Out to Review | Original | / | 4/14/2015 | BPHILLIPS | BPHILLIPS | teri 491-5711 | | Out to Review | 776368 |
Health Dept. | Original | / | 4/6/2015 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 774118 |
Water Division | Original | D | 4/6/2015 | CSUREVIEW | CSUREVIEW | Same comments. to rbd | awerner | Water Division | 774101 |
Waste Water Div | Original | D | 4/6/2015 | CSUREVIEW | CSUREVIEW | Same comments. | awerner | Waste Water Div | 774100 |
Gas/Elec. Utils | Original | A | 4/6/2015 | CSUREVIEW | CSUREVIEW | Same comments. | awerner | Gas/Elec. Utils | 774099 |
City Engr (SERT) | Original | D | 4/3/2015 | CSENGINEER | CSENGINEER | A copy of the Grading and Erosion Control Plan approved by City Engineering is requires in the building permit set. Plan Set routed to CSU Utilities. pvm | csengineer | City Engr (SERT) | 773679 |
CSU Utilities | Original | / | 4/3/2015 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 773594 |
CO Springs Fire | Original | D | 4/3/2015 | CSFIRE | CSFIRE | plans withdrawn without review - previous review comments not addressed - still need approved water plans and enumerations approval. (see full review) | csfdit | CO Springs Fire | 773593 |
CO Springs DRE | Original | D | 3/27/2015 | DTORTORICE | DTORTORICE | New Event Center (Bldg B) - Denied DMT for MLH. 1) the subdivision plat is not yet recorded, 2) Although development plan CPC DP 13-00099 is attached, it does not appear the final landscape and irrigation plans have bee approved or submitted for review, the FLP must be submitted and review paid for prior to permitting. Contact Connie Perry regarding the latter matter, if not yet addressed: her contact info is 719-385-5375. 30 Has the $5000 escrow due prior to building permit for future traffic calming (per the notes on the approved DP) and the $100,000 escrow for a signal at Descartes and Austin Bluffs been addressed? (see full review) | | CO Springs DRE | 771743 |
Fire | Original | / | 3/27/2015 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 771740 |
Fire | Original | / | 3/27/2015 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 771738 |
Fire | Original | / | 3/27/2015 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 771737 |
CO Springs DRE | Original | D | 3/27/2015 | DTORTORICE | DTORTORICE | New Event Center (Bldg B) - Denied DMT for MLH. 1) the subdivision plat is not yet recorded, 2) Although development plan CPC DP 13-00099 is attached, it does not appear the final landscape and irrigation plans have bee approved or submitted for review, the FLP must be submitted and review paid for prior to permitting. Contact Connie Perry regarding the latter matter, if not yet addressed: her contact info is 719-385-5375. (see full review) | | CO Springs DRE | 771736 |
Zoning/Planning | Original | / | 3/25/2015 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 771019 |
Plumbing | Original | D | 3/25/2015 | TCRIPPEN | TCRIPPEN | men`s requires 5 fixtures///// The cover sheet is wrong only 4 provide and only 3 required TCC 3-31-15 | | Plumbing | 770990 |
Plumbing | Original | / | 3/25/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 770958 |
Plumbing | Original | / | 3/25/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 770903 |
Plan Coordinator | Original | / | 3/25/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 770896 |
Electrical | Original | D | 3/25/2015 | DOUG | DOUG | Review comments from 10/06/2014 not addressed. | | Electrical | 770895 |
Electrical | Original | / | 3/25/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 770860 |
Electrical | Original | / | 3/24/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 770615 |
Plan Coordinator | Original | / | 3/24/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 770581 |
Mechanical | Original | A | 3/24/2015 | RUSSELL | RUSSELL | Released for permit as noted on plans | | Mechanical | 770580 |
Mechanical | Original | / | 3/24/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 770474 |
Mechanical | Original | / | 3/19/2015 | | RITA | Location = Mechanical by RITA | | Mechanical | 769623 |
Plan Coordinator | Original | / | 3/19/2015 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 769615 |
Construction | Original | A | 3/19/2015 | DANM | DANM | | | Construction | 769614 |
Construction | Original | / | 3/18/2015 | DANM | DANM | In Current Review by DANM | | Construction | 769513 |
Construction | Original | / | 3/18/2015 | | RITA | Location = Construction by RITA | | Construction | 769487 |
Plan Coordinator | Original | / | 3/18/2015 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 769478 |
Enumeration | Original | D | 3/18/2015 | JEANNINE | JEANNINE | Code study form incomplete--provide current parcel schedule (tax schedule number) & the new legal description after the property has a recorded plat. The address appears to be correct for the structure noted. Provide a copy of the final recorded plat for plan approval. | | Enumeration | 769477 |
Enumeration | Original | / | 3/18/2015 | | REBECCA | Location = Enumeration by REBECCA | | Enumeration | 769402 |
Resubmittal 2 | Original | / | 3/18/2015 | REBECCA | REBECCA | Resubmittal #2 | | Resubmittal 2 | 769401 |
Out to Review | Original | / | 11/14/2014 | NELIDA | NELIDA | Teri 491-5711 | | Out to Review | 745860 |
Finished Bin | Original | / | 10/17/2014 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 740388 |
CSU Contract Admin. | Original | D | 10/17/2014 | CSUAPPSPRM | CSUAPPSPRM | Same comments as 5/5/14 review. Please ensure address approved by Enumerations prior to submittal of Commercial Water Meter Sizing Form. Plan returned to RBD permit counter. BTE | Benglish | CSU Contract Admin. | 740373 |
City Engr (SERT) | Original | D | 10/17/2014 | CSENGINEER | CSENGINEER | Same comment from 5/15/2014: A copy of the Grading and Erosion Control Plan approved by City Engineering is requires in the building permit set. Plan routed to CSU Contract Admin. pvm | csengineer | City Engr (SERT) | 740296 |
Water Division | Original | D | 10/17/2014 | CSUREVIEW | CSUREVIEW | Comments not addressed, yet. (mt_10/17/2014) | mtroche | Water Division | 740247 |
Waste Water Div | Original | D | 10/17/2014 | CSUREVIEW | CSUREVIEW | Comments not addressed, yet. (mt_10/17/2014) | mtroche | Waste Water Div | 740246 |
CSU Utilities | Original | / | 10/15/2014 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 739819 |
CO Springs Fire | Original | D | 10/15/2014 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 739815 |
Fire | Original | / | 10/8/2014 | | MHERINGTON | Location = Fire by MHERINGTON | | Fire | 738202 |
CO Springs DRE | Original | D | 10/8/2014 | MHERINGTON | MHERINGTON | Final plat has not yet been recorded. Plat needs to be recorded prior to zoning sign-off. Final Landscape Plan and Final Irrigation Plan are due. Also, there is a $5000 escrow due prior to building permit for future traffic calming (per the notes on the approved DP) and a $100,000 escrow for a signal at Descartes and Austin Bluffs. (see full review) | | CO Springs DRE | 738201 |
Zoning/Planning | Original | / | 10/6/2014 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 737651 |
Plan Coordinator | Original | / | 10/6/2014 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 737646 |
Plumbing | Original | D | 10/6/2014 | TCRIPPEN | TCRIPPEN | our rain is 3 inches per hour not 2" | | Plumbing | 737645 |
Plumbing | Original | / | 10/6/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 737517 |
Plumbing | Original | / | 10/6/2014 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 737491 |
Plan Coordinator | Original | / | 10/6/2014 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 737489 |
Electrical | Original | D | 10/6/2014 | DOUG | DOUG | NOTES 2,3,5,7 FROM PRIOR REVIEW NOT ADDRESSED | | Electrical | 737488 |
Electrical | Original | / | 10/3/2014 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 737394 |
Electrical | Original | / | 10/3/2014 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 737364 |
Plan Coordinator | Original | / | 10/3/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 737346 |
Mechanical | Original | D | 10/3/2014 | RUSSELL | RUSSELL | Small Conference room is still short of O.A., however, does RTU-10 have a CO2 sensor or not, conflicting on the drawings, sheet M2.0 doesn't indicate that RTU-10 has CO2 based on Control Diagram, however, RTU Schedule on sheet M3.o indicates in it's notes that RTU-10 has 100% O.A.,with enthalpy controls, how does that provide required O.A.?, sheet M2.0 gas isometric, need to field label all medium pressure gas piping every 6 feet per RBC amendments, bird screen on exhaust fan detail. | | Mechanical | 737345 |
Mechanical | Original | / | 10/3/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 737121 |
Mechanical | Original | / | 10/2/2014 | | RITA | Location = Mechanical by RITA | | Mechanical | 736943 |
Plan Coordinator | Original | / | 10/2/2014 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 736932 |
Construction | Original | D | 10/2/2014 | DANM | DANM | Verify that the attached soils report was used for the foundation design since the incorrect one was listed on the Sheet S0.1 See plans Walk OK | | Construction | 736930 |
Construction | Original | / | 10/1/2014 | DANM | DANM | In Current Review by DANM | | Construction | 736667 |
Construction | Original | / | 10/1/2014 | | MINDY | Location = Construction by MINDY | | Construction | 736584 |
Resubmittal 1 | Original | / | 10/1/2014 | MINDY | MINDY | Resubmittal #1 Route to RBD depts only | | Resubmittal 1 | 736583 |
Out to Review | Original | / | 5/20/2014 | REBECCA | REBECCA | teri 491-5711 | | Out to Review | 708564 |
Finished Bin | Original | / | 5/19/2014 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 707995 |
Health Dept. | Original | D | 5/19/2014 | HEALTHDEPT | HEALTHDEPT | A plan review is required for a retail food establishment by El Paso County Public Health for licensing. rw 575-8968 | rwarwick | Health Dept. | 707985 |
Health Dept. | Original | / | 5/15/2014 | | RITA | Location = Health Dept. by RITA | | Health Dept. | 707623 |
City Engr (SERT) | Original | D | 5/15/2014 | CSENGINEER | CSENGINEER | A Grading and Erosion Control Plan approved by City Engineering is requires in the building permit set. Plan Set routed to RBD. pvm | csengineer | City Engr (SERT) | 707574 |
Water Division | Original | D | 5/14/2014 | CSUREVIEW | CSUREVIEW | Need approved wastewater drawings in RBD set of plans. Taken plans to the SERT bin AJ 5/14/14 | ajuvera | Water Division | 707152 |
Waste Water Div | Original | D | 5/14/2014 | CSUREVIEW | CSUREVIEW | Need approved wastewater drawings in RBD set of plans. Taken plans to the SERT bin AJ 5/14/14 | ajuvera | Waste Water Div | 707151 |
City Engr (SERT) | Original | / | 5/13/2014 | | CSFIRE | Location = City Engr (SERT) by CSFIRE | csfdit | City Engr (SERT) | 707053 |
Hazmat | Original | N | 5/13/2014 | CSFIRE | CSFIRE | | csfdit | Hazmat | 707052 |
CO Springs Fire | Original | D | 5/13/2014 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 707051 |
Fire | Original | / | 5/9/2014 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 706379 |
CO Springs DRE | Original | D | 5/9/2014 | DTORTORICE | DTORTORICE | New Event Center - Bldg B - Plat not yet recorded. Per DP approval letter, landscape and irrigation plans must be approved prior to building permit issuance. CPC PUD 13-00099 is attached. (see full review) | | CO Springs DRE | 706376 |
Water Division | Original | D | 5/5/2014 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. at sert | awerner | Water Division | 705351 |
Waste Water Div | Original | D | 5/5/2014 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. | awerner | Waste Water Div | 705350 |
Gas/Elec. Utils | Original | A | 5/5/2014 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service/transformer/etc locations. | awerner | Gas/Elec. Utils | 705349 |
CSU Contract Admin. | Original | D | 5/5/2014 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/extrx/util_dev_svcs/svc_standards/water/chapter/wp_8.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. | lmpope | CSU Contract Admin. | 705313 |
CSU Contract Admin. | Original | / | 5/5/2014 | | KENYATTA | Location = CSU Contract Admin. by KENYATTA | | CSU Contract Admin. | 705262 |
Zoning/Planning | Original | / | 5/5/2014 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 705197 |
Plan Coordinator | Original | / | 5/5/2014 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 705188 |
Electrical | Original | D | 5/5/2014 | DOUG | DOUG | 1. Not used 2. Incorrect SCA value for Utility Transformer. Revise calcualtions. Z=1.4% per CSU handbook. 3. Panle M cannot be series rated. 240.86(C) 4. GFCI symbols and labels unclear. Does WP=GFCI? Clarify. 5. Clarify intent of lighting control system. Must meet minimum of IECC 2009. 6. SCA vs. AIC ratings of one-line and panel schedules incorrect. 7. 210.8 requires all kitchen receptacles 125V 15 and 20A be GFCI and readily accessible. 8. Scale labels of plans incorrect. | | Electrical | 705187 |
Electrical | Original | / | 5/2/2014 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 704846 |
Electrical | Original | / | 4/30/2014 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 704156 |
Plumbing | Original | D | 4/30/2014 | TCRIPPEN | TCRIPPEN | Provide water pipe size calculations on plans floor drain required for water meter and back flow device.All hand washing sinks to be 110 degrees max mixing valve required. | | Plumbing | 704155 |
Plumbing | Original | / | 4/30/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 704138 |
Plumbing | Original | / | 4/30/2014 | | RITA | Location = Plumbing by RITA | | Plumbing | 704137 |
Electrical | Original | / | 4/28/2014 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 703656 |
Plan Coordinator | Original | / | 4/28/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 703637 |
Mechanical | Original | D | 4/28/2014 | RUSSELL | RUSSELL | Sheet M1.0, Serving room range/oven if more than a waring range, must provide a Type I hood with makeup air interlocked, if warming range, must still be vented to the exterior with a type ii residential type hood, small conference room appears to be way short of O.A., ass note in general notes: provide a test and balance report to the mechanical inspector at time of heating final inspection, not sure where there's a walk-in cooler and freezer?, it appears there are only reach-in type?, provide type and quantity of refrigeration for AC-1 and HP if required to verify compliance with '09 IMC Table 1103.1, sheet M2.0, see plan track #75127 for CO2 sensor remarks, sheet M5.0, bord screen on exhaust fan detail, sheet P-1.0 and all other "P" sheets with gas piping, details schematics, etc, to be put on a "M" sheet, see comments on plan track # 75127, NO WALK, return all red line comment sheets with next review/submittal | | Mechanical | 703636 |
Mechanical | Original | / | 4/28/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 703584 |
Mechanical | Original | / | 4/24/2014 | | RITA | Location = Mechanical by RITA | | Mechanical | 702912 |
Plan Coordinator | Original | / | 4/24/2014 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 702888 |
Construction | Original | D | 4/24/2014 | DANM | DANM | Revise referenced codes Revise bldg area to include covered outdoor areas that have a specific purpose other than providing weather protection for entering/exiting Revise occupant load for lobby and to include all outdoor courtyard areas used for dining, etc. COMcheck does not seem to match dwgs and IECC Code Study Form - revise occupant load and bldg area Revise Occupancy and Exiting Plan Door 106 must swing out (more than 50 occupants) Small conference room must have two exits (more than 50 occupants) - show second exit sign on RCP Correct mislabeled door hardware Group 10 Clarify locations of fire penetration details - if not applicable to this project remove from set Revise structural load calculation criteria and reference submitted soils report TRUSSES PENDING See plans No Walk | | Construction | 702887 |
Construction | Original | / | 4/24/2014 | DANM | DANM | In Current Review by DANM | | Construction | 702725 |
Construction | Original | / | 4/23/2014 | | RITA | Location = Construction by RITA | | Construction | 702606 |
Plan Coordinator | Original | / | 4/23/2014 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 702569 |
Enumeration | Original | D | 4/23/2014 | AMY | AMY | Address is 7581 Austin Bluffs Pkwy, Current Tax schedule number & Legal Description should be added to the Code Study form even if it is to change after recording the plat. Final recorded plat, along with a copy of the recorded plat & addressing fees are still pending. | | Enumeration | 702568 |
Floodplain | Original | N | 4/23/2014 | AMY | AMY | Flood Plain on the lot but not in area of proposed work. | | Floodplain | 702565 |