Construction | Splice 12/20/19 | A | 12/20/2019 | BPHILLIPS | BPHILLIPS | Revised Comcheck. | | Construction | 1269185 |
Out to Review | Splice 12/20/19 | / | 12/20/2019 | GITA | GITA | | | Out to Review | 1269179 |
Mechanical | Splice 11/07/19 | A | 11/15/2019 | TCRIPPEN | TCRIPPEN | okay see notes on plan set | | Mechanical | 1257219 |
Resubmittal 1 | Splice 11/07/19 | / | 11/15/2019 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1257194 |
Mechanical | Splice 11/07/19 | D | 11/7/2019 | TCRIPPEN | TCRIPPEN | no clouds no narrative ? please provide both. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1254461 |
High Pile | Original | A | 5/2/2018 | GITA | GITA | | | High Pile | 1063825 |
Hazmat | Original | A | 5/2/2018 | GITA | GITA | | | Hazmat | 1063824 |
County Fire | Original | A | 5/2/2018 | GITA | GITA | | | County Fire | 1063823 |
Palmer Lake Zoning | Original | A | 5/2/2018 | GITA | GITA | | | Palmer Lake Zoning | 1063822 |
Electrical | Original | A | 4/24/2018 | BERTHA | BERTHA | | | Electrical | 1060969 |
Plumbing | Original | A | 4/24/2018 | JOEL | JOEL | | | Plumbing | 1060849 |
Electrical | Original | D | 4/24/2018 | BERTHA | BERTHA | Provide classified locations for Major Repair Garage.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1060840 |
Out to Review | Original | / | 4/9/2018 | RITA | RITA | BJ 719-6510949 | | Out to Review | 1055345 |
Finished Bin | Original | / | 4/9/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1055217 |
Plan Coordinator | Original | / | 4/9/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1055160 |
Plumbing | Original | D | 4/9/2018 | TCRIPPEN | TCRIPPEN | These comments still not addressed, Add sizes to water entry detail on page P 0,1, remove general note 6 and add PEX. piping note, Provide an water piping size analysis data on plans, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1055158 |
Plumbing | Original | / | 4/9/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1055154 |
Plumbing | Original | / | 4/6/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1055045 |
Plan Coordinator | Original | / | 4/6/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1055006 |
Mechanical | Original | A | 4/6/2018 | JUSTINC | JUSTINC | | | Mechanical | 1055005 |
Mechanical | Original | / | 4/6/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1054954 |
Mechanical | Original | / | 4/6/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1054942 |
Plan Coordinator | Original | / | 4/6/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1054919 |
Electrical | Original | D | 4/6/2018 | BERTHA | BERTHA | Comply with previous review comment #2. Provide classification for garage. Minor or Major.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1054917 |
Electrical | Original | / | 4/6/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1054834 |
Electrical | Original | / | 4/3/2018 | | NELIDA | Location = Electrical by NELIDA | | Electrical | 1053325 |
Resubmittal 2 | Original | / | 4/3/2018 | NELIDA | NELIDA | Resubmittal #2 4/3/18 | | Resubmittal 2 | 1053324 |
Out to Review | Original | / | 2/20/2018 | JANE | JANE | david 719 330 3455 | | Out to Review | 1039304 |
Finished Bin | Original | / | 1/26/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1032300 |
Plumbing | Original | D | 1/26/2018 | TCRIPPEN | TCRIPPEN | comments not addressed (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1032297 |
Plumbing | Original | / | 1/26/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1032191 |
Plan Coordinator | Original | / | 1/26/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1032040 |
Mechanical | Original | D | 1/26/2018 | JUSTINC | JUSTINC | Verify combustion air opening indicated on plan. Per 09' IFGC 304.5.3.1 (2) openings are required each within 12" of ceiling and 12" of floor. Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Ventilation schedule is to be located on plan pages not on 8 1/2" x 11" Indicate warehouse storage ventilation per 09' IMC 403.3 (STORAGE) "Warehouse" on ventilation schedule
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1032039 |
Mechanical | Original | / | 1/25/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1031911 |
Mechanical | Original | / | 1/24/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1031540 |
Plan Coordinator | Original | / | 1/24/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1031513 |
Electrical | Original | D | 1/24/2018 | BERTHA | BERTHA | 1. Provide footprint showing all electrical service equipment and disconnects serving the structure. 2. Comply 511.3 - provide classification for garage.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1031510 |
Electrical | Original | / | 1/22/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1030483 |
Plan Coordinator | Original | / | 1/22/2018 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1030475 |
Construction | Original | A | 1/22/2018 | BPHILLIPS | BPHILLIPS | | | Construction | 1030474 |
Construction | Original | / | 1/19/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1030437 |
Construction | Original | / | 1/19/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1030176 |
Resubmittal 1 | Original | / | 1/19/2018 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 1030174 |
Out to Review | Original | / | 12/5/2017 | RITA | RITA | BJ 719-651-0949 | | Out to Review | 1018906 |
Finished Bin | Original | / | 11/22/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1015161 |
Plan Coordinator | Original | / | 11/22/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1015090 |
Plumbing | Original | D | 11/22/2017 | TCRIPPEN | TCRIPPEN | add sizes to water entry detail on page P 0,1, remove general note 6 and add PEX. piping note, Provide an water piping size analysis data on plans, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1015089 |
Plumbing | Original | / | 11/21/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1014944 |
Plan Coordinator | Original | / | 11/21/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1014757 |
Mechanical | Original | D | 11/21/2017 | JUSTINC | JUSTINC | Indicate on (M) floor plan how providing O.S.A to furnace? Provide ventilation schedule per 09' IMC 403.3
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1014755 |
Mechanical | Original | / | 11/21/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1014718 |
Mechanical | Original | / | 11/20/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1014473 |
Plan Coordinator | Original | / | 11/20/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1014435 |
Electrical | Original | D | 11/20/2017 | BERTHA | BERTHA | Provide electrical.
https://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1014434 |
Electrical | Original | / | 11/17/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1014149 |
Electrical | Original | / | 11/17/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1014100 |
Plan Coordinator | Original | / | 11/17/2017 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1014090 |
Construction | Original | D | 11/17/2017 | BPHILLIPS | BPHILLIPS | Openings don't match metal building drawings. Handwritten comments on stamped plans must be initialed and dated by the design professional. Indicate occupancy classifications on code check. Foundation sheet F-1 must be at least 18"x24" and reference soils report. Verify ANSI compliance on shower drawing. No walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1014089 |
Construction | Original | / | 11/17/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1013919 |
Construction | Original | / | 11/16/2017 | | GITA | Location = Construction by GITA | | Construction | 1013587 |
Out to Review | Original | / | 11/13/2017 | AMY | AMY | | | Out to Review | 1012471 |
Floodplain | Original | N | 11/13/2017 | AMY | AMY | | | Floodplain | 1012469 |