Out to Review | Original | / | 9/29/2015 | JANE | JANE | Jack 475 1727 | | Out to Review | 819549 |
Finished Bin | Original | / | 9/28/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 819146 |
Health Dept. | Original | D | 9/28/2015 | HEALTHDEPT | HEALTHDEPT | Plan review required. AP 578-3199 Option #3 | Aparikh | Health Dept. | 819129 |
Health Dept. | Original | / | 9/22/2015 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 817876 |
City Engr (SERT) | Original | D | 9/22/2015 | CSENGINEER | CSENGINEER | City Engineering requires an approved Development Plan in the building permit set. Plans routed to RBD. pvm | csengineer | City Engr (SERT) | 817871 |
Water Division | Original | D | 9/21/2015 | CSUREVIEW | CSUREVIEW | Provide approved development plan. Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. to sert | awerner | Water Division | 817539 |
Waste Water Div | Original | D | 9/21/2015 | CSUREVIEW | CSUREVIEW | Provide approved development plan. Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. | awerner | Waste Water Div | 817538 |
Gas/Elec. Utils | Original | D | 9/21/2015 | CSUREVIEW | CSUREVIEW | Provide approved development plan. | awerner | Gas/Elec. Utils | 817537 |
Hazmat | Original | D | 9/18/2015 | CSFIRE | CSFIRE | rce
routed to utilities | rembres | Hazmat | 817152 |
CO Springs Fire | Original | D | 9/18/2015 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
routed to utilities (see full review) | csfdit | CO Springs Fire | 817151 |
Fire | Original | / | 9/17/2015 | | HVANNIMWEGEN | Location = Fire by HVANNIMWEGEN | | Fire | 816812 |
CO Springs DRE | Original | D | 9/17/2015 | HVANNIMWEGEN | HVANNIMWEGEN | Pending approval of Development Plan AR DP 15-00420 (see full review) | | CO Springs DRE | 816811 |
Zoning/Planning | Original | / | 9/10/2015 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | lmpope | Zoning/Planning | 815050 |
CSU Contract Admin. | Original | D | 9/10/2015 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form and payment of development charges/fees. | lmpope | CSU Contract Admin. | 815049 |
CSU Contract Admin. | Original | / | 9/9/2015 | | KENYATTA | Location = CSU Contract Admin. by KENYATTA | | CSU Contract Admin. | 814607 |
Plan Coordinator | Original | / | 9/8/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 814451 |
Mechanical | Original | D | 9/8/2015 | RUSSELL | RUSSELL | CO2 tank enclosure?, how is it being ventilated?, coordinate grease duct outlets on hood per sheet M4 & M6, verify wall is of non-combustible materials?, walk-in cooler and freezer, where is the condenser located for these two units?, is it on the lid of the cooler and freezer or is it remote on the roof?, please clarify on the drawing, gas piping to fryers, show minimum discharge height on grease duct exhaust fans, is the grease duct wrapped with required grease duct wrap?, clearances to combustibles?,gas on all the "P" pages to get put on the "M" pages, see attachment on sheet P1,, NO WALK, return all red line comments with re-submittal of plans loose on top of set, | | Mechanical | 814450 |
Mechanical | Original | / | 9/3/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 813855 |
Mechanical | Original | / | 9/3/2015 | | RITA | Location = Mechanical by RITA | | Mechanical | 813631 |
Plan Coordinator | Original | / | 9/3/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 813614 |
Plumbing | Original | D | 9/3/2015 | TCRIPPEN | TCRIPPEN | P-1 Provide sizes here or add note to read see page P 3 for sizes water pipes drains and vents. Gas piping and related items to be on the M-pages see added sheet from are web page on sheet P1. Per the 2012 IPC hot water source to be within 50 ‘or you can use a re circulating pump. See red lines.///// No walk through.///// | | Plumbing | 813613 |
Plumbing | Original | / | 9/2/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 813563 |
Plumbing | Original | / | 9/2/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 813553 |
Plan Coordinator | Original | / | 9/2/2015 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 813540 |
Electrical | Original | A | 9/2/2015 | SHELBY | SHELBY | | | Electrical | 813539 |
Electrical | Original | / | 9/2/2015 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 813376 |
Electrical | Original | / | 9/2/2015 | | RITA | Location = Electrical by RITA | | Electrical | 813249 |
Plan Coordinator | Original | / | 8/31/2015 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 812724 |
Construction | Original | D | 8/31/2015 | MICHAELA | MICHAELA | Missing soils report Missing IECC certificate for envelope compliance Missing specifications for balcony and awning Revise project data to current codes A-2 w/ occupant load greater than 100 requires sprinkler system Trusses pending - see plan for requirements Walk-through OK | | Construction | 812720 |
Construction | Original | / | 8/31/2015 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 811665 |
Construction | Original | / | 8/31/2015 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 811635 |
Plan Coordinator | Original | / | 8/31/2015 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 811617 |
Enumeration | Original | A | 8/31/2015 | AMY | AMY | Address 6417 Source Center Pt is given to trash enclosure. Separate address is required so second permit is needed. | | Enumeration | 811616 |
Floodplain | Original | N | 8/28/2015 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 811458 |