Construction | Splice 07/23/19 | A | 7/24/2019 | MICHAELA | MICHAELA | Revise wall configuration | | Construction | 1216015 |
Electrical | Splice 06/06/19 | A | 6/6/2019 | BERTHA | BERTHA | Revised one-line per inspector's comments. | | Electrical | 1199178 |
Electrical | Splice 06/06/19 | D | 6/6/2019 | BERTHA | BERTHA | Per inspector's comments 3/0 AL is installed. Revise plans to reflect the installation.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1199018 |
Electronic Plan | Splice 06/06/19 | / | 6/6/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1199011 |
Mechanical | Splice 04/12/19 | A | 4/16/2019 | JUSTINC | JUSTINC | Water heater venting revisions | | Mechanical | 1179253 |
Electronic Plan | Splice 04/12/19 | / | 4/15/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1178886 |
Construction | Splice 03/06/19 | A | 3/6/2019 | MICHAELA | MICHAELA | Revise wall types | | Construction | 1165605 |
Out to Review | Splice 03/06/19 | / | 3/6/2019 | BECKYA | BECKYA | | | Out to Review | 1165530 |
Construction | Splice 01/17/19 Trusses | A | 1/22/2019 | MICHAELA | MICHAELA | | | Construction | 1151562 |
Resubmittal 1 | Splice 01/17/19 Trusses | / | 1/22/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1151482 |
Construction | Splice 01/17/19 Trusses | D | 1/22/2019 | MICHAELA | MICHAELA | The shop stamp needs to be checked "Reviewed". Address the comments, get a new stamp from the engineer. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1151409 |
Scanned/Finished Bin | 11/2/18 | / | 12/20/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1144012 |
To Be Scanned Bin | 11/2/18 | / | 12/19/2018 | | BECKYA | Location = To Be Scanned Bin by BECKYA | | To Be Scanned Bin | 1143431 |
Out to Review | 11/2/18 | / | 12/19/2018 | SHELLEY | SHELLEY | kyleen walking | | Out to Review | 1143428 |
Construction | 11/2/18 | A | 12/19/2018 | SHELLEY | SHELLEY | Complete re-review of plans | | Construction | 1143426 |
Plumbing | 11/2/18 | A | 11/16/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1131852 |
Finished Bin | 11/2/18 | / | 11/12/2018 | | SCANNING | Location = Finished Bin by SCANNING In oversized bin in a bundle | | Finished Bin | 1129678 |
Plan Coordinator | 11/2/18 | / | 11/12/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1129648 |
Plumbing | 11/2/18 | D | 11/12/2018 | TCRIPPEN | TCRIPPEN | Need to add F-22 to fixture schedule cloud and resubmit P-16 okay removed pages not required for this splice,Note: Seven plans in this set 86589, 86591, 86592, 86593, 102937, 103064, 103066 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1129647 |
Plumbing | 11/2/18 | / | 11/12/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1129637 |
Plumbing | 11/2/18 | / | 11/12/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1129581 |
Plan Coordinator | 11/2/18 | / | 11/12/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1129539 |
Electrical | 11/2/18 | A | 11/12/2018 | SHELBY | SHELBY | Maintenance garage only Note: Seven plans in this set 86589, 86591, 86592, 86593, 102937, 103064, 103066 | | Electrical | 1129538 |
Electrical | 11/2/18 | / | 11/9/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1129308 |
Electrical | 11/2/18 | / | 11/9/2018 | | JUSTINC | Location = Electrical by JUSTINC | | Electrical | 1129307 |
Plan Coordinator | 11/2/18 | / | 11/8/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1128946 |
Mechanical | 11/2/18 | A | 11/8/2018 | JUSTINC | JUSTINC | | | Mechanical | 1128945 |
Mechanical | 11/2/18 | / | 11/7/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1128028 |
Plan Coordinator | 11/2/18 | / | 11/6/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1127908 |
Electrical | 11/2/18 | D | 11/6/2018 | SHELBY | SHELBY | Include only sheets with revisions ( cloud all changes). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1127907 |
Electrical | 11/2/18 | / | 11/6/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1127632 |
Electrical | 11/2/18 | / | 11/6/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1127603 |
Plan Coordinator | 11/2/18 | / | 11/5/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1127551 |
Construction | 11/2/18 | D | 11/5/2018 | MICHAELA | MICHAELA | Clarify why walls and roof/ceiling are rated - appears to be separated use? Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1127550 |
Construction | 11/2/18 | / | 11/5/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1127208 |
Construction | 11/2/18 | / | 11/2/2018 | | NELIDA | Location = Construction by NELIDA | | Construction | 1126996 |
Construction | Splice 7/31/18 | A | 8/1/2018 | MICHAELA | MICHAELA | Trusses | | Construction | 1095220 |
Scanned/Finished Bin | Original | / | 4/6/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1054907 |
To Be Scanned Bin | Original | / | 4/5/2018 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1054544 |
Fountain Waste Water | Original | A | 4/5/2018 | GITA | GITA | | | Fountain Waste Water | 1054534 |
Widefield Water | Original | A | 4/5/2018 | GITA | GITA | | | Widefield Water | 1054533 |
Widefield Water | Original | N | 4/5/2018 | GITA | GITA | | | Widefield Water | 1054532 |
Fountain Zoning | Original | A | 4/5/2018 | GITA | GITA | | | Fountain Zoning | 1054531 |
Out to Review | Original | / | 3/28/2018 | AMY | AMY | TERI P | | Out to Review | 1051425 |
Enumeration | Original | A | 3/26/2018 | AMY | AMY | | | Enumeration | 1050618 |
Enumeration | Original | / | 3/26/2018 | | GITA | Location = Enumeration by GITA | | Enumeration | 1050341 |
Finished Bin | Original | / | 3/23/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1050036 |
Plan Coordinator | Original | / | 3/23/2018 | | JAY | Location = Plan Coordinator by JAY | | Plan Coordinator | 1049923 |
Construction | Original | A | 3/23/2018 | JAY | JAY | OK | | Construction | 1049922 |
Construction | Original | / | 3/22/2018 | | GITA | Location = Construction by GITA | | Construction | 1049794 |
Out to Review | Original | / | 3/14/2018 | MICHAELA | MICHAELA | Terri | | Out to Review | 1046986 |
Construction | Original | D | 3/14/2018 | MICHAELA | MICHAELA | Allowable bearing must match soils report Walk OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1046984 |
Construction | Original | / | 3/14/2018 | GITA | GITA | construction only | | Construction | 1046915 |
Out to Review | Original | / | 3/12/2018 | JANE | JANE | Teri | | Out to Review | 1045841 |
Finished Bin | Original | / | 3/12/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1045514 |
Enumeration | Original | D | 3/12/2018 | AMY | AMY | ENUMERATIONS/FLOODPLAIN WILL REVIEW THE MYLAR PRIOR TO PLAT FOR ADDRESS PLACEMENT, ROAD NAMING, TITLE BLOCK, & FLOODPLAIN STATEMENT.
$10.00 PER LOT & TRACT FEE WILL BE DUE AT THE TIME OF THE REVIEW OF THE MYLAR. IF AN ADDRESS IN NOT NEEDED ON A TRACT THEN NO FEE APPLIES. CHECK SHOULD BE MADE OUT TO PIKES PEAK REGIONAL BUILDING DEPARTMENT. PAID DIRECTLY TO ENUMERATIONS DEPARTMENT.
A COPY OF THE FINAL RECORDED PLAT IS REQUIRED PRIOR TO APPROVAL IN ENUMERATIONS DEPARTMENT ON ANY COMMERCIAL PLANS SUBMITTAL.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1045480 |
Plan Coordinator | Original | / | 3/12/2018 | AMY | AMY | In Current Review by AMY | | Plan Coordinator | 1045473 |
Plan Coordinator | Original | / | 3/9/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1045287 |
Construction | Original | D | 3/9/2018 | MICHAELA | MICHAELA | Provide soils report dated less than 24 mos. or recertify the report provided. Walk OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1045286 |
Enumeration | Original | / | 3/9/2018 | | SCANNING | Location = Enumeration by SCANNING | | Enumeration | 1045278 |
Construction | Original | / | 3/9/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1045269 |
Construction | Original | / | 3/8/2018 | | RITA | Location = Construction by RITA | | Construction | 1044967 |
Resubmittal 1 | Original | / | 3/8/2018 | RITA | RITA | 1st Resubmittal | | Resubmittal 1 | 1044956 |
Electrical | Original | A | 3/7/2018 | SHELBY | SHELBY | Release is for garage only | | Electrical | 1044561 |
Plumbing | Original | A | 3/7/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1044526 |
Mechanical | Original | A | 3/7/2018 | JUSTINC | JUSTINC | | | Mechanical | 1044515 |
Plumbing | Original | N | 2/26/2018 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 1040964 |
Fountain Fire | Original | A | 2/2/2018 | FNTNFIRE | FNTNFIRE | MAS Fountain Fire Department OK | mstanwood | Fountain Fire | 1034416 |
Health Dept. | Original | N | 2/1/2018 | HEALTHDEPT | HEALTHDEPT | Construction activity permit issued 12/29/17. AnkitP 719-578-3278 | Aparikh | Health Dept. | 1033774 |
Out to Review | Original | / | 1/22/2018 | JANE | JANE | Teri | | Out to Review | 1030593 |
Finished Bin | Original | / | 1/19/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1030247 |
Plan Coordinator | Original | / | 1/19/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1030230 |
Mechanical | Original | D | 1/19/2018 | JUSTINC | JUSTINC | Garages have been indicated as S-2. Per the 09' IBC S-2 garages are classified as "enclosed parking garages" Per the 09' IMC 403.3 (STORAGE) "enclosed parking garages" Which will require mechanical ventilation. Also see 09' IMC 404 Indicate condensate routing, pipe sizes, termination location on plan per 09' IMC 307.
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1030229 |
Mechanical | Original | / | 1/19/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1030172 |
Mechanical | Original | / | 1/18/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1029849 |
Plan Coordinator | Original | / | 1/18/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1029828 |
Electrical | Original | D | 1/18/2018 | BERTHA | BERTHA | 1. Provide conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work. 2. Provide footprint (site plan) showing all electrical service equipment and disconnects serving the structure. 3. Provide listed combinations for series rating. 4. Provide only the information pertaining to this scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1029827 |
Electrical | Original | / | 1/17/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1029374 |
Electrical | Original | / | 1/16/2018 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 1028618 |
Plumbing | Original | D | 1/16/2018 | TCRIPPEN | TCRIPPEN | Provide an water pipe size analysis data on plans , indicate which fixture you are using for the maintenance area, need an approve occupant load for fixture count, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1028616 |
Plumbing | Original | / | 1/16/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1028569 |
Plumbing | Original | / | 1/16/2018 | | TCRIPPEN | Location = Plumbing by TCRIPPEN | | Plumbing | 1028568 |
Electrical | Original | / | 1/11/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1027815 |
Plan Coordinator | Original | / | 1/11/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1027795 |
Construction | Original | D | 1/11/2018 | MICHAELA | MICHAELA | Clarify the purpose of the exterior and interior rated walls Provide a soils report Missing structural pages Missing IECC certificate for conditioned space Indicate compliance with IBC section 1210 for toilet room walls and floor Correct the Code Analysis Indicate which rated assemblies are required and remove the rest No Walk-through
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1027793 |
Construction | Original | / | 1/9/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1026985 |
Construction | Original | / | 1/8/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1026872 |
Plan Coordinator | Original | / | 1/8/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1026821 |
Enumeration | Original | D | 1/8/2018 | AMY | AMY | 2-GARAGES FOR THIS PLAN 7684 PHOEBE RIVER & 7641 CAMERON VISTA POINT.
APPROVAL PENDING COPY OF THE FINAL RECORDED PLAT. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1026820 |
Enumeration | Original | / | 1/8/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1026813 |
Enumeration | Original | / | 1/4/2018 | | BPHILLIPS | Location = Enumeration by BPHILLIPS | | Enumeration | 1026015 |
Construction | Original | / | 1/3/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1025378 |
Construction | Original | / | 12/29/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1024892 |
Enumeration | Original | D | 12/29/2017 | AMY | AMY | PENDING COPY OF FINAL RECORDED PLAT (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1024866 |
Plan Coordinator | Original | / | 12/29/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1024854 |
Enumeration | Original | A | 12/29/2017 | AMY | AMY | 7684 PHOEBE RIVER VIEW & 7641 CAMERON VISTA POINT 2-6 BAY GARAGES W/HANDICAP ACCESSIBLY,
7679 MCGEE VIEW 1 MAINTENANCE BLDG W/6 BAY GARAGE ATTACHED,
7643 ROB POINT, 7664 MCGEE VIEW, 7671 CAMERON VISTA POINT & 7621 CAMERON VISTA POINT 4-6 BAY GARAGES.
1 PLAN & 7 PERMITS WILL BE REQUIRED | | Enumeration | 1024853 |
Enumeration | Original | / | 12/29/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 1024806 |
Floodplain | Original | N | 12/27/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5529100017) | | Floodplain | 1024340 |