Out to Review | Original | / | 4/23/2018 | GITA | GITA | dave | | Out to Review | 1060436 |
Scanned/Finished Bin | Original | / | 4/5/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING - Updated Plan Label (1) & Updated Electrical Pages (2) Scanned into permit in place of old ones. -J3- | | Scanned/Finished Bin | 1054542 |
Electrical | Original | A | 4/4/2018 | BERTHA | BERTHA | Re-approved for revisions prior to permit and after scanning. Removed 225A disconnect for Panel L7. Panel L7 replaced with MCB. | | Electrical | 1053958 |
Out to Review | Original | / | 4/4/2018 | GITA | GITA | 2873192 Dave | | Out to Review | 1053936 |
Scanned/Finished Bin | Original | / | 3/27/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1050991 |
To Be Scanned Bin | Original | / | 3/27/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1050963 |
Electrical | Original | A | 3/27/2018 | SHELBY | SHELBY | | | Electrical | 1050909 |
Electrical | Original | D | 3/23/2018 | BERTHA | BERTHA | Set back to Disapproved - plan comments have not been addressed. Address all previous plan comments.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1049967 |
Electrical | Original | D | 3/21/2018 | SHELBY | SHELBY | 1. Show feeder 4 over current protection one one line. 2. Show feeder 5 over current protection on one line. 3. New transformer SSBJ sized incorrectly. 4. Show equipment ground for new transformer feeder. 5. Panel schedules do not match one line ( L8 breaker is not shown in L6 panel schedule etc). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1049328 |
Electrical | Original | D | 2/14/2018 | SHELBY | SHELBY | 1. One line is incorrect ( See record drawings). 2. Provide load calculation for buss way feeding space. 3. Comply with previous review comment 2. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1037642 |
Hazmat | Original | N | 2/12/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1036862 |
CO Springs Fire | Original | A | 2/12/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1036861 |
Water Division | Original | N | 2/12/2018 | CSUREVIEW | CSUREVIEW | No new services being proposed AJ 2/12/18 | ajuvera | Water Division | 1036809 |
Waste Water Div | Original | N | 2/12/2018 | CSUREVIEW | CSUREVIEW | No new services being proposed AJ 2/12/18 | ajuvera | Waste Water Div | 1036808 |
Out to Review | Original | / | 2/8/2018 | RDCUSER | RDCUSER | | | Out to Review | 1036044 |
CO Springs DRE | Original | N | 2/8/2018 | RDCUSER | RDCUSER | INTERIOR REMODEL ONLY, NO CHANGE OF USE (see full review) | | CO Springs DRE | 1036043 |
Plumbing | Original | N | 2/8/2018 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit. | | Plumbing | 1036040 |
Enumeration | Original | A | 2/8/2018 | AMY | AMY | | | Enumeration | 1036030 |
Construction | Original | A | 2/8/2018 | DANM | DANM | | | Construction | 1036024 |
Mechanical | Original | A | 2/8/2018 | JUSTINC | JUSTINC | | | Mechanical | 1036009 |
Out to Review | Original | / | 2/8/2018 | BERTHA | BERTHA | Dave walking 719-287-3192 | | Out to Review | 1036004 |
Electrical | Original | D | 2/8/2018 | BERTHA | BERTHA | 1. Provide conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work. 2. Service load summary. 3. Provide available fault current for all new panels. 4. Provide 2009 IECC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1036002 |
Floodplain | Original | N | 2/8/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418301020) | | Floodplain | 1035988 |