Out to Review | Original | / | 3/23/2018 | GITA | GITA | Colin | | Out to Review | 1050138 |
Scanned/Finished Bin | Original | / | 3/23/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1049878 |
To Be Scanned Bin | Original | / | 3/23/2018 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1049851 |
Waste Water Div | Original | A | 3/23/2018 | GITA | GITA | | | Waste Water Div | 1049850 |
Water Division | Original | A | 3/23/2018 | GITA | GITA | | | Water Division | 1049849 |
Monument Zoning | Original | A | 3/23/2018 | GITA | GITA | | | Monument Zoning | 1049848 |
Hazmat | Original | A | 3/16/2018 | CSFIRE | CSFIRE | Plans approved. Please read approval comments. Plans forwarded to Waste Water. (see full review) | smanning | Hazmat | 1048122 |
Hazmat | Original | / | 3/15/2018 | | SCANNING | Location = Hazmat by SCANNING | | Hazmat | 1047447 |
Plan Coordinator | Original | / | 3/15/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1047446 |
Mechanical | Original | A | 3/15/2018 | JUSTINC | JUSTINC | | | Mechanical | 1047445 |
Mechanical | Original | / | 3/15/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1047316 |
Mechanical | Original | / | 3/14/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1047134 |
Plan Coordinator | Original | / | 3/14/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1047123 |
Electrical | Original | A | 3/14/2018 | SHELBY | SHELBY | | | Electrical | 1047120 |
Construction | Original | A | 3/14/2018 | SHELLEY | SHELLEY | revised sheets | | Construction | 1047019 |
Hazmat | Original | D | 2/27/2018 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproval comments. Plans forwarded to Fire Construction Services for holding. (see full review) | smanning | Hazmat | 1041468 |
Hazmat | Original | / | 2/23/2018 | | CSFIRE | Location = Hazmat by CSFIRE | wtaylor | Hazmat | 1040578 |
Tri-Lakes Fire | Original | A | 2/23/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | Tri-Lakes Fire | 1040577 |
Fire | Original | / | 2/16/2018 | | MATTHEWM | Location = Fire by MATTHEWM | | Fire | 1038648 |
Health Dept. | Original | A | 2/16/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | rnielsen | Health Dept. | 1038632 |
Finished Bin | Original | / | 2/16/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1038341 |
Plan Coordinator | Original | / | 2/15/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1038243 |
Mechanical | Original | D | 2/15/2018 | JUSTINC | JUSTINC | Indicate condensate removal for walk-in cooler/freezer per 09' IMC 307. Indicate termination locations. Provide refrigeration calculation per 09' IMC 1103.1 Indicate on plan if within allowable limits per the table. If over the allowable limits indicate on plan how protecting. All must be located on (M) sheet. Provide a complete interlock schedule on (M) sheet. To include but not limited to all associated interlocks for makeup air and shutdowns. ie, RTU-1, RTU-2, EF-2, KH-2, Gas solenoid valves, ect... Add note to plan that wall backing TYPE I hood to be constructed of non-combustible materials. Add note to plan: "Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Air balance indicates within 30% This air balance must be within 10% Vented roof curbs only allowed when duct is to be installed within a 1hour shaft.
NO WALK Questions - Justin C. - 719-327-2899
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1038242 |
Plumbing | Original | A | 2/15/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1038139 |
Mechanical | Original | / | 2/15/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1037928 |
Mechanical | Original | / | 2/15/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1037920 |
Plan Coordinator | Original | / | 2/14/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1037894 |
Electrical | Original | D | 2/14/2018 | SHELBY | SHELBY | 1. Show all disconnects serving the structure on site plan. Include voltage of each disconnect. 2. Remove parallel neutral ( ground) from service lateral. 3. Clearly identify components of this installation on one line completed under the core and shell scope ( UNG for branch panels etc). 4. Show available fault current on one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1037893 |
Electrical | Original | / | 2/14/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1037732 |
Electrical | Original | / | 2/13/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1037039 |
Plan Coordinator | Original | / | 2/13/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1037034 |
Construction | Original | A | 2/13/2018 | MICHAELA | MICHAELA | | | Construction | 1037033 |
Construction | Original | / | 2/13/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1037007 |
Construction | Original | / | 2/12/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1036882 |
Resubmittal 1 | Original | / | 2/12/2018 | SCANNING | SCANNING | Resubmittal #1 | | Resubmittal 1 | 1036881 |
Plumbing | Original | D | 1/26/2018 | TCRIPPEN | TCRIPPEN | Stop reviews this plan will need to be modified to reflect scope of work (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1032210 |
Finished Bin | Original | / | 1/26/2018 | | SCANNING | Location = Finished Bin by SCANNING On hold by TCC | | Finished Bin | 1032027 |
Plumbing | Original | / | 1/25/2018 | | TCRIPPEN | Location = Plumbing by TCRIPPEN | | Plumbing | 1031615 |
Plumbing | Original | D | 1/25/2018 | TCRIPPEN | TCRIPPEN | pending still need splice 100847 to install all plumbing and must match this plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1031614 |
Electrical | Original | / | 1/23/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1030932 |
Plan Coordinator | Original | / | 1/23/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1030911 |
Construction | Original | D | 1/23/2018 | MICHAELA | MICHAELA | Correct information on plan and code study to include entire structure and all occupancies Dining area requires (2) exits - cannot be through kitchen - show entire structure and compliant second exit Add note requiring signage at gate to indicate that gate must remain open when restaurant is in use. Locate required toilet rooms No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1030910 |
Construction | Original | / | 1/23/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1030818 |
Construction | Original | / | 1/23/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1030758 |
Enumeration | Original | A | 1/16/2018 | BRENT | BRENT | Address for the fast food restaurant side of the building is 15445 Terrazzo Dr. | | Enumeration | 1028905 |
Plan Coordinator | Original | / | 1/16/2018 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1028903 |
Floodplain | Original | N | 1/16/2018 | BRENT | BRENT | | | Floodplain | 1028902 |
Floodplain | Original | / | 1/12/2018 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7135000019) | | Floodplain | 1028350 |