Mechanical | Splice 9/25/18 | A | 9/26/2018 | TCRIPPEN | TCRIPPEN | okay removed added supply ducts | | Mechanical | 1113966 |
Mechanical | Splice 9/6/18 | A | 9/6/2018 | JUSTINC | JUSTINC | Revised plan for inspector comments | | Mechanical | 1107069 |
Out to Review | Splice 9/6/18 | / | 9/6/2018 | BECKYA | BECKYA | | | Out to Review | 1107062 |
Mechanical | Splice 8/16/18 | A | 8/21/2018 | JUSTINC | JUSTINC | Revised for TYPE 2 hood | | Mechanical | 1101971 |
Out to Review | Splice 8/16/18 | / | 8/16/2018 | BECKYA | BECKYA | | | Out to Review | 1100730 |
Electrical | Splice 6/25/18 | A | 6/25/2018 | BERTHA | BERTHA | Added three receptacles and revised panel schedule. | | Electrical | 1083221 |
Out to Review | Splice 6/25/18 | / | 6/25/2018 | BECKYA | BECKYA | | | Out to Review | 1083218 |
Plumbing | Splice 6/14/18 | A | 6/15/2018 | TCRIPPEN | TCRIPPEN | okay, relocate sinks and waste and water lines | | Plumbing | 1080385 |
Plumbing | Splice 6/14/18 | D | 6/14/2018 | TCRIPPEN | TCRIPPEN | need plumbing pages to show all changes (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1079785 |
Construction | Splice 6/14/18 | N | 6/14/2018 | MICHAELA | MICHAELA | | | Construction | 1079760 |
Out to Review | Splice 6/14/18 | / | 6/14/2018 | BECKYA | BECKYA | | | Out to Review | 1079750 |
CO Springs Fire | Original | A | 4/20/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1059990 |
Hazmat | Original | N | 4/20/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1059989 |
Mechanical | Original | A | 4/16/2018 | JUSTINC | JUSTINC | | | Mechanical | 1057908 |
Resubmittal 4 | Original | / | 4/11/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1056619 |
CO Springs Fire | Original | D | 4/10/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1055957 |
Hazmat | Original | D | 4/10/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1055955 |
Health Dept. | Original | A | 4/10/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | galvarez | Health Dept. | 1055907 |
Mechanical | Original | D | 4/9/2018 | JUSTINC | JUSTINC | Provide ventilation schedule per 09' IMC 403.3Provide existing equipment schedules to verify ventilation requirements per 09' IMC 403.3 This air balance schedule appears to be incomplete? It does not indicate the other (E) KEF shown in the kitchen?
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1055144 |
Plumbing | Original | A | 4/6/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1054859 |
Electronic Plan | Original | / | 4/6/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1054827 |
Construction | Original | A | 4/6/2018 | MICHAELA | MICHAELA | | | Construction | 1054774 |
Resubmittal 3 | Original | / | 4/5/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1054505 |
Hazmat | Original | D | 3/7/2018 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1044495 |
CO Springs Fire | Original | D | 3/7/2018 | CSFIRE | CSFIRE | CO2 FORM WAS PROVIDED BUT IT WAS NOT COMPLETED. (see full review) | csfdit | CO Springs Fire | 1044494 |
Electrical | Original | A | 3/5/2018 | SHELBY | SHELBY | | | Electrical | 1043453 |
Health Dept. | Original | D | 3/5/2018 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3199 option 3. | Aparikh | Health Dept. | 1043342 |
Mechanical | Original | D | 3/5/2018 | DALEH | DALEH | appears there are multiple copies of the mechanical sheets up loaded (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1043243 |
Plumbing | Original | A | 3/5/2018 | TCRIPPEN | TCRIPPEN | okay. | | Plumbing | 1043006 |
Electronic Plan | Original | / | 3/5/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1043003 |
Construction | Original | A | 3/5/2018 | MICHAELA | MICHAELA | | | Construction | 1043002 |
Resubmittal 2 | Original | / | 3/2/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1042955 |
Plan Coordinator | Original | D | 3/2/2018 | BECKYA | BECKYA | Disapprove all remaining departments to allow plan to be resubmitted (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1042723 |
Construction | Original | A | 3/2/2018 | MICHAELA | MICHAELA | | | Construction | 1042589 |
Resubmittal 1 | Original | / | 3/1/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1042398 |
Hazmat | Original | D | 12/20/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1023081 |
CO Springs Fire | Original | D | 12/20/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1023080 |
Electrical | Original | D | 12/18/2017 | SHELBY | SHELBY | please provide load calculation for building service. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1022075 |
Health Dept. | Original | D | 12/14/2017 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719)578-3199 option 3. AB (719)578-3278 | abrannon | Health Dept. | 1021537 |
CO Springs DRE | Original | N | 12/14/2017 | SDALSING | SDALSING | Interior remodel - use allowed (see full review) | | CO Springs DRE | 1021465 |
Mechanical | Original | D | 12/12/2017 | DALEH | DALEH | provide kitchen air balance schedule for kitchen equipment documents cant say for reference only no review of hood drawings vented curbs not allowed in this application see plans for complete red lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1020609 |
Electronic Plan | Original | / | 12/12/2017 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1020571 |
Water Division | Original | N | 12/12/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Water Division | 1020516 |
Waste Water Div | Original | N | 12/12/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Waste Water Div | 1020515 |
Zoning/Planning | Original | / | 12/12/2017 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1020378 |
Plumbing | Original | A | 12/12/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1020370 |
Construction | Original | A | 12/11/2017 | MICHAELA | MICHAELA | | | Construction | 1020048 |
Electronic Plan | Original | / | 12/8/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1019919 |
Enumeration | Original | A | 12/7/2017 | BRENT | BRENT | | | Enumeration | 1019555 |
Floodplain | Original | N | 12/7/2017 | BRENT | BRENT | floodplain on parcel, not near area of work. | | Floodplain | 1019554 |
Floodplain | Original | / | 12/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7323404008) | | Floodplain | 1016908 |