750 |
CO Springs DRE | Original | D | 12/20/2017 | LTHELEN | LTHELEN | insert approved plan set AR MA 00-00566-MM04 (see full review) | | CO Springs DRE | 1023061 |
Mechanical | Original | N | 12/19/2017 | DALEH | DALEH | diesel ,,,,no gas piping | | Mechanical | 1022538 |
Electrical | Original | D | 12/18/2017 | SHELBY | SHELBY | Please address all previous review comments. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1022366 |
Water Division | Original | D | 12/18/2017 | CSUREVIEW | CSUREVIEW | Previous comments not addressed. Provide a copy of the approved development plan. JPN | jnoble | Water Division | 1022177 |
Waste Water Div | Original | D | 12/18/2017 | CSUREVIEW | CSUREVIEW | Previous comments not addressed. Provide a copy of the approved development plan. JPN | jnoble | Waste Water Div | 1022176 |
Zoning/Planning | Original | / | 12/18/2017 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 1021995 |
Enumeration | Original | A | 12/15/2017 | AMY | AMY | PAGES WERE EDITED BASED ON MY COMMENTS FROM 11-6-17. WORK IS FOR THE SHELTER ONLY | | Enumeration | 1021887 |
Resubmittal 2 | Original | / | 12/15/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1021723 |
Electrical | Original | D | 11/27/2017 | SHELBY | SHELBY | 1. Panel B is overloaded. Review load summary. 2. Show all existing, relocated ,and new electrical equipment on site plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1015513 |
Water Division | Original | D | 11/16/2017 | CSUREVIEW | CSUREVIEW | Previous comments not addressed. Provide a copy of the approved development plan. JPN | jnoble | Water Division | 1013530 |
Waste Water Div | Original | D | 11/16/2017 | CSUREVIEW | CSUREVIEW | Previous comments not addressed. Provide a copy of the approved development plan. JPN | jnoble | Waste Water Div | 1013528 |
CO Springs DRE | Original | D | 11/15/2017 | RTEIXEIRA2 | RTEIXEIRA2 | DISAPPROVED. PROVIDE A COPY OF THE STAMPED APPROVED SET OF PLANS (FILE NO. AR MA 00-00566-MM01) WITH THE BUILDING PERMIT SET OF PLANS. (see full review) | | CO Springs DRE | 1013371 |
Mechanical | Original | D | 11/15/2017 | DALEH | DALEH | provide complete mechanical drawings showing mechanical scope for back up generator IE gas piping venting etc.. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1013070 |
Hazmat | Original | D | 11/14/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1013009 |
CO Springs Fire | Original | D | 11/14/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1013008 |
Zoning/Planning | Original | / | 11/14/2017 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 1013002 |
Construction | Original | N | 11/14/2017 | SHELLEY | SHELLEY | Fence <7', no permit required for equipment pad. | | Construction | 1012824 |
Enumeration | Original | D | 11/14/2017 | AMY | AMY | SEE NOTES 11-6-17 NOTHING CHANGED (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1012667 |
Electronic Plan | Original | / | 11/14/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1012660 |
Resubmittal 1 | Original | / | 11/14/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1012523 |
Plan Coordinator | Original | D | 11/13/2017 | SHELLEY | SHELLEY | Disapprove all remaining departments to allow plan to be resubmitted - PLANS NOT LEGIBLE. NEED TO UPLOAD NEW DOCUMENTS. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1012295 |
Electrical | Original | D | 11/9/2017 | SHELBY | SHELBY | Text is indecipherable. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1011933 |
Mechanical | Original | D | 11/7/2017 | DALEH | DALEH | need legible plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1011001 |
Electronic Plan | Original | / | 11/7/2017 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1010998 |
Water Division | Original | D | 11/7/2017 | CSUREVIEW | CSUREVIEW | Provide an approved development plan. RDS | rsolberg | Water Division | 1010790 |
Waste Water Div | Original | D | 11/7/2017 | CSUREVIEW | CSUREVIEW | Provide an approved development plan. RDS | rsolberg | Waste Water Div | 1010789 |
CO Springs DRE | Original | D | 11/6/2017 | MBINGMAN | MBINGMAN | MRB per RMT. Please assign to RMT at resubmittal.
Provide a copy of the stamped approved development plan. (see full review) | | CO Springs DRE | 1010608 |
Zoning/Planning | Original | / | 11/6/2017 | GSANDERS | GSANDERS | In Current Review by GSANDERS | | Zoning/Planning | 1010606 |
Construction | Original | D | 11/6/2017 | SHELLEY | SHELLEY | Provide legible plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1010565 |
Enumeration | Original | D | 11/6/2017 | AMY | AMY | ADDRESS TO EQUIPMENT SHELTER IS 8294 VOYAGER PKWY, ANTENNA FOR AT &T IS 8280 VOYAGER PKWY. IF ALL THE WORK IS FOR THE SHELTER CHANGE THE ADDRESSING ON ALL PAGES TO 8294 VOYAGER PKWY.
THERE IS AN OPEN MECHANICAL PERMIT FOR AT &T AT 8280 VOYAGER PKWY THAT NEEDS TO BE RE-OPEN AND INSPECTED-PERMIT NUMBER IS K16430. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1010301 |
Electronic Plan | Original | / | 11/6/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1010291 |
Floodplain | Original | N | 11/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6305104004) | | Floodplain | 1008988 |