Construction | Splice 8/21/18 | A | 8/22/2018 | MICHAELA | MICHAELA | Additional foundation details | | Construction | 1102536 |
Mechanical | Splice 8/14/18 | A | 8/16/2018 | DALEH | DALEH | | | Mechanical | 1100662 |
Resubmittal 1 | Splice 8/14/18 | / | 8/16/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1100648 |
Scanned/Finished Bin | Splice 08/07/18 | / | 8/15/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1099985 |
Mechanical | Splice 8/14/18 | D | 8/15/2018 | DALEH | DALEH | comment from submitter states we installed two fire dampers ....Need to show on floor plans with clouds. The only thing submitted was the fire damper specs. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1099952 |
To Be Scanned Bin | Splice 08/07/18 | / | 8/14/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1099911 |
Plan Coordinator | Splice 08/07/18 | / | 8/14/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1099864 |
Mechanical | Splice 08/07/18 | A | 8/14/2018 | DALEH | DALEH | refrigerant calcs are ok per Jack Arrington | | Mechanical | 1099863 |
Construction | Splice 8/13/18 | A | 8/13/2018 | DANM | DANM | Revisions to existing front and rear entry doors per Fire comments | | Construction | 1099383 |
Out to Review | Splice 8/13/18 | / | 8/13/2018 | BECKYA | BECKYA | | | Out to Review | 1099346 |
Resubmittal 1 | Splice 08/07/18 | / | 8/13/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1099330 |
Finished Bin | Splice 08/07/18 | / | 8/8/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1098085 |
Plan Coordinator | Splice 08/07/18 | / | 8/8/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1097983 |
Mechanical | Splice 08/07/18 | D | 8/8/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Sheet M2.01 Key note #1 indicates to provide door undercut for build up of refrigerant. Verify amounts per room per 09' IMC 1103.1 Indicate calculations on plan. Verify if within allowable limits per table. If over allowable limits indicate on plan how protecting. Door undercut is not protection.
O.S.A removed from units. Indicate how O.S.A ducts to room are to terminate. Indicate duct sizes
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1097982 |
Mechanical | Splice 08/07/18 | / | 8/8/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1097730 |
Mechanical | Splice 08/07/18 | / | 8/7/2018 | | RITA | Location = Mechanical by RITA | | Mechanical | 1097603 |
Construction | Splice | A | 6/22/2018 | LBENNETT | LBENNETT | Revised rated assembly for vertical lift | | Construction | 1082952 |
Out to Review | Splice | / | 6/22/2018 | GITA | GITA | | | Out to Review | 1082932 |
Out to Review | Original | / | 4/11/2018 | NELIDA | NELIDA | scanned plan picked up by Stephen 719-377-0595 | | Out to Review | 1056381 |
Scanned/Finished Bin | Original | / | 4/10/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1055698 |
To Be Scanned Bin | Original | / | 4/10/2018 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1055690 |
Construction | Original | A | 4/6/2018 | MICHAELA | MICHAELA | | | Construction | 1055100 |
Out to Review | Original | / | 3/26/2018 | RITA | RITA | Ralph 632-3384 | | Out to Review | 1050485 |
Finished Bin | Original | / | 3/26/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1050325 |
Plan Coordinator | Original | / | 3/26/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1050299 |
Construction | Original | D | 3/26/2018 | SHELLEY | SHELLEY | See A3.04 - Need continuity shown at stair, verify continuity between beams, every angle will require membrane penetration protection, verify all supporting elements for 1-hour floor are also 1-hour rated - beams and columns. Walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1050298 |
Construction | Original | / | 3/26/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1050255 |
Construction | Original | / | 3/26/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1050251 |
Resubmittal 3 | Original | / | 3/16/2018 | NELIDA | NELIDA | Resubmittal #3 3/16/18 | | Resubmittal 3 | 1047855 |
Out to Review | Original | / | 3/13/2018 | JANE | JANE | Ralph | | Out to Review | 1046293 |
Finished Bin | Original | / | 3/7/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1044068 |
Plan Coordinator | Original | / | 3/7/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1044063 |
Construction | Original | D | 3/7/2018 | MICHAELA | MICHAELA | Comments not addressed No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1044062 |
Out to Review | Original | / | 3/7/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Out to Review | 1044056 |
Resubmittal 2 | Original | / | 3/6/2018 | MATTHEWM | MATTHEWM | Resubmittal #2 | | Resubmittal 2 | 1043907 |
Plumbing | Original | A | 3/6/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1043905 |
Out to Review | Original | / | 3/6/2018 | MATTHEWM | MATTHEWM | Douglas Hatfield 719 200 9488 | | Out to Review | 1043893 |
Finished Bin | Original | / | 3/5/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1043047 |
Plan Coordinator | Original | / | 3/5/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1043041 |
Plumbing | Original | D | 3/5/2018 | TCRIPPEN | TCRIPPEN | no pipe material types provided what can they use ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1043039 |
Plumbing | Original | / | 3/5/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1043020 |
Plumbing | Original | / | 3/2/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1042915 |
Plan Coordinator | Original | / | 3/2/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1042869 |
Construction | Original | D | 3/2/2018 | MICHAELA | MICHAELA | Address fire protection issues at elevator shaft No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1042868 |
Construction | Original | / | 3/2/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1042832 |
Construction | Original | / | 3/2/2018 | | RITA | Location = Construction by RITA | | Construction | 1042638 |
Resubmittal 1 | Original | / | 3/2/2018 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1042637 |
Out to Review | Original | / | 2/27/2018 | NELIDA | NELIDA | Ryan 719-491-0855 | | Out to Review | 1041288 |
Water Division | Original | N | 2/26/2018 | CSUREVIEW | CSUREVIEW | No new services being proposed AJ 2/26/18 | ajuvera | Water Division | 1040918 |
Waste Water Div | Original | N | 2/26/2018 | CSUREVIEW | CSUREVIEW | No new services being proposed AJ 2/26/18 | ajuvera | Waste Water Div | 1040917 |
CSU Utilities | Original | / | 2/26/2018 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 1040646 |
Hazmat | Original | N | 2/26/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1040645 |
CO Springs Fire | Original | A | 2/26/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1040643 |
Fire | Original | / | 2/20/2018 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1039279 |
CO Springs DRE | Original | N | 2/20/2018 | RDCUSER | RDCUSER | INTERIOR REMODEL ONLY, NO CHANGE OF USE (see full review) | | CO Springs DRE | 1039278 |
Zoning/Planning | Original | / | 2/16/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1038798 |
Plan Coordinator | Original | / | 2/16/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1038742 |
Mechanical | Original | A | 2/16/2018 | JUSTINC | JUSTINC | | | Mechanical | 1038741 |
Mechanical | Original | / | 2/16/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1038582 |
Mechanical | Original | / | 2/15/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1037915 |
Plan Coordinator | Original | / | 2/14/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1037882 |
Electrical | Original | A | 2/14/2018 | SHELBY | SHELBY | | | Electrical | 1037881 |
Electrical | Original | / | 2/14/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1037737 |
Plumbing | Original | D | 2/12/2018 | TCRIPPEN | TCRIPPEN | see constructions notes the shower does not meet the Accessibly. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1036806 |
Electrical | Original | / | 2/12/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1036620 |
Plan Coordinator | Original | / | 2/12/2018 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1036605 |
Elevators | Original | A | 2/12/2018 | ERIC | ERIC | Hydraulic VPL by Morningstar | | Elevators | 1036603 |
Elevators | Original | / | 2/9/2018 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1036300 |
Plan Coordinator | Original | / | 2/9/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1036243 |
Construction | Original | D | 2/9/2018 | MICHAELA | MICHAELA | Provide structural plans for all new beams, bearing walls etc. New shower must be ANSI compliant Elevator must be in a 1-hr. shaft with 1-hr. supporting construction Provide sections through new framing at vestibule ceiling Accessible service counter is required at reception if transactions take place. No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1036242 |
Construction | Original | / | 2/7/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1035668 |
Construction | Original | / | 2/1/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1034103 |
Plan Coordinator | Original | / | 2/1/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1034096 |
Enumeration | Original | N | 2/1/2018 | AMY | AMY | | | Enumeration | 1034095 |
Enumeration | Original | / | 2/1/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1034094 |
Floodplain | Original | N | 1/31/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6407207014) | | Floodplain | 1033606 |