Construction | Splice 05/26/20 trusses | A | 5/27/2020 | MICHAELA | MICHAELA | Trusses | | Construction | 1327219 |
Electronic Plan | Splice 05/26/20 trusses | / | 5/27/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1327218 |
Finished Bin | Splice 02/26/20 | / | 2/26/2020 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1291116 |
To Be Scanned Bin | Splice 02/26/20 | / | 2/26/2020 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1290990 |
Plan Coordinator | Splice 02/26/20 | / | 2/26/2020 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1290919 |
Construction | Splice 02/26/20 | A | 2/26/2020 | MICHAELA | MICHAELA | Relocate water entry room | | Construction | 1290918 |
Construction | Splice 02/26/20 | / | 2/26/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1290860 |
Construction | Splice 02/26/20 | / | 2/26/2020 | | BECKYA | Location = Construction by BECKYA | | Construction | 1290816 |
Scanned/Finished Bin | Splice 11/25/19 | / | 11/25/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1261255 |
To Be Scanned Bin | Splice 11/25/19 | / | 11/25/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1261158 |
Plan Coordinator | Splice 11/25/19 | / | 11/25/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1261064 |
Construction | Splice 11/25/19 | A | 11/25/2019 | MICHAELA | MICHAELA | Clarify penetrations at Mech. closet | | Construction | 1261063 |
Construction | Splice 11/25/19 | / | 11/25/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1260988 |
Construction | Splice 11/25/19 | / | 11/25/2019 | | MICHAELA | Location = Construction by MICHAELA | | Construction | 1260987 |
Out to Review | Splice 11/25/19 | / | 11/25/2019 | BECKYA | BECKYA | | | Out to Review | 1260758 |
Scanned/Finished Bin | Splice 10/28/19 | / | 11/1/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Rolled Plan in Regular Finished Bin -J3) | | Scanned/Finished Bin | 1252380 |
Electrical | Splice 10/28/19 | A | 11/1/2019 | SHELBY | SHELBY | | | Electrical | 1252195 |
Finished Bin | Splice 10/28/19 | / | 10/30/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1251114 |
Plan Coordinator | Splice 10/28/19 | / | 10/30/2019 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1251088 |
Electrical | Splice 10/28/19 | D | 10/30/2019 | BERTHA | BERTHA | Comply 310.15(B)(3)(a) - 2017 NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1251087 |
Out to Review | Splice 10/28/19 | / | 10/29/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Out to Review | 1250866 |
Out to Review | Splice 10/28/19 | / | 10/28/2019 | BECKYA | BECKYA | | | Out to Review | 1250284 |
Scanned/Finished Bin | L82833 Splice 06/03/19 | / | 6/6/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Splice scanned to the plan image per Michael A. Located in "B" bin) -J3- | | Scanned/Finished Bin | 1198944 |
To Be Scanned Bin | L82833 Splice 06/03/19 | / | 6/5/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1198654 |
Plan Coordinator | L82833 Splice 06/03/19 | / | 6/5/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1198591 |
Construction | L82833 Splice 06/03/19 | A | 6/5/2019 | MICHAELA | MICHAELA | Clarify rated assemblies | | Construction | 1198589 |
Construction | L82833 Splice 06/03/19 | / | 6/3/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1197886 |
Construction | L82833 Splice 06/03/19 | / | 6/3/2019 | | GITA | Location = Construction by GITA | | Construction | 1197637 |
Scanned/Finished Bin | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/10/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Located in "C Bin" L82830 : 1850 Chippenham Hts -J3-) | | Scanned/Finished Bin | 1176972 |
Scanned/Finished Bin | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/10/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Located in "B Bin" L82833 : 1864 Birmingham Loop -J3-) | | Scanned/Finished Bin | 1176725 |
To Be Scanned Bin | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/9/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1176361 |
Plan Coordinator | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/9/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1176277 |
Electrical | L82833 Splice 04/05/19 1864 Birmingham Loop | A | 4/9/2019 | SHELBY | SHELBY | | | Electrical | 1176276 |
To Be Scanned Bin | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/9/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1176259 |
Electrical | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/9/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1176257 |
Plan Coordinator | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/9/2019 | SHELBY | SHELBY | In Current Review by SHELBY | | Plan Coordinator | 1176244 |
Plan Coordinator | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/9/2019 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1176065 |
Electrical | L82830 Splice 04/05/19 1850 Chippenham Hts | A | 4/9/2019 | BERTHA | BERTHA | Revised lighting. | | Electrical | 1176064 |
Electrical | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/8/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1175665 |
Electrical | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/8/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1175399 |
Plan Coordinator | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/8/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1175388 |
Construction | L82833 Splice 04/05/19 1864 Birmingham Loop | A | 4/8/2019 | MICHAELA | MICHAELA | Update details and assemblies | | Construction | 1175387 |
Plan Coordinator | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/8/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1175378 |
Construction | L82830 Splice 04/05/19 1850 Chippenham Hts | A | 4/8/2019 | MICHAELA | MICHAELA | Update details and assemblies | | Construction | 1175377 |
Construction | L82833 Splice 04/05/19 1864 Birmingham Loop | / | 4/5/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1174976 |
Construction | L82830 Splice 04/05/19 1850 Chippenham Hts | / | 4/5/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1174942 |
Scanned/Finished Bin | Splice 03/29/19 L82830 | / | 4/1/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (Site Specific Splice Scanned into PERMIT IMAGES, L82830 -J3-) | | Scanned/Finished Bin | 1173080 |
To Be Scanned Bin | Splice 03/29/19 L82830 | / | 3/29/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1172877 |
Plan Coordinator | Splice 03/29/19 L82830 | / | 3/29/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1172774 |
Plumbing | Splice 03/29/19 L82830 | A | 3/29/2019 | SHANEN | SHANEN | Building type 3 new pages P0.1-5, P0.2-5, P0.3-5, P0.4-5, P1.0-5, P3.0-5, P3.2-5, P3.3-5, P3.4-5 | | Plumbing | 1172771 |
Out to Review | L82833 Splice 03/28/19 1864 Birmingham Lp | / | 3/29/2019 | NELIDA | NELIDA | Brian 303-332-5257 | | Out to Review | 1172635 |
Plumbing | Splice 03/29/19 L82830 | / | 3/29/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1172611 |
Plumbing | Splice 03/29/19 L82830 | / | 3/29/2019 | | BECKYA | Location = Plumbing by BECKYA | | Plumbing | 1172594 |
Scanned/Finished Bin | L82833 Splice 03/28/19 1864 Birmingham Lp | / | 3/28/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING -J3- | | Scanned/Finished Bin | 1172273 |
To Be Scanned Bin | L82833 Splice 03/28/19 1864 Birmingham Lp | / | 3/28/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1172218 |
Plan Coordinator | L82833 Splice 03/28/19 1864 Birmingham Lp | / | 3/28/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1172217 |
Plumbing | L82833 Splice 03/28/19 1864 Birmingham Lp | A | 3/28/2019 | SHANEN | SHANEN | Building type 3B new pages inserted P0.1-2, P0.2-2, P0.3-2, P0.4-2 P1.0-2, P3.0-2, P3.1-2, P3.1a-2, P3.2-2, P3.3-2 | | Plumbing | 1172215 |
Plumbing | L82833 Splice 03/28/19 1864 Birmingham Lp | / | 3/28/2019 | | BECKYA | Location = Plumbing by BECKYA | | Plumbing | 1172159 |
Out to Review | L82833 Splice 03/28/19 1864 Birmingham Lp | / | 3/28/2019 | BECKYA | BECKYA | | | Out to Review | 1172149 |
Mechanical | Splice 03/25/19 L82833 L82830 | A | 3/25/2019 | JUSTINC | JUSTINC | Revised gas | | Mechanical | 1170380 |
Out to Review | Splice 03/25/19 L82833 L82830 | / | 3/25/2019 | BECKYA | BECKYA | | | Out to Review | 1170347 |
Scanned/Finished Bin | Splice 02/11/19 | / | 2/12/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1158456 |
To Be Scanned Bin | Splice 02/11/19 | / | 2/12/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1158415 |
Plan Coordinator | Splice 02/11/19 | / | 2/12/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1158376 |
Construction | Splice 02/11/19 | A | 2/12/2019 | MICHAELA | MICHAELA | Revise wall assembly | | Construction | 1158375 |
Construction | Splice 02/11/19 | / | 2/12/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1158365 |
Construction | Splice 02/11/19 | / | 2/11/2019 | | JANE | Location = Construction by JANE | | Construction | 1158117 |
Plumbing | Splice 01/30/19 L82833 L82830 | A | 1/30/2019 | SHANEN | SHANEN | Added new riser diagrams. | | Plumbing | 1154383 |
Out to Review | Splice 01/30/19 L82833 L82830 | / | 1/30/2019 | BECKYA | BECKYA | | | Out to Review | 1154356 |
Mechanical | Splice 01/28/19 L82833 | A | 1/28/2019 | DALEH | DALEH | DELTA 5 | | Mechanical | 1153547 |
Mechanical | Splice 01/28/19 L82830 | A | 1/28/2019 | DALEH | DALEH | DELTA 5 | | Mechanical | 1153545 |
Out to Review | Splice 01/28/19 L82830 | / | 1/28/2019 | BECKYA | BECKYA | | | Out to Review | 1153509 |
Mechanical | Splice 01/15/19 | A | 1/15/2019 | JUSTINC | JUSTINC | Revised layout | | Mechanical | 1149784 |
Out to Review | Splice 01/15/19 | / | 1/15/2019 | BECKYA | BECKYA | | | Out to Review | 1149778 |
Construction | Splice 12/12/18 | A | 12/12/2018 | SHELLEY | SHELLEY | Revised floor assembly | | Construction | 1140631 |
Out to Review | Splice 12/12/18 | / | 12/12/2018 | BECKYA | BECKYA | | | Out to Review | 1140615 |
Construction | Splice 10/3/18 L82830 And L82833 | A | 10/3/2018 | SHELLEY | SHELLEY | Added headers | | Construction | 1116074 |
Out to Review | Splice 10/3/18 L82830 And L82833 | / | 10/3/2018 | SHELBY | SHELBY | | | Out to Review | 1116063 |
Electrical | Splice 10/3/18 L82830 And L82833 | A | 10/3/2018 | SHELBY | SHELBY | | | Electrical | 1116062 |
CSU Contract Admin. | Original | A | 9/21/2018 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees paid 9/21/18. BML | bmludiker | CSU Contract Admin. | 1112621 |
Scanned/Finished Bin | Original | / | 9/20/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING - LOCATED IN LG FINISHED BIN -J3- | | Scanned/Finished Bin | 1112368 |
To Be Scanned Bin | Original | / | 9/20/2018 | | JANE | Location = To Be Scanned Bin by JANE | | To Be Scanned Bin | 1111985 |
Health Dept. | Original | N | 9/19/2018 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT0040730 is valid from 5/2/2018 to 11/2/2018. | MelissaLovato | Health Dept. | 1111803 |
Out to Review | Original | / | 9/19/2018 | NELIDA | NELIDA | Andy 719-419-2300 | | Out to Review | 1111594 |
Finished Bin | Original | / | 9/18/2018 | | SCANNING | Location = Finished Bin by SCANNING( Oversized Plan Bin) | | Finished Bin | 1111254 |
Health Dept. | Original | D | 9/18/2018 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. For questions contact Environmental Health at (719)578-3199 option 3. AB | abrannon | Health Dept. | 1111181 |
Health Dept. | Original | / | 9/17/2018 | | JANE | Location = Health Dept. by JANE | | Health Dept. | 1110535 |
Plumbing | Original | A | 9/17/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1110530 |
Out to Review | Original | / | 9/14/2018 | NELIDA | NELIDA | Ray 623-5641 | | Out to Review | 1110136 |
CSU Contract Admin. | Original | / | 9/14/2018 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1110095 |
Plan Coordinator | Original | / | 9/14/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1110089 |
Plumbing | Original | / | 9/14/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1110036 |
Plumbing | Original | D | 9/12/2018 | TCRIPPEN | TCRIPPEN | need a pipe material schedule as to what can be used on this job you can email it to me tcrippen@pprbd.org (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1109426 |
Plumbing | Original | / | 9/12/2018 | | RITA | Location = Plumbing by RITA | | Plumbing | 1109176 |
Resubmittal 3 | Original | / | 9/12/2018 | RITA | RITA | Resubmittal #3 | | Resubmittal 3 | 1109168 |
Out to Review | Original | / | 8/28/2018 | JANE | JANE | Rick 623 5641 | | Out to Review | 1104489 |
Finished Bin | Original | / | 8/28/2018 | | SCANNING | Location = Finished Bin by SCANNING( oversized bin) | | Finished Bin | 1104256 |
Plan Coordinator | Original | / | 8/28/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1104228 |
Mechanical | Original | A | 8/28/2018 | JUSTINC | JUSTINC | | | Mechanical | 1104227 |
Mechanical | Original | / | 8/27/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1103794 |
Mechanical | Original | / | 8/24/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1103471 |
Plan Coordinator | Original | / | 8/24/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1103468 |
Plumbing | Original | D | 8/24/2018 | TCRIPPEN | TCRIPPEN | still need to revise floor plan rated walls have changed some doors removed , some door swing are different please see A pages for changes (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1103467 |
Plumbing | Original | / | 8/24/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1103449 |
Plumbing | Original | / | 8/24/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1103328 |
Plan Coordinator | Original | / | 8/23/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1103254 |
Electrical | Original | A | 8/23/2018 | BERTHA | BERTHA | ELECTRICAL INSPECTOR - SEE SHEET A0.1 FOR ACCESSIBILITY REQUIREMENTS. | | Electrical | 1103253 |
Electrical | Original | / | 8/23/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1103229 |
Electrical | Original | / | 8/23/2018 | | GITA | Location = Electrical by GITA | | Electrical | 1103160 |
Out to Review | Original | / | 8/15/2018 | JANE | JANE | Rick 719 623 5641 | | Out to Review | 1100140 |
Finished Bin | Original | / | 8/15/2018 | | SCANNING | Location = Finished Bin by SCANNING oversized | | Finished Bin | 1100081 |
Plan Coordinator | Original | / | 8/15/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1100051 |
Construction | Original | A | 8/15/2018 | MICHAELA | MICHAELA | | | Construction | 1100050 |
Construction | Original | / | 8/15/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1099965 |
Construction | Original | / | 8/13/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1099290 |
Resubmittal 2 | Original | / | 8/13/2018 | GITA | GITA | Resubmittal #2 CONSTRUCTION ONLY | | Resubmittal 2 | 1099186 |
Out to Review | Original | / | 7/30/2018 | NELIDA | NELIDA | Kristin 719-623-5641 | | Out to Review | 1094514 |
Finished Bin | Original | / | 7/27/2018 | | SCANNING | Location = Finished Bin by SCANNING( Oversized Plan Bin) | | Finished Bin | 1093813 |
CO Springs Fire | Original | A | 7/25/2018 | CSFIRE | CSFIRE | Fee is per building. RTP | rpeterson | CO Springs Fire | 1093358 |
CO Springs Fire | Original | A | 7/25/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1093355 |
Fire | Original | / | 7/19/2018 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1091440 |
CO Springs DRE | Original | A | 7/19/2018 | RDCUSER | RDCUSER | (see full review) | | CO Springs DRE | 1091439 |
Zoning/Planning | Original | / | 7/12/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1089068 |
Plumbing | Original | D | 7/12/2018 | TCRIPPEN | TCRIPPEN | review stopped back grounds no match, see notes for construction (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1089061 |
Plan Coordinator | Original | / | 7/12/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1088976 |
Mechanical | Original | D | 7/12/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Unable to perform mechanical review pending construction reviewer comments. Verify mechanical scope with any (A) sheet revisions.
NO WALK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1088975 |
Mechanical | Original | / | 7/12/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1088942 |
Mechanical | Original | / | 7/12/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1088921 |
Plan Coordinator | Original | / | 7/12/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1088861 |
Electrical | Original | D | 7/12/2018 | BERTHA | BERTHA | 1. Provide complete one-line diagram with all conductor size, type and quantity beginning at the utility transformer (between main service disconnect and meter stack). 2. Approval pending approval by Construction - Accessibility sheet is required.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1088860 |
Electrical | Original | / | 7/11/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1088348 |
Plan Coordinator | Original | / | 7/11/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1088289 |
Construction | Original | D | 7/11/2018 | MICHAELA | MICHAELA | Soils report must be recertified - more than 2 years old 2nd and 3rd floor corridor walls are not fire barriers - fire partitions Indicate 1-hr. floors required to separate dwelling units Still missing listing for 1-hr. floor at TJI floor joists above garage Accessibility plan must list unit numbers in specific buildings Comply with 1022.6 for protection of exit enclosures Main level corridors are exit enclosures - only doors from normally occupied space may open into an exit enclosure Provide additional building section through space open to below Correct floor plan keynote 1 - wrong page is referenced Verify microwave meets reach range in type A units - provide detail Storage room at ANSI garage may not open into exit enclosure Provide corrected reflected ceiling plan for new corridor configuration Label rated floor and ceiling assemblies on section plan Provide rated floor in 2nd. level corridor for exit enclosure below Re-draw detail 6/A3.9 to show correct floor assemblies - deck does not need to be separated from garage or insulation Add detail for fire barrier continuity on section plan A4.3 Clarify where floating walls will be required or remove detail No walk-through
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1088287 |
Construction | Original | / | 7/11/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1088123 |
Construction | Original | / | 7/11/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1088068 |
Plan Coordinator | Original | / | 7/10/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1088049 |
Enumeration | Original | A | 7/10/2018 | AMY | AMY | BUILDING TYPES 3 & 3B FOR THIS PLAN- 1850 CHIPPENHAM HEIGHTS & 1864 BIRMINGHAM LOOP. COPY OF FINAL RECORDED PLAT RECEIVED. | | Enumeration | 1088048 |
Enumeration | Original | / | 7/10/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1088047 |
Enumeration | Original | / | 7/3/2018 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1086008 |
Resubmittal 1 | Original | / | 7/3/2018 | NELIDA | NELIDA | Resubmittal #1 7/3/18 | | Resubmittal 1 | 1086006 |
Out to Review | Original | / | 2/14/2018 | RITA | RITA | Kristen 719-623-5641 | | Out to Review | 1037477 |
Finished Bin | Original | / | 2/12/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1036899 |
Health Dept. | Original | D | 2/12/2018 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application For questions contact Environmental Health at 719-578-3199 option 3. | rnielsen | Health Dept. | 1036886 |
Health Dept. | Original | / | 2/9/2018 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1036179 |
Hazmat | Original | N | 2/8/2018 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1035815 |
Hazmat | Original | / | 2/7/2018 | | SCANNING | Location = Hazmat by SCANNING | | Hazmat | 1035769 |
City Engr | Original | A | 2/7/2018 | CSENGINEER | CSENGINEER | Plan set routed to RBD. jad | csengineer | City Engr | 1035704 |
Water Division | Original | A | 2/7/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Water Division | 1035691 |
Waste Water Div | Original | A | 2/7/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Waste Water Div | 1035690 |
Gas/Elec. Utils | Original | A | 2/7/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Gas/Elec. Utils | 1035689 |
CO Springs Fire | Original | D | 2/5/2018 | CSFIRE | CSFIRE | reference review report for comments to be addressed (see full review) | csfdit | CO Springs Fire | 1034843 |
CO Springs DRE | Original | D | 1/31/2018 | MSCHULTZ | MSCHULTZ | Plan sets are okay - Plat needs to be recorded (Vistas at Spring Creek Filing No 1) and financial assurance secured before issuance of a building permit (see full review) | | CO Springs DRE | 1033599 |
CSU Contract Admin. | Original | D | 1/30/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. ZJS | zshearer | CSU Contract Admin. | 1033021 |
Plan Coordinator | Original | / | 1/26/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1032285 |
Mechanical | Original | D | 1/26/2018 | JUSTINC | JUSTINC | Clarify on plan with note or indicate on floor plan how providing return air paths. Verify details for furnaces with floor plans? They do not appear to match? See plan for additional info. Clarify on plan how providing minimum 100 square inch makeup air to laundry rooms Clarify if a range hood will be installed? Verify if range hood is installed if makeup air will be required if so indicate how providing. Provide fire/fire-smoke damper schedule indicate brands, model numbers,UL listing
See plan for all additional comments and clarifications.
MECHANICAL REVIEW INCOMPLETE PENDING DESIGN TEAM RESPONSES NO WALK
For all written PPRBD comments on plan see plan track # 102897
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1032283 |
Mechanical | Original | / | 1/26/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1032147 |
Mechanical | Original | / | 1/24/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1031175 |
Plan Coordinator | Original | / | 1/23/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1031138 |
Electrical | Original | D | 1/23/2018 | BERTHA | BERTHA | 1. Approval pending approval by Enumerations. 2. Provide secondary addressing on meter stack on one-line diagram. 3. Approval pending approval by Construction - Accessibility sheet is required.
Complete re-review required.
Plans in this series 102871 (Type 3), 102869 (Type 1B), 101847 (Type 4), 102897 (Type 1), 102870 (Type 3B) (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1031137 |
Electrical | Original | / | 1/17/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1029376 |
Plumbing | Original | D | 1/2/2018 | TCRIPPEN | TCRIPPEN | fix note 4 on P 3.2 all accessible units to be marked and show what type A or B ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1025244 |
Electrical | Original | / | 1/2/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1025172 |
Plan Coordinator | Original | / | 1/2/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1025158 |
Construction | Original | D | 1/2/2018 | MICHAELA | MICHAELA | Soils report needs to be recertified Correct code study Please use building type as the primary descriptor for all plans Does this plan cove type 3B Provide accessibility plan per RBD requirements Revise egress plan wall ratings to match correct floor plan Do not show rating extending in between unit and mechanical room Correct code data Locate attic access on third floor floor plan Label windows Exit enclosure must comply with 1022.6 at intersection of exterior wall Doors may not encroach corridor width more than half of the required width Provide floor assemblies for TJI floor construction Add a building section for area open to below Remove overall plans that do not apply on floor plan pages Type B option B units may not have a fixture in the required clear floor space for the tub Doors may not swing into the required clear floor space for any fixture unless a turning radius is provided beyond the door swing Fire suppression room is not shown on floor plan Clarify how attic will be accessed Show both beam orientations at garage ceiling at deck - clarify how protection of dwelling unit will be continuous How can TJI floor system be used at exposed deck condition Clarify where floating wall will be used on post tension slab No walk-through
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1025155 |
Construction | Original | / | 12/29/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1024911 |
Construction | Original | / | 12/27/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1024248 |
Enumeration | Original | D | 12/27/2017 | AMY | AMY | WHEN CHECKING IN THE PLANS BUILDING TYPE SHOULD CORRESPOND WITH ASSIGNED ADDRESSES- THIS WAS NOT THE CASE. PLAN CHECKED IN UNDER 1864 BIRMINGHAM LOOP BUT THE ADDRESS ASSIGNED IN THIS LOCATION IS 1850 CHIPPENHAM HEIGHTS/TYPE 3 BUILDING. ON CODE STUDY FORM- ZIP CODE IS INCORRECT & CURRENT LEGAL DESCRIPTION FROM THE EL PASO COUNTY ASSESSOR;S SHOULD BE APPLIED ON THIS LINE. ON PAGE AD.3-SECONDARY ADDRESSING LOCATION-UNIT 205 SHOULD BE 203 & 305 SHOULD BE 303. ON PAGE AO.1-ADD ALL ADDRESSES TO ALL APARTMENT BUILDINGS. APPROVAL IN THIS DEPARTMENT IS PENDING REVIEW OF THE MYLAR PRIOR TO PLAT. ADDRESSING FEE OF $10.00 PER LOT AND TRACT, A COPY OF THE FINAL RECORDED PLAT IS REQUIRED ALONG WILL ALL INFO ABOVE.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1024195 |
Plan Coordinator | Original | / | 12/27/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1024183 |
Floodplain | Original | N | 12/27/2017 | AMY | AMY | | | Floodplain | 1024184 |
Enumeration | Original | A | 12/27/2017 | AMY | AMY | WHEN CHECKING IN THE PLANS BUILDING TYPE SHOULD CORRESPOND WITH ASSIGNED ADDRESSES- THIS WAS NOT THE CASE. PLAN CHECKED IN UNDER 1864 BIRMINGHAM LOOP BUT THE ADDRESS ASSIGNED IN THIS LOCATION IS 1850 CHIPPENHAM HEIGHTS/TYPE 3 BUILDING. ON CODE STUDY FORM- ZIP CODE IS INCORRECT & CURRENT LEGAL DESCRIPTION FROM THE EL PASO COUNTY ASSESSOR;S SHOULD BE APPLIED ON THIS LINE. ON PAGE AD.3-SECONDARY ADDRESSING LOCATION, ON PAGE AO.1-ADD ALL ADDRESSES TO ALL APARTMENT BUILDINGS. APPROVAL IN THIS DEPARTMENT IS PENDING REVIEW OF THE MYLAR PRIOR TO PLAT. ADDRESSING FEE OF $10.00 PER LOT AND TRACT, A COPY OF THE FINAL RECORDED PLAT IS REQUIRED ALONG WILL ALL INFO ABOVE. | | Enumeration | 1024182 |
Enumeration | Original | / | 12/27/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 1024143 |