Out to Review | Original | / | 4/14/2015 | BPHILLIPS | BPHILLIPS | teri 491-5711 | | Out to Review | 776367 |
Finished Bin | Original | / | 4/6/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 774119 |
Water Division | Original | D | 4/6/2015 | CSUREVIEW | CSUREVIEW | Same comments. to rbd. | awerner | Water Division | 774089 |
Waste Water Div | Original | D | 4/6/2015 | CSUREVIEW | CSUREVIEW | Same comments. | awerner | Waste Water Div | 774087 |
Gas/Elec. Utils | Original | A | 4/6/2015 | CSUREVIEW | CSUREVIEW | Same comment. | awerner | Gas/Elec. Utils | 774084 |
City Engr (SERT) | Original | D | 4/3/2015 | CSENGINEER | CSENGINEER | A copy of the Grading and Erosion Control Plan approved by City Engineering is requires in the building permit set. Plan Set routed to CSU Utilities. pvm | csengineer | City Engr (SERT) | 773681 |
CSU Utilities | Original | / | 4/3/2015 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 773585 |
CO Springs Fire | Original | D | 4/3/2015 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 773584 |
Fire | Original | / | 3/27/2015 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 771763 |
CO Springs DRE | Original | D | 3/27/2015 | DTORTORICE | DTORTORICE | New Event Center (Bldg A) - Denied DMT for MLH. 1) the subdivision plat is not yet recorded, 2) Although development plan CPC DP 13-00099 is attached, it does not appear the final landscape and irrigation plans have bee approved or submitted for review, the FLP must be submitted and review paid for prior to permitting. Contact Connie Perry regarding the latter matter, if not yet addressed: her contact info is 719-385-5375. 3) Has the $5000 escrow due prior to building permit for future traffic calming (per the notes on the approved DP) and the $100,000 escrow for a signal at Descartes and Austin Bluffs been addressed? (see full review) | | CO Springs DRE | 771762 |
Zoning/Planning | Original | / | 3/25/2015 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 770905 |
Plan Coordinator | Original | / | 3/25/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 770890 |
Electrical | Original | D | 3/25/2015 | DOUG | DOUG | See 10/06/2014 review. No changes from that issue. | | Electrical | 770889 |
Electrical | Original | / | 3/25/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 770861 |
Electrical | Original | / | 3/24/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 770657 |
Plan Coordinator | Original | / | 3/24/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 770651 |
Plumbing | Original | D | 3/24/2015 | TCRIPPEN | TCRIPPEN | see appendix 13 of the 2009 IPC for water pipe size analysis data. | | Plumbing | 770650 |
Plumbing | Original | / | 3/24/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 770646 |
Plumbing | Original | / | 3/24/2015 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 770616 |
Plan Coordinator | Original | / | 3/24/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 770610 |
Mechanical | Original | A | 3/24/2015 | RUSSELL | RUSSELL | Released for permit as noted on the plans | | Mechanical | 770609 |
Mechanical | Original | / | 3/24/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 770570 |
Mechanical | Original | / | 3/19/2015 | | RITA | Location = Mechanical by RITA | | Mechanical | 769625 |
Plan Coordinator | Original | / | 3/19/2015 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 769556 |
Construction | Original | A | 3/19/2015 | DANM | DANM | | | Construction | 769555 |
Construction | Original | / | 3/18/2015 | DANM | DANM | In Current Review by DANM | | Construction | 769514 |
Construction | Original | / | 3/18/2015 | | RITA | Location = Construction by RITA | | Construction | 769476 |
Plan Coordinator | Original | / | 3/18/2015 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 769462 |
Enumeration | Original | D | 3/18/2015 | JEANNINE | JEANNINE | Code study form incomplete--provide current parcel schedule (tax schedule number) & the new legal description after the property has a recorded plat. The address appears to be correct for the structure noted. Provide a copy of the final recorded plat for plan approval. | | Enumeration | 769461 |
Enumeration | Original | / | 3/18/2015 | | REBECCA | Location = Enumeration by REBECCA | | Enumeration | 769400 |
Resubmittal 2 | Original | / | 3/18/2015 | REBECCA | REBECCA | Resubmittal #2 starting over with new stamps and expired approvals | | Resubmittal 2 | 769396 |
Out to Review | Original | / | 10/15/2014 | JANE | JANE | Teri | | Out to Review | 739864 |
Finished Bin | Original | / | 10/6/2014 | | REBECCA | Location = Finished Bin by REBECCA | | Finished Bin | 737573 |
Zoning/Planning | Original | / | 10/6/2014 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 737511 |
Plan Coordinator | Original | / | 10/6/2014 | | KENYATTA | Location = Plan Coordinator by KENYATTA | | Plan Coordinator | 737495 |
Electrical | Original | D | 10/6/2014 | KENYATTA | KENYATTA | NOTES 2,3,5,7 FROM PRIOR REVIEW NOT ADDRESSED | | Electrical | 737494 |
Electrical | Original | / | 10/6/2014 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 737490 |
Electrical | Original | / | 10/3/2014 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 737402 |
Plan Coordinator | Original | / | 10/3/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 737401 |
Mechanical | Original | D | 10/3/2014 | RUSSELL | RUSSELL | SHeet M1.0, Provide a test and balance report to the mechanical inspector at time of the heating final inspection, how providing makeup air in the Service area, for KH1?, no communicating openings into the Main hall area?,,sheet M2.0, CO2 for RTU's 6.5 & 8.5, similar key notes for all RTU's including RTu-12.5a & 12.5b?,see key notes on sheet M5.0,sheet M3.0 see '09 IFGC section 409.4, the shut-off valve needs to preceed the gas pressure regulator?, also indicate gas piping dow where shown & needs to match up on sheet M4.0?sheet M6.0 & MP1.0 are duplicates?, bird screen on exhaust fan detail, | | Mechanical | 737399 |
Mechanical | Original | / | 10/3/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 737348 |
Mechanical | Original | / | 10/3/2014 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 737146 |
Plan Coordinator | Original | / | 10/3/2014 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 737139 |
Plumbing | Original | D | 10/3/2014 | TCRIPPEN | TCRIPPEN | are rain fall here is figured at 3 inched per hour. still need a water pipe size analysis data on plans | | Plumbing | 737138 |
Plumbing | Original | / | 10/3/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 737120 |
Plumbing | Original | / | 10/3/2014 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 737119 |
Mechanical | Original | / | 10/2/2014 | | RITA | Location = Mechanical by RITA | | Mechanical | 736942 |
Plan Coordinator | Original | / | 10/2/2014 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 736726 |
Construction | Original | D | 10/2/2014 | DANM | DANM | Verify that the attached soils report was used for the foundation design since the incorrect one was listed on the Sheet S0.1 See plans Walk OK | | Construction | 736725 |
Construction | Original | / | 10/1/2014 | DANM | DANM | In Current Review by DANM | | Construction | 736606 |
Construction | Original | / | 10/1/2014 | | MINDY | Location = Construction by MINDY | | Construction | 736582 |
Resubmittal 1 | Original | / | 10/1/2014 | MINDY | MINDY | Resubmittal #1 RBD depts only (C, E, M, P) | | Resubmittal 1 | 736581 |
Out to Review | Original | / | 5/20/2014 | REBECCA | REBECCA | teri 491-5711 | | Out to Review | 708562 |
Finished Bin | Original | / | 5/15/2014 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 707617 |
City Engr (SERT) | Original | D | 5/15/2014 | CSENGINEER | CSENGINEER | A Grading and Erosion Control Plan approved by City Engineering is requires in the building permit set. Plan Set routed to RBD. pvm | csengineer | City Engr (SERT) | 707572 |
Water Division | Original | D | 5/14/2014 | CSUREVIEW | CSUREVIEW | Need approved water drawings in RBD set taken plan to the SERT bin AJ 5/14/14 | ajuvera | Water Division | 707162 |
Waste Water Div | Original | D | 5/14/2014 | CSUREVIEW | CSUREVIEW | Need approved wastewater drawings in RBD set taken plan to the SERT bin AJ 5/14/14 | ajuvera | Waste Water Div | 707161 |
City Engr (SERT) | Original | / | 5/13/2014 | | CSFIRE | Location = City Engr (SERT) by CSFIRE | csfdit | City Engr (SERT) | 707043 |
Hazmat | Original | N | 5/13/2014 | CSFIRE | CSFIRE | | csfdit | Hazmat | 707042 |
CO Springs Fire | Original | D | 5/13/2014 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 707041 |
Fire | Original | / | 5/9/2014 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 706380 |
CO Springs DRE | Original | D | 5/9/2014 | DTORTORICE | DTORTORICE | New Event Center - Bldg A - Plat not yet recorded. Per DP approval letter, landscape and irrigation plans must be approved prior to building permit issuance. CPC PUD 13-00099 is attached. (see full review) | | CO Springs DRE | 706375 |
Health Dept. | Original | A | 5/7/2014 | HEALTHDEPT | HEALTHDEPT | Construction activity permit approved for facility. If food is being prepared and sold to the public a plan review must be submitted to the health department prior to construction site. rw 575-8968 | rwarwick | Health Dept. | 706003 |
Water Division | Original | D | 5/5/2014 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. taken to sert | awerner | Water Division | 705344 |
Waste Water Div | Original | D | 5/5/2014 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. | awerner | Waste Water Div | 705343 |
Gas/Elec. Utils | Original | A | 5/5/2014 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service/transformer/etc locations. | awerner | Gas/Elec. Utils | 705342 |
CSU Contract Admin. | Original | D | 5/5/2014 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/extrx/util_dev_svcs/svc_standards/water/chapter/wp_8.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. | lmpope | CSU Contract Admin. | 705315 |
CSU Contract Admin. | Original | / | 5/5/2014 | | KENYATTA | Location = CSU Contract Admin. by KENYATTA | | CSU Contract Admin. | 705263 |
Zoning/Planning | Original | / | 5/5/2014 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 705196 |
Plan Coordinator | Original | / | 5/5/2014 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 705191 |
Electrical | Original | D | 5/5/2014 | DOUG | DOUG | 1. Not used 2. Incorrect SCA value for Utility Transformer. Revise calcualtions. Z=1.4% per CSU handbook. 3. Panle M cannot be series rated. 240.86(C) 4. GFCI symbols and labels unclear. Does WP=GFCI? Clarify. 5. Clarify intent of lighting control system. Must meet minimum of IECC 2009. 6. SCA vs. AIC ratings of one-line and panel schedules incorrect. 7. 210.8 requires all kitchen receptacles 125V 15 and 20A be GFCI and readily accessible. 8. Scale labels of plans incorrect. | | Electrical | 705190 |
Electrical | Original | / | 5/2/2014 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 705020 |
Electrical | Original | / | 4/30/2014 | | RITA | Location = Electrical by RITA | | Electrical | 704136 |
Plan Coordinator | Original | / | 4/30/2014 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 704134 |
Plumbing | Original | D | 4/30/2014 | TCRIPPEN | TCRIPPEN | Floor drain required for water meter and back flow device.Provide water pipe size calculations on plans.Need an approved occupant load for fixture count. see P2.0 for isometric correction. See P3.0 for clarification on S-X not scheduled. see added note for removal of gas pipe and related items.All hand washing sinks to be 110 degrees max. | | Plumbing | 704133 |
Plumbing | Original | / | 4/30/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 704103 |
Plumbing | Original | / | 4/30/2014 | | RITA | Location = Plumbing by RITA | | Plumbing | 704102 |
Electrical | Original | / | 4/28/2014 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 703657 |
Plan Coordinator | Original | / | 4/28/2014 | BLAKE | BLAKE | In Current Review by BLAKE | | Plan Coordinator | 703571 |
Plan Coordinator | Original | / | 4/28/2014 | AMY | AMY | In Current Review by AMY | | Plan Coordinator | 703570 |
Plan Coordinator | Original | / | 4/28/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 703569 |
Mechanical | Original | D | 4/28/2014 | RUSSELL | RUSSELL | Sheet M1.0, Game Room, appears to be similar to '09 IMC Table 403, Games arcade?, so it would appear that the O.A> is short based on occupant load O.A. ventilation at 7.5 cfm /ocupant ant .18 cfm O.A> per square foot, need O.A> Ventilation Table and the RTU schedule to match each other, one shows 2- RTU-6.5, where the other show 1 RTU -6.5 and 1 RTU-10?, need to provide a residential type hood over the range in the Serving Room, glad you've shown the refrigeration for a walk-in cooler and walk-in freezer, but I don't see either on the plan?, however, what about the refrigeration for AC-1 and possible the HP's?, add a general note: Provide a test and balance report to the mechanical inspector at time of the heating final inspection,sheet M2.o, add the RTU's where the CO@'s are indicated, also RTU note 2 referencing CO2's, prior to elevated levels of CO2, is the O.A. damper pre-set to cfms shown in the schedule or a lower rate, then upon elevated levels of CO2 (800ppm), the O.A> damper then opens to "full open" until CO2 levels drop below (500ppm)?, then closes down to the pre-determined setting?, please clarify, remove all gas piping from the "P" pages and put on the mechanical pages, see attachment on sheet P2.0, , sheet M3.0, coordinate which RTU's are the correct ones and number of each between the Packaged A/C Unit Schedule and the Outside Air Balance Schedule,sheet M5.0, add bird screen to the roof exhaust fan detail,sheet P1.0, remove gas, sheet P2.0, remove gas piping and schematic and calc tabulation, sheet P4.0, remove gas detail, same on P5.0, NO WALK, return all red line comment sheets with next review/submittal | | Mechanical | 703568 |
Mechanical | Original | / | 4/25/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 703149 |
Mechanical | Original | / | 4/24/2014 | | RITA | Location = Mechanical by RITA | | Mechanical | 702911 |
Plan Coordinator | Original | / | 4/24/2014 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 702848 |
Construction | Original | D | 4/24/2014 | DANM | DANM | Revise referenced codes Revise bldg area to include covered outdoor areas that have a specific purpose other than providing weather protection for entering/exiting Revise occupant load for lobby and to include all outdoor courtyard areas used for dining, etc. COMcheck does not seem to match dwgs and IECC Code Study Form - revise occupant load and bldg area Revise Occupancy and Exiting Plan Doors 117 and 1119 encroach on egress width Clarify locations of fire penetration details - if not applicable to this project remove from set Revise structural load calculation criteria and reference submitted soils report TRUSSES PENDING See plans No Walk | | Construction | 702847 |
Construction | Original | / | 4/24/2014 | DANM | DANM | In Current Review by DANM | | Construction | 702726 |
Construction | Original | / | 4/23/2014 | | RITA | Location = Construction by RITA | | Construction | 702559 |
Plan Coordinator | Original | / | 4/23/2014 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 702553 |
Enumeration | Original | D | 4/23/2014 | AMY | AMY | Address is 7561 Austin Bluffs Pkwy, Current Tax schedule number & Legal Description should be added to the Code Study form even if it is to change after recording the plat. Final recorded plat, along with a copy of the recorded plat & addressing fees are still pending. | | Enumeration | 702552 |
Floodplain | Original | N | 4/23/2014 | AMY | AMY | Flood Plain on the lot but not in area of proposed work. | | Floodplain | 702550 |