Mechanical | Splice 06/14/22 | A | 6/15/2022 | JUSTINC | JUSTINC | Revised duct layout, removed booster fans, revised schedule - Changes by contractor accepted per JE. | | Mechanical | 1698993 |
Electronic Plan | Splice 06/14/22 | / | 6/15/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1698733 |
Mechanical | Splice 06/11/20 | A | 6/11/2020 | JUSTINC | JUSTINC | Gas lines ran in 3/4 Gastite CSST | | Mechanical | 1334769 |
Electronic Plan | Splice 06/11/20 | / | 6/11/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1334754 |
Electrical | Splice 06/04/20 | A | 6/4/2020 | BERTHA | BERTHA | Revised breakers. | | Electrical | 1331842 |
Electronic Plan | Splice 06/04/20 | / | 6/4/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1331824 |
Electrical | Splice 06/01/20 | A | 6/3/2020 | BECKYA | BECKYA | per BA | | Electrical | 1330710 |
Electrical | Splice 06/01/20 | A | 6/2/2020 | BERTHA | BERTHA | Revised breakers and GEC. | | Electrical | 1330254 |
Electronic Plan | Splice 06/01/20 | / | 6/2/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1330213 |
Construction | Splice 04/20/20 | A | 4/22/2020 | BPHILLIPS | BPHILLIPS | Revised R/C assembly, shear walls. | | Construction | 1312732 |
Electronic Plan | Splice 04/20/20 | / | 4/22/2020 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1312729 |
Resubmittal 1 | Splice 04/20/20 | / | 4/21/2020 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1312416 |
Construction | Splice 04/20/20 | D | 4/21/2020 | BPHILLIPS | BPHILLIPS | Separate splices required for buildings 2 and 3. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1312225 |
Electronic Plan | Splice 04/20/20 | / | 4/20/2020 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1311974 |
To Be Scanned Bin | Splice 10/08/19 - Trusses | / | 12/4/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1262989 |
Plan Coordinator | Splice 10/08/19 - Trusses | / | 12/4/2019 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1262962 |
Construction | Splice 10/08/19 - Trusses | A | 12/4/2019 | BPHILLIPS | BPHILLIPS | Provided floor and roof trusses with layouts. | | Construction | 1262961 |
Construction | Splice 10/08/19 - Trusses | / | 12/3/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1262680 |
Construction | Splice 10/08/19 - Trusses | / | 12/3/2019 | | NELIDA | Location = Construction by NELIDA | | Construction | 1262646 |
Resubmittal 1 | Splice 10/08/19 - Trusses | / | 12/3/2019 | NELIDA | NELIDA | Resubmittal #1 12/3/19 | | Resubmittal 1 | 1262645 |
Finished Bin | Splice 10/08/19 - Trusses | / | 10/8/2019 | | SCANNING | Location = Flat finished bin. | | Finished Bin | 1243883 |
Plan Coordinator | Splice 10/08/19 - Trusses | / | 10/8/2019 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1243811 |
Construction | Splice 10/08/19 - Trusses | D | 10/8/2019 | BPHILLIPS | BPHILLIPS | Many truss profiles sheets either missing engineer's stamp or stamp illegible. Missing shop stamp on layout. No review performed. No walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1243810 |
Construction | Splice 10/08/19 - Trusses | / | 10/8/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1243783 |
Construction | Splice 10/08/19 - Trusses | / | 10/8/2019 | | JANE | Location = Construction by JANE | | Construction | 1243735 |
CSU Contract Admin. | Original | A | 1/2/2019 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved, applicable development charges and fees paid. MKL | mkluke | CSU Contract Admin. | 1146054 |
CSU Contract Admin. | Original | / | 1/2/2019 | CSUAPPSPRM | CSUAPPSPRM | | mkluke | CSU Contract Admin. | 1146052 |
City Engr | Original | A | 10/15/2018 | PMORRIS | PMORRIS | | | City Engr | 1120024 |
CO Springs DRE | Original | A | 10/12/2018 | HVANNIMWEGEN | HVANNIMWEGEN | Approved development plan uploaded. All comments addressed. (see full review) | | CO Springs DRE | 1119460 |
Water Division | Original | A | 10/12/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | Water Division | 1119406 |
Waste Water Div | Original | A | 10/12/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | Waste Water Div | 1119405 |
Gas/Elec. Utils | Original | A | 10/12/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | Gas/Elec. Utils | 1119404 |
CSU Contract Admin. | Original | D | 10/12/2018 | CSUAPPSPRM | CSUAPPSPRM | Same comment as 7/30/18. ZJS | zshearer | CSU Contract Admin. | 1119346 |
Zoning/Planning | Original | / | 10/11/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In Current Review by HVANNIMWEGEN | | Zoning/Planning | 1119294 |
Enumeration | Original | A | 10/11/2018 | AMY | AMY | | | Enumeration | 1119114 |
Electronic Plan | Original | / | 10/11/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1119109 |
Resubmittal 5 | Original | / | 10/11/2018 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1119081 |
CO Springs DRE | Original | D | 10/10/2018 | HVANNIMWEGEN | HVANNIMWEGEN | Please upload the copy of the development plan which is stamped. Please let Hannah Van Nimwegen know if a copy of the approved set is needed. 719-385-5365. CGS reviewed and approved the set. (see full review) | | CO Springs DRE | 1118512 |
City Engr | Original | D | 9/27/2018 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan. jad | | City Engr | 1114528 |
Water Division | Original | D | 9/26/2018 | CSUREVIEW | CSUREVIEW | Some comments have been addressed, but a copy of the approved Development Plan must be included in the permit set prior to CSU approval. JPN | jnoble | Water Division | 1114136 |
Waste Water Div | Original | D | 9/26/2018 | CSUREVIEW | CSUREVIEW | Some comments have been addressed, but a copy of the approved Development Plan must be included in the permit set prior to CSU approval. JPN | jnoble | Waste Water Div | 1114135 |
Gas/Elec. Utils | Original | D | 9/26/2018 | CSUREVIEW | CSUREVIEW | Some comments have been addressed, but a copy of the approved Development Plan must be included in the permit set prior to CSU approval. JPN | jnoble | Gas/Elec. Utils | 1114134 |
CSU Contract Admin. | Original | D | 9/26/2018 | CSUAPPSPRM | CSUAPPSPRM | Same comment as 7/30/18. ZJS | zshearer | CSU Contract Admin. | 1114057 |
Zoning/Planning | Original | / | 9/25/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In Current Review by HVANNIMWEGEN | | Zoning/Planning | 1113683 |
Resubmittal 4 | Original | / | 9/25/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1113542 |
CO Springs DRE | Original | D | 9/6/2018 | HVANNIMWEGEN | HVANNIMWEGEN | Pending CGS review (see full review) | | CO Springs DRE | 1107211 |
Plumbing | Original | A | 8/6/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1097041 |
CO Springs Fire | Original | A | 8/6/2018 | CSFIRE | CSFIRE | REFERENCE ONLINE REVIEW REPORT FOR INFORMATION REGARDING INSPECTIONS! (see full review) | csfdit | CO Springs Fire | 1096884 |
CO Springs Fire | Original | A | 8/6/2018 | CSFIRE | CSFIRE | REFERENCE ONLINE REVIEW REPORT FOR INFORMATION REGARDING INSPECTIONS! (see full review) | csfdit | CO Springs Fire | 1096883 |
City Engr | Original | D | 8/3/2018 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Water Resources Engineering approved Grading & Erosion Control Plan. jad | | City Engr | 1096514 |
CSU Contract Admin. | Original | D | 7/30/2018 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved 5/16/2018; however, still requires payment of applicable development charges and fees. MKL | mkluke | CSU Contract Admin. | 1094228 |
Health Dept. | Original | N | 7/27/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable | galvarez | Health Dept. | 1094065 |
Electrical | Original | A | 7/27/2018 | SHELBY | SHELBY | | | Electrical | 1093745 |
Mechanical | Original | A | 7/27/2018 | JUSTINC | JUSTINC | Sheets resubmitted before permit | | Mechanical | 1093743 |
Electronic Plan | Original | / | 7/27/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1093741 |
Zoning/Planning | Original | / | 7/26/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In Current Review by HVANNIMWEGEN | | Zoning/Planning | 1093722 |
Gas/Elec. Utils | Original | D | 7/26/2018 | CSUREVIEW | CSUREVIEW | See previous comments. ERW
Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. | ewidrick | Gas/Elec. Utils | 1093455 |
Water Division | Original | D | 7/26/2018 | CSUREVIEW | CSUREVIEW | See previous comments. ERW
Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. | ewidrick | Water Division | 1093462 |
Waste Water Div | Original | D | 7/26/2018 | CSUREVIEW | CSUREVIEW | See previous comments. ERW
Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. | ewidrick | Waste Water Div | 1093460 |
Construction | Original | A | 7/26/2018 | BPHILLIPS | BPHILLIPS | | | Construction | 1093434 |
Electronic Plan | Original | / | 7/25/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1092872 |
Enumeration | Original | A | 7/24/2018 | AMY | AMY | | | Enumeration | 1092856 |
Electronic Plan | Original | / | 7/24/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1092847 |
Resubmittal 3 | Original | / | 7/24/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1092744 |
CO Springs DRE | Original | D | 5/17/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In review by CGS (see full review) | | CO Springs DRE | 1069855 |
CO Springs Fire | Original | D | 5/10/2018 | CSFIRE | CSFIRE | Pending approved water plans. (see full review) | csfdit | CO Springs Fire | 1067103 |
Health Dept. | Original | D | 5/10/2018 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application For questions contact Environmental Health at 719-578-3199 option 3. | rnielsen | Health Dept. | 1066949 |
City Engr | Original | D | 5/9/2018 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering approved Grading & Erosion Control Plan. jad | | City Engr | 1066638 |
Plumbing | Original | D | 5/8/2018 | TCRIPPEN | TCRIPPEN | only one fixture per 1/2 inch water line all so missing sizes on your isometrics all lines should have a size on it///// mike called on 5-30-18 and will adjust sizes on fixture schedule and one fixture per 1/2 waterline\\\\\
. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1066104 |
Mechanical | Original | A | 5/8/2018 | JUSTINC | JUSTINC | | | Mechanical | 1065976 |
Electronic Plan | Original | / | 5/8/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1065840 |
Construction | Original | D | 5/7/2018 | BPHILLIPS | BPHILLIPS | Provide CRS compliance information per accessibility handout on our website. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1065724 |
CSU Contract Admin. | Original | D | 5/7/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | aguerin | CSU Contract Admin. | 1065358 |
CO Springs DRE | Original | / | 5/7/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In review by Colorado Geologic Survey | | CO Springs DRE | 1065338 |
Electronic Plan | Original | / | 5/7/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1065313 |
Electrical | Original | D | 5/4/2018 | SHELBY | SHELBY | Pending construction ( Accessibility plan). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1065100 |
Gas/Elec. Utils | Original | D | 5/4/2018 | CSUREVIEW | CSUREVIEW | See previous comments. ERW | ewidrick | Gas/Elec. Utils | 1064879 |
Water Division | Original | D | 5/4/2018 | CSUREVIEW | CSUREVIEW | See previous comments. ERW | ewidrick | Water Division | 1064878 |
Waste Water Div | Original | D | 5/4/2018 | CSUREVIEW | CSUREVIEW | See previous comments. ERW | ewidrick | Waste Water Div | 1064877 |
Zoning/Planning | Original | / | 5/4/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In Current Review by HVANNIMWEGEN | | Zoning/Planning | 1064875 |
Construction | Original | D | 5/4/2018 | BPHILLIPS | BPHILLIPS | Architectural submittal has electronic permission issue which does not allow markup. No review performed. Change permission settings and resubmit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1064850 |
Enumeration | Original | A | 5/3/2018 | AMY | AMY | SECONDARY ADDRESSING SHEETS PAGES T2.TA & T2.2A | | Enumeration | 1064574 |
Electronic Plan | Original | / | 5/3/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1064564 |
Resubmittal 2 | Original | / | 5/3/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1064349 |
Plan Coordinator | Original | D | 4/4/2018 | BPHILLIPS | BPHILLIPS | Disapprove all remaining departments to allow plan to be resubmitted.
Resubmittal missing critical sheets from original review. No review performed. Call Brett Phillips @ 719-327-2917 with questions. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1053668 |
Electronic Plan | Original | / | 4/4/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1053627 |
Enumeration | Original | A | 4/4/2018 | AMY | AMY | ADDRESSING PLAN FOR ALL BUILDINGS PAGE-DP 5 OF 25
SECONDARY ADDRESSING PAGES-A1.0A & A1.1A.
COPY OF THE FINAL PLAT RECEIVED.
ADDRESSING FOR TRASH ENCLOSURES NOT REQUIRED DUE TO HEIGHT UNDER 7FT-REMOVE FROM PLAN. | | Enumeration | 1053596 |
Enumeration | Original | D | 4/4/2018 | AMY | AMY | REMOVE PAGE A3.5 TRASH ENCLOSURE PAGES-FENCING AND WALL ARE UNDER 7FT AND DO NOT REQUIRE AN ADDRESS OR PERMIT. REMOVE ADDRESSING 4323 & 4380 TIMBERVIEW POINT FOR THE TRASH ENCLOSURES FROM ALL SITE PLANS. ALSO REMOVE THE SIGN- SEPARATE ADDRESS AND PLAN REQUIRED. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1053594 |
Electronic Plan | Original | / | 4/4/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1053593 |
Electronic Plan | Original | / | 4/4/2018 | TIMA | TIMA | In Current Review by TIMA | | Electronic Plan | 1053583 |
Electronic Plan | Original | / | 4/4/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1053581 |
Resubmittal 1 | Original | / | 4/3/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1053423 |
CO Springs DRE | Original | D | 3/1/2018 | MBINGMAN | MBINGMAN | Pending Development plan approval and CGS review - please submit stamped approved development plan when complete. MRB per HVN (see full review) | | CO Springs DRE | 1042186 |
Mechanical | Original | D | 1/29/2018 | JUSTINC | JUSTINC | Add note: Provide 1 copy of test and balance report to mechanical inspector at time of heating final inspection. Add note: Gas is an engineered system Add note: Water heaters are to be electric Add note: Radiation dampers at all membrane penetrations. (TYP.) Provide section view detail of range hood and vent penetrations through rated floor/ceiling assembly to clarify how protecting. Furnace supply plenum damper to be dynamic per indicated application per 09' IMC 607.3.1 See detail Provide on plan fire / fire-smoke damper schedule. Indicate Brand and model number. Clarify locations of each damper to verify it is compatible with wall rating and UL listings Only dryer booster fan acceptable model is FANTECH DEDPV-705UL Provide schedule for range hoods vented to exterior. Indicate if range hood will require makeup air per 09' IMC 505.2. If they will indicate how providing. How providing outside air to furnaces? No O.S.A duct indicated? Indicate size and duct routing.Indicate by unit type not bedrooms Clarify on plan return air paths (TYP.)
MECHANICAL REVIEW INCOMPLETE PENDING DESIGN TEAM RESPONSES
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1032407 |
Electronic Plan | Original | / | 1/29/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1032331 |
Hazmat | Original | N | 1/24/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1031590 |
CO Springs Fire | Original | D | 1/24/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1031589 |
Plumbing | Original | D | 1/24/2018 | TCRIPPEN | TCRIPPEN | P1.U where do the vertical risers go and what number goes where, missing sizes on water lines.P2.0 provide risers for storm drains. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1031334 |
Electronic Plan | Original | / | 1/24/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1031210 |
Electrical | Original | D | 1/23/2018 | SHELBY | SHELBY | 1. Provide accessibility plan ( see construction review comments). 2. Show available fault current on one line. Note: Three plans in this series 103150, 103161,103163 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1031146 |
City Engr | Original | D | 1/23/2018 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering approved Grading and Erosion Control Plan in the electronic building permit set. jad | | City Engr | 1031108 |
Zoning/Planning | Original | / | 1/23/2018 | HVANNIMWEGEN | HVANNIMWEGEN | In Current Review by HVANNIMWEGEN | | Zoning/Planning | 1030941 |
Gas/Elec. Utils | Original | D | 1/22/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. JPN | jnoble | Gas/Elec. Utils | 1030696 |
Water Division | Original | D | 1/22/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. JPN | jnoble | Water Division | 1030687 |
Waste Water Div | Original | D | 1/22/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. JPN | jnoble | Waste Water Div | 1030685 |
CSU Contract Admin. | Original | D | 1/22/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf
AG | aguerin | CSU Contract Admin. | 1030677 |
Health Dept. | Original | D | 1/22/2018 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required. Contact 578-3199 option #3 for more information regarding construction activity permits. AP 578-3278 | Aparikh | Health Dept. | 1030670 |
Construction | Original | D | 1/22/2018 | BPHILLIPS | BPHILLIPS | Provide CRS compliance information. Clarify if units marked as "accessible" are Type A units or fully accessible. Provide 2-sided assembly for corridors.Indicate wall types where noted. Correct labeling orientation where noted. Balconies require fire protection. Clarify how complying. Provide enlarged detail where assemblies intersect. Provide sheet A3.0. Cross out or delete all information not pertaining to this building. Turning space required at balcony. Recessed fire extinguisher cabinets are inside rated assembly. Indicate how rating maintained. Revise door schedule. Provide 1-hr floor/ceiling assembly for breezeways (corridors). In listed assemblies with multiple systems, indicate which system used. Trusses pending. See plans for all comments. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1030495 |
Electronic Plan | Original | / | 1/16/2018 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1028789 |
Enumeration | Original | D | 1/11/2018 | AMY | AMY | ON CODE STUDY FORM THE TAX SCHEDULE NUMBER AND LEGAL DESCRIPTION WILL CHANGE.
ON PAGE T2.0A & T4.0A REMOVE THE SECONDARY ADDRESSING FROM THE BUILDINGS. PAGE T2.1A & T2.2A ARE THE SECONDARY REFERENCE PAGES . REMOVE PAGE A3.5 TRASH ENCLOSURE PAGES-FENCING AND WALL ARE UNDER 7FT AND DO NOT REQUIRE AN ADDRESS OR PERMIT. REMOVE ADDRESSING 4323 & 4380 TIMBERVIEW POINT FOR THE TRASH ENCLOSURES FROM ALL SITE PLANS. ALSO REMOVE THE SIGN- SEPARATE ADDRESS AND PLAN REQUIRED. APPROVAL OF THIS PLAN IS PENDING THE REVIEW OF THE MYLAR, ADDRESSING FEE, AND A COPY OF THE FINAL RECORDED PLAT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1027968 |
Electronic Plan | Original | / | 1/11/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1027811 |
Floodplain | Original | N | 1/9/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6506410108) | | Floodplain | 1027044 |