Construction | 4/27/15 | A | 4/27/2018 | SHELLEY | SHELLEY | bike platforms | | Construction | 1062334 |
Electrical | 4/27/15 | A | 4/27/2018 | BERTHA | BERTHA | Revised 400A Panel LA to two section 225A Panel La. | | Electrical | 1062309 |
Out to Review | 4/27/15 | / | 4/27/2018 | NELIDA | NELIDA | Brian 719-650-1598 | | Out to Review | 1062291 |
Construction | Splice Construction 4/18/18 | A | 4/18/2018 | SHELLEY | SHELLEY | Revised plan to remove rated demising walls. | | Construction | 1058604 |
Out to Review | Splice Construction 4/18/18 | / | 4/18/2018 | MATTHEWM | MATTHEWM | Walk | | Out to Review | 1058588 |
Mechanical | Original | A | 3/16/2018 | DALEH | DALEH | | | Mechanical | 1048100 |
Construction | Original | A | 3/16/2018 | MICHAELA | MICHAELA | | | Construction | 1047997 |
Resubmittal 3 | Original | / | 3/16/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1047962 |
Mechanical | Original | D | 3/13/2018 | DALEH | DALEH | the new uploaded mechanical drawings are the old set of drawings ....see engineers dated stamp for old drawings to new (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1045947 |
Construction | Original | D | 3/12/2018 | MICHAELA | MICHAELA | If you look at the original review you will see at the very bottom of page G001 a note indicating that this structure was not proposed to be an A occupancy when the shell was permitted. Because the building does not prescriptively meet allowable area requirements (V-B, A3 / 6000 sq. ft.) and allowable area was not reviewed for an A occupancy at shell, you must now provide the calculations for allowable area and include them on page G001.Please do not include comments in the architectural submittal when the plan is resubmitted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1045723 |
Resubmittal 2 | Original | / | 3/12/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1045632 |
Plumbing | Original | A | 3/7/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1044359 |
Mechanical | Original | D | 3/5/2018 | DALEH | DALEH | +only upload new mechanical drawings remove old ones from this pdf all else ok (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1043232 |
Construction | Original | D | 3/5/2018 | MICHAELA | MICHAELA | Provide allowable area calculations as requested in the first review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1043007 |
Resubmittal 1 | Original | / | 3/5/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1042973 |
CO Springs Fire | Original | A | 2/20/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1038901 |
Hazmat | Original | N | 2/20/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1038900 |
Electrical | Original | A | 2/16/2018 | SHELBY | SHELBY | | | Electrical | 1038428 |
CO Springs DRE | Original | A | 2/15/2018 | MBINGMAN | MBINGMAN | Use consistent with DP - Parking okay per DP (Commercial center).
No signage approved with this review. (see full review) | | CO Springs DRE | 1038306 |
Plumbing | Original | D | 2/15/2018 | TCRIPPEN | TCRIPPEN | high - low drinking fountain required need an approved occupant type see constructions notes.
. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1038218 |
CSU Contract Admin. | Original | N | 2/15/2018 | CSUAPPSPRM | CSUAPPSPRM | No Development Charges/Fees due for permit. ZJS | zshearer | CSU Contract Admin. | 1038113 |
Health Dept. | Original | N | 2/15/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable | rnielsen | Health Dept. | 1038098 |
Water Division | Original | A | 2/15/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Water Division | 1037958 |
Waste Water Div | Original | A | 2/15/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Waste Water Div | 1037956 |
Gas/Elec. Utils | Original | A | 2/15/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Gas/Elec. Utils | 1037955 |
City Engr | Original | N | 2/14/2018 | JDAGNILLO | JDAGNILLO | | | City Engr | 1037848 |
Mechanical | Original | D | 2/14/2018 | DALEH | DALEH | see plans for complete red lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1037611 |
Electronic Plan | Original | / | 2/14/2018 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1037578 |
Zoning/Planning | Original | / | 2/14/2018 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 1037541 |
Construction | Original | D | 2/14/2018 | MICHAELA | MICHAELA | This is an A-3 occupancy - This occupancy classification was not proposed at the shell building Provide allowable area calculations Revise Code Information Correct elevation at womens toilet room (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1037519 |
Electronic Plan | Original | / | 2/13/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1037036 |
Enumeration | Original | A | 2/6/2018 | BRENT | BRENT | | | Enumeration | 1035126 |
Floodplain | Original | N | 2/5/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6207107015) | | Floodplain | 1034582 |