Out to Review | Splice 03/29/19 L53393 1578 Monterey | / | 6/24/2019 | SCANNING | SCANNING | Jim | | Out to Review | 1205725 |
Out to Review | L53395 Splice 03/29/19 1592 Monterey | / | 6/24/2019 | SCANNING | SCANNING | Jim | | Out to Review | 1205724 |
Out to Review | L53398 splice 03/29/19 1606 Monterey | / | 6/24/2019 | SCANNING | SCANNING | Jim | | Out to Review | 1205723 |
Scanned/Finished Bin | Splice 03/29/19 L53393 1578 Monterey | / | 6/24/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1205721 |
Scanned/Finished Bin | L53395 Splice 03/29/19 1592 Monterey | / | 4/26/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Rolled Plan SITE SPECIFIC 1592 Monterey Rd : L53395 -J3-) | | Scanned/Finished Bin | 1183674 |
Scanned/Finished Bin | L53398 splice 03/29/19 1606 Monterey | / | 4/26/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Rolled Plan SITE SPECIFIC 1606 Monterey Rd : L53398 -J3-) | | Scanned/Finished Bin | 1183661 |
To Be Scanned Bin | L53395 Splice 03/29/19 1592 Monterey | / | 4/26/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1183553 |
To Be Scanned Bin | Splice 03/29/19 L53393 1578 Monterey | / | 4/26/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING (Rolled Plan SITE SPECIFIC 1578 Monterey Rd : L53393 -J3-) | | To Be Scanned Bin | 1183552 |
To Be Scanned Bin | L53398 splice 03/29/19 1606 Monterey | / | 4/26/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1183548 |
Plan Coordinator | L53395 Splice 03/29/19 1592 Monterey | / | 4/26/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1183371 |
Plan Coordinator | L53398 splice 03/29/19 1606 Monterey | / | 4/26/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1183368 |
Plumbing | L53395 Splice 03/29/19 1592 Monterey | A | 4/26/2019 | SHANEN | SHANEN | Delta 4 revisions P1.0 update fixture schedule, P1.1 floor drain AAV, P1.2 no revisions | | Plumbing | 1183365 |
Plan Coordinator | Splice 03/29/19 L53393 1578 Monterey | / | 4/26/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1183342 |
Plumbing | Splice 03/29/19 L53393 1578 Monterey | A | 4/26/2019 | SHANEN | SHANEN | OK | | Plumbing | 1183339 |
Plumbing | L53398 splice 03/29/19 1606 Monterey | A | 4/26/2019 | SHANEN | SHANEN | Delta 4 revisions P1.0 update fixture schedule, P1.1 floor drain AAV, P1.2 no revisions | | Plumbing | 1183331 |
Plumbing | L53395 Splice 03/29/19 1592 Monterey | / | 4/25/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1183075 |
Plumbing | L53398 splice 03/29/19 1606 Monterey | / | 4/25/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1183074 |
Plumbing | Splice 03/29/19 L53393 1578 Monterey | / | 4/25/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1183030 |
Plumbing | Splice 03/29/19 L53393 1578 Monterey | / | 4/25/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1182893 |
Plumbing | L53395 Splice 03/29/19 1592 Monterey | / | 4/25/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1182892 |
Plumbing | L53398 splice 03/29/19 1606 Monterey | / | 4/25/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1182891 |
Plan Coordinator | Splice 03/29/19 L53393 1578 Monterey | / | 4/25/2019 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1182873 |
Mechanical | Splice 03/29/19 L53393 1578 Monterey | A | 4/25/2019 | DALEH | DALEH | delta 4 | | Mechanical | 1182872 |
Plan Coordinator | L53398 splice 03/29/19 1606 Monterey | / | 4/25/2019 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1182871 |
Mechanical | L53398 splice 03/29/19 1606 Monterey | A | 4/25/2019 | DALEH | DALEH | delta 4 | | Mechanical | 1182870 |
Plan Coordinator | L53395 Splice 03/29/19 1592 Monterey | / | 4/25/2019 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1182851 |
Mechanical | L53395 Splice 03/29/19 1592 Monterey | A | 4/25/2019 | DALEH | DALEH | delta 4 | | Mechanical | 1182848 |
Mechanical | Splice 03/29/19 L53393 1578 Monterey | / | 4/25/2019 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1182807 |
Mechanical | L53398 splice 03/29/19 1606 Monterey | / | 4/24/2019 | | BECKYA | Location = Mechanical by BECKYA | | Mechanical | 1182618 |
Mechanical | L53395 Splice 03/29/19 1592 Monterey | / | 4/24/2019 | | BECKYA | Location = Mechanical by BECKYA | | Mechanical | 1182617 |
Mechanical | Splice 03/29/19 L53393 1578 Monterey | / | 4/24/2019 | | BECKYA | Location = Mechanical by BECKYA | | Mechanical | 1182616 |
Out to Review | L53395 Splice 03/29/19 1592 Monterey | / | 3/29/2019 | BECKYA | BECKYA | | | Out to Review | 1172830 |
Out to Review | Splice 03/29/19 L53393 1578 Monterey | / | 3/29/2019 | BECKYA | BECKYA | | | Out to Review | 1172518 |
Out to Review | Splice 02/08/19 L53393 L53395 L53398 | / | 2/12/2019 | RITA | RITA | Jim 719-499-7657 | | Out to Review | 1158536 |
To Be Scanned Bin | Splice 02/08/19 L53393 L53395 L53398 | / | 2/12/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1158420 |
Construction | Splice 02/08/19 L53393 L53395 L53398 | A | 2/12/2019 | BPHILLIPS | BPHILLIPS | Provided fire protection continuity detail for "tunnel" area in garage.Revised detail notations. | | Construction | 1158410 |
Out to Review | Splice 02/08/19 L53393 L53395 L53398 | / | 2/11/2019 | JANE | JANE | | | Out to Review | 1158072 |
Finished Bin | Splice 02/08/19 L53393 L53395 L53398 | / | 2/11/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1158069 |
Plan Coordinator | Splice 02/08/19 L53393 L53395 L53398 | / | 2/11/2019 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1158050 |
Construction | Splice 02/08/19 L53393 L53395 L53398 | D | 2/11/2019 | BPHILLIPS | BPHILLIPS | Provide horizontal assembly below stair/ landing in garage. If prescriptive, show compliance with 721.6. Show continuity detail where horizontal assembly meets shaft wall. Walk with Brett only or resubmit at permit counter. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1158049 |
Construction | Splice 02/08/19 L53393 L53395 L53398 | / | 2/11/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1157794 |
Construction | Splice 02/08/19 L53393 L53395 L53398 | / | 2/8/2019 | | SCANNING | Location = Construction by SCANNING | | Construction | 1157590 |
Out to Review | Splice 02/08/19 L53393 L53395 L53398 | / | 2/8/2019 | BECKYA | BECKYA | | | Out to Review | 1157571 |
Construction | Splice 01/23/19 | A | 1/23/2019 | SHELLEY | SHELLEY | Revised accessibility plan and columns | | Construction | 1151956 |
Construction | Splice 01/23/19 | D | 1/23/2019 | SHELLEY | SHELLEY | Need revised accessibility plan showing entire development (all 24 units), not the next phase. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1151844 |
Out to Review | Splice 01/23/19 | / | 1/23/2019 | BECKYA | BECKYA | | | Out to Review | 1151834 |
Electrical | Splice 01/07/19 | A | 1/7/2019 | BERTHA | BERTHA | Added house panel. | | Electrical | 1147455 |
Out to Review | Splice 01/07/19 | / | 1/7/2019 | BECKYA | BECKYA | | | Out to Review | 1147422 |
Out to Review | Splice 10/18/18 | / | 1/7/2019 | GITA | GITA | jim 499-7657 | | Out to Review | 1147419 |
Scanned/Finished Bin | Splice 10/18/18 | / | 1/7/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1147234 |
To Be Scanned Bin | Splice 10/18/18 | / | 1/7/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1147188 |
Plan Coordinator | Splice 10/18/18 | / | 1/7/2019 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1147176 |
Plumbing | Splice 10/18/18 | A | 1/7/2019 | TCRIPPEN | TCRIPPEN | revised layout, | | Plumbing | 1147175 |
Construction | Splice 10/18/18 | A | 1/3/2019 | MICHAELA | MICHAELA | | | Construction | 1146755 |
Out to Review | Splice 10/18/18 | / | 12/13/2018 | BECKYA | BECKYA | Jim has splice will add individual Electrical Splice later | | Out to Review | 1141224 |
Finished Bin | Splice 10/18/18 | / | 10/22/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1122282 |
Plan Coordinator | Splice 10/18/18 | / | 10/22/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1122212 |
Plumbing | Splice 10/18/18 | A | 10/22/2018 | TCRIPPEN | TCRIPPEN | Need new splice pages from construction to match back grounds first. | | Plumbing | 1122208 |
Plumbing | Splice 10/18/18 | / | 10/22/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1122192 |
Plumbing | Splice 10/18/18 | / | 10/19/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1121768 |
Plan Coordinator | Splice 10/18/18 | / | 10/19/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1121766 |
Mechanical | Splice 10/18/18 | A | 10/19/2018 | JUSTINC | JUSTINC | Revised layout | | Mechanical | 1121765 |
Mechanical | Splice 10/18/18 | / | 10/18/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1121693 |
Mechanical | Splice 10/18/18 | / | 10/18/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1121628 |
Plan Coordinator | Splice 10/18/18 | / | 10/18/2018 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1121617 |
Construction | Splice 10/18/18 | D | 10/18/2018 | BPHILLIPS | BPHILLIPS | Provide clouds, deltas, explanations of all changes you wish to be reviewed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1121616 |
Construction | Splice 10/18/18 | / | 10/18/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1121576 |
Construction | Splice 10/18/18 | / | 10/18/2018 | | BECKYA | Location = Construction by BECKYA | | Construction | 1121334 |
Scanned/Finished Bin | Original | / | 6/14/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1079844 |
CO Springs Fire | Original | A | 6/14/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1079796 |
Out to Review | Original | / | 5/22/2018 | | HVANNIMWEGEN | Location = Out to Review by HVANNIMWEGEN | | Out to Review | 1071224 |
CO Springs DRE | Original | A | 5/22/2018 | HVANNIMWEGEN | HVANNIMWEGEN | Financial Assurance approved for landscape and irrigation (see full review) | | CO Springs DRE | 1071223 |
City Engr | Original | A | 5/18/2018 | PMORRIS | PMORRIS | | | City Engr | 1070164 |
Health Dept. | Original | N | 4/12/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB (719)578-3199 option 3 | abrannon | Health Dept. | 1056883 |
Construction | Original | A | 4/4/2018 | SHELLEY | SHELLEY | | | Construction | 1053900 |
Out to Review | Original | / | 4/2/2018 | LBENNETT | LBENNETT | walking | | Out to Review | 1053041 |
Construction | Original | D | 4/2/2018 | LBENNETT | LBENNETT | missing IECC certificate (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1053040 |
Zoning/Planning | Original | / | 4/2/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In Current Review by HVANNIMWEGEN | | Zoning/Planning | 1052820 |
Zoning/Planning | Original | / | 3/30/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1052547 |
Plan Coordinator | Original | / | 3/30/2018 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1052490 |
Construction | Original | D | 3/30/2018 | BPHILLIPS | BPHILLIPS | Show clear floor space for ANSI compliance. Show turning space in all rooms of Type A units. Revise elevation to show accessible route to door. Walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1052488 |
Construction | Original | / | 3/30/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1052402 |
Construction | Original | / | 3/29/2018 | | GITA | Location = Construction by GITA | | Construction | 1051874 |
Resubmittal 2 | Original | / | 3/29/2018 | GITA | GITA | Resubmittal #2 CONSTRUCTION ONLY | | Resubmittal 2 | 1051872 |
Zoning/Planning | Original | / | 3/28/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1051109 |
Plan Coordinator | Original | / | 3/28/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1051072 |
Plumbing | Original | A | 3/28/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1051071 |
Plumbing | Original | / | 3/28/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1051070 |
Plumbing | Original | / | 3/27/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1050877 |
Plan Coordinator | Original | / | 3/27/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1050862 |
Mechanical | Original | A | 3/27/2018 | JUSTINC | JUSTINC | | | Mechanical | 1050861 |
Mechanical | Original | / | 3/27/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1050729 |
Mechanical | Original | / | 3/26/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1050563 |
Plan Coordinator | Original | / | 3/26/2018 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1050548 |
Construction | Original | D | 3/26/2018 | BPHILLIPS | BPHILLIPS | Provide accessibility plan per attached handout. Accessible garage required per IBC. No accessibility review performed. Provide reconciled square footage/ occupant loading per notes. Provide revised elevation drawing to show riser room. Reference continuity detail where assemblies intersect. Where listed assembly has multiple systems, indicate which system is being used. Note: Upon further review, initial common path of travel distances were compliant. Thus, exit enclosures not required. Please contact Brett Phillips to discuss - 327-2917. No walk through review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1050547 |
Construction | Original | / | 3/22/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1049707 |
Construction | Original | / | 3/22/2018 | | RITA | Location = Construction by RITA | | Construction | 1049699 |
Resubmittal 1 | Original | / | 3/22/2018 | RITA | RITA | Resubmittal #1 For construction, mechanical and plumbing only, will be walking the outside departments. | | Resubmittal 1 | 1049698 |
CSU Contract Admin. | Original | A | 3/22/2018 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and all applicable development fees/charges paid for all buildings. AG | aguerin | CSU Contract Admin. | 1049694 |
Water Division | Original | A | 3/22/2018 | CSUREVIEW | CSUREVIEW | MLW | mlwilliams | Water Division | 1049578 |
Waste Water Div | Original | A | 3/22/2018 | CSUREVIEW | CSUREVIEW | MLW | mlwilliams | Waste Water Div | 1049577 |
Gas/Elec. Utils | Original | A | 3/22/2018 | CSUREVIEW | CSUREVIEW | MLW | mlwilliams | Gas/Elec. Utils | 1049576 |
Waste Water Div | Original | D | 3/22/2018 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Provide copy of approved plan in permit set. JPN | jnoble | Waste Water Div | 1049493 |
CSU Contract Admin. | Original | D | 3/20/2018 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved for 1" combined domestic/irrigation per building. Payment of development fees/charges required for three buildings - 1578, 1592, 1606 Monterey Rd. Contact Utilities Development Services at 719-668-8111 for assistance. AG | aguerin | CSU Contract Admin. | 1048997 |
CSU Contract Admin. | Original | / | 3/20/2018 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1048830 |
Finished Bin | Original | / | 3/20/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1048817 |
Water Division | Original | D | 3/20/2018 | CSUREVIEW | CSUREVIEW | You have approved civil plans in RBD set, however for the 3 lots that you propose you have no water approved utility service plan in the RBD set for this project. This will need to be in the RBD set prior to water approval. AJ | ajuvera | Water Division | 1048745 |
Waste Water Div | Original | A | 3/20/2018 | CSUREVIEW | CSUREVIEW | All comments addressed AJ | ajuvera | Waste Water Div | 1048744 |
Gas/Elec. Utils | Original | D | 3/20/2018 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views to make sure gas regulator vent is at least 3ft away from any electric meter socket and openings like windows, doors, and garage doors. Contact the CSU Field Engineer, Mary Hoaglund (719-668-4083) to coordinate the gas and electric services. | ajuvera | Gas/Elec. Utils | 1048736 |
Enumeration | Original | A | 3/16/2018 | AMY | AMY | 3 buildings for this plan 1578, Monterey Road units 101, 102, 201, 202. 1592 Monterey Road units 101, 102, 201, 202, 1606 Monterey Road 101, 102, 201, 202. SEE ALL ADDRESSING ON PAGE DP1- 1 OF 6 | | Enumeration | 1047780 |
Out to Review | Original | / | 1/31/2018 | JANE | JANE | Jim 719 499 7657 | | Out to Review | 1033460 |
Finished Bin | Original | / | 1/31/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1033370 |
Health Dept. | Original | D | 1/31/2018 | HEALTHDEPT | HEALTHDEPT | Plan review required. Please contact the health department at (719) 578-3199 option 3. Gustavo Alvarez (719) 578-3295 | galvarez | Health Dept. | 1033345 |
Health Dept. | Original | / | 1/25/2018 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1031962 |
City Engr | Original | D | 1/25/2018 | CSENGINEER | CSENGINEER | Include a copy of the Water Resources Engineering approved Grading and Erosion Control Plan in the building permit set. Plan Set routed to RBD. pvm | csengineer | City Engr | 1031892 |
Water Division | Original | D | 1/25/2018 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved water Utility Plan(USP)in the plan set. Contact Utilities Development Services at 719-668-8111 with questions. | ajuvera | Water Division | 1031680 |
Waste Water Div | Original | D | 1/25/2018 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved wastewater Utility Plan(USP)in the plan set. Contact Utilities Development Services at 719-668-8111 with questions. | ajuvera | Waste Water Div | 1031678 |
Gas/Elec. Utils | Original | D | 1/25/2018 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views to make sure gas regulator vent is at least 3ft away from any electric meter socket and openings like windows, doors, and garage doors. Contact the CSU Field Engineer, Mary Hoaglund (719-668-4083) to coordinate the gas and electric services. This will need to be shown on the building elevations. AJ | ajuvera | Gas/Elec. Utils | 1031677 |
CO Springs DRE | Original | D | 1/23/2018 | HVANNIMWEGEN | HVANNIMWEGEN | Submit a final landscape and a final irrigation plan to Connie Perry (Contact: 719-385-5375 or cperry@springsgov.com). Submit a complete financial assurance for the landscaping and irrigation (Contact Hannah Van Nimwegen: 719-385-5365, hvannimwegen@springsgov.com) (see full review) | | CO Springs DRE | 1030779 |
City Engr | Original | / | 1/19/2018 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 1030062 |
Hazmat | Original | N | 1/18/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1029630 |
CO Springs Fire | Original | D | 1/18/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1029628 |
Fire | Original | / | 1/12/2018 | | HVANNIMWEGEN | Location = Fire by HVANNIMWEGEN | | Fire | 1028388 |
CO Springs DRE | Original | D | 1/12/2018 | HVANNIMWEGEN | HVANNIMWEGEN | Please include a copy of the approved development plan in the plan set. Submit a final landscape and a final irrigation plan to Connie Perry (Contact: 719-385-5375 or cperry@springsgov.com). Submit a complete financial assurance for the landscaping and irrigaiton. (see full review) | | CO Springs DRE | 1028387 |
Zoning/Planning | Original | / | 1/8/2018 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | lmpope | Zoning/Planning | 1026580 |
CSU Contract Admin. | Original | D | 1/8/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form and payment of development charges/fees. LMP | lmpope | CSU Contract Admin. | 1026579 |
Gas/Elec. Utils | Original | D | 1/5/2018 | CSUREVIEW | CSUREVIEW | Provide an approved Development Plan, include a proposed location for gas and electric meters on building elevations. MLW | mlwilliams | Gas/Elec. Utils | 1026232 |
Water Division | Original | D | 1/5/2018 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved development plan in the set. Provide approved wastewater and water construction drawings in the set. Contact Utilities Development Services at 719.668.8261 with any questions. MLW | mlwilliams | Water Division | 1026231 |
Waste Water Div | Original | D | 1/5/2018 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved development plan in the set. Provide approved wastewater and water construction drawings in the set. Contact Utilities Development Services at 719.668.8261 with any questions. MLW | mlwilliams | Waste Water Div | 1026230 |
City Engr | Original | / | 12/22/2017 | | CSUREVIEW | Location = City Engr by CSUREVIEW | jnoble | City Engr | 1023595 |
CSU Contract Admin. | Original | / | 12/21/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1023559 |
Plan Coordinator | Original | / | 12/21/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1023516 |
Mechanical | Original | D | 12/21/2017 | DALEH | DALEH | bath exhaust venting see plan note about duct routing see plans for complete red lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1023515 |
Mechanical | Original | / | 12/21/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1023332 |
Mechanical | Original | / | 12/21/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1023209 |
Plan Coordinator | Original | / | 12/19/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1022598 |
Electrical | Original | A | 12/19/2017 | SHELBY | SHELBY | | | Electrical | 1022596 |
Electrical | Original | / | 12/19/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1022581 |
Plumbing | Original | D | 12/19/2017 | TCRIPPEN | TCRIPPEN | see red lines for sizes and missing notes (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1022555 |
Electrical | Original | / | 12/14/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1021419 |
Plan Coordinator | Original | / | 12/14/2017 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1021327 |
Construction | Original | D | 12/14/2017 | BPHILLIPS | BPHILLIPS | Provide accessibility plan - no accessibility review performed. Provide current listed assemblies where required. Sprinklers are required for this project. Upstairs travel distance exceeds requirements in Table 1021.2. Provide detail to show continuity of fire-resistive assemblies.Provide IECC form or Comcheck. See plans for all notes. No walk through review allowed upon resubmittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1021326 |
Construction | Original | / | 12/12/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1020719 |
Construction | Original | / | 12/12/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1020627 |
Plan Coordinator | Original | / | 12/12/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1020623 |
Enumeration | Original | D | 12/12/2017 | AMY | AMY | -ON A SEPARATE SHEET FOR ADDRESSING PURPOSES HOW ALL HOMES THAT APPLY TO THIS PLAN SET -TO INCLUDE THE FRONT DOORS SO THAT UNIT NUMBERING CAN BE ASSIGNED TO ALL 4 PLEXES.
-PLAN CHECKED IN 3 DUPLEX BUILDINGS, 6 ADDRESSES ON CODE STUDY FORM-EDIT TO SHOW CORRECTLY.
-DP PAGE 1 OF 6 SHOWS 3 BUILDINGS CLOUDED, PAGE 6 OF 6 SHOWS 6 BUILDINGS. THE PLAN NEEDS TO BE CLEAR THROUGHOUT.
-ONCE IT IS CLEAR AS TO THE ADDRESSING THAT THIS PLAN IS FOR-THE PLAN WILL BE UNDER 1 OF THE ADDRESSES WITH ALL OTHER LISTED ON THE PLAN LABEL. EACH BUILDING WILL HAVE A SEPARATE PERMIT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1020622 |
Enumeration | Original | / | 12/12/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 1020584 |
Enumeration | Original | / | 12/11/2017 | | JANE | Location = Enumeration by JANE | | Enumeration | 1020246 |
Finished Bin | Original | / | 12/5/2017 | | RITA | Location = Finished Bin by RITA. Waiting for plan check fee to start routing plans. Please route as soon as money is recieved , | | Finished Bin | 1017797 |
Floodplain | Original | N | 12/5/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6428111042) | | Floodplain | 1017796 |