Out to Review | Original | / | 2/8/2016 | JANE | JANE | Teri. Job cancelled | | Out to Review | 846047 |
Canceled Plans | Original | / | 2/4/2016 | | JANE | Location = Canceled Plans by JANE | | Canceled Plans | 845140 |
Health Dept. | Original | / | 1/27/2016 | | RITA | Location = Health Dept. by RITA | | Health Dept. | 843970 |
Hazmat | Original | D | 1/27/2016 | RITA | RITA | PER CLT 01/26/16 | | Hazmat | 843969 |
Falcon Fire | Original | D | 1/27/2016 | RITA | RITA | PER CLT 01/26/16 | | Falcon Fire | 843968 |
Water Division | Original | D | 1/27/2016 | CSUREVIEW | CSUREVIEW | Same comments apply reference comments from 1/20/16 review AJ 1/27/16 Taken plan set to RBD counter down stairs. | ajuvera | Water Division | 843825 |
Waste Water Div | Original | D | 1/27/2016 | CSUREVIEW | CSUREVIEW | Same comments apply reference comments from 1/20/16 review AJ 1/27/16 Taken plan set to RBD counter down stairs. | ajuvera | Waste Water Div | 843824 |
Gas/Elec. Utils | Original | D | 1/27/2016 | CSUREVIEW | CSUREVIEW | Same comments apply reference comments from 1/20/16 review AJ 1/27/16 Taken plan set to RBD counter down stairs. | ajuvera | Gas/Elec. Utils | 843822 |
Fire | Original | / | 1/20/2016 | | RITA | Location = Fire by RITA | | Fire | 842303 |
County Zoning | Original | D | 1/20/2016 | DSDRANGEL | DSDRANGEL | DOES NOT HAVE APPROVED SITE DEVELOPMENT PLAN PER RF | | County Zoning | 842267 |
Zoning/Planning | Original | / | 1/20/2016 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 842146 |
Water Division | Original | D | 1/20/2016 | CSUREVIEW | CSUREVIEW | Need approved construction drawings in RBD set of plans, and approved Development Plan in RBD set AJ 1/20/16. Taken plan set to RBD counter down stairs. | ajuvera | Water Division | 842082 |
Waste Water Div | Original | D | 1/20/2016 | CSUREVIEW | CSUREVIEW | Need approved construction drawings in RBD set of plans, and approved Development Plan in RBD set AJ 1/20/16. Taken plan set to RBD counter down stairs. | ajuvera | Waste Water Div | 842081 |
Gas/Elec. Utils | Original | D | 1/20/2016 | CSUREVIEW | CSUREVIEW | Need to show gas/electric meter locations on building elevations gas meter needs to be 3'-0" away from any door or window opening. AJ 1/20/16. Taken plan set to RBD counter down stairs. | ajuvera | Gas/Elec. Utils | 842080 |
Out to Review | Original | / | 1/5/2016 | REBECCA | REBECCA | Terri 719-491-5711 | | Out to Review | 839494 |
Health Dept. | Original | / | 1/4/2016 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 839310 |
Gas/Elec. Utils | Original | D | 1/4/2016 | CSUREVIEW | CSUREVIEW | Provide approved development plan. to rbd | awerner | Gas/Elec. Utils | 839256 |
City Engr | Original | / | 12/30/2015 | | CSUAPPSPRM | Location = City Engr by CSUAPPSPRM | mkluke | City Engr | 838832 |
CSU Contract Admin. | Original | N | 12/30/2015 | CSUAPPSPRM | CSUAPPSPRM | CSU gas service territory only -- please contact gas field engineer, JC, at 719-668-5618 for applicable gas extension/service stub charges and fees. | mkluke | CSU Contract Admin. | 838829 |
CSU Contract Admin. | Original | / | 12/30/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | CSU Contract Admin. | 838736 |
CSU Contract Admin. | Original | / | 12/30/2015 | | RITA | Location = CSU Contract Admin. by RITA | | CSU Contract Admin. | 838711 |
Plan Coordinator | Original | / | 12/30/2015 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 838592 |
Electrical | Original | D | 12/30/2015 | SHELBY | SHELBY | 1. Missing engineers stamp. 2. Show feeder over current protection on one line. 3. Provide panel schedules for all panels ( House DTA etc). 4. Show AIC of panel H1A. 5. For series rated panels specify AIC of lowest rated breaker( comply 240.86(C) NEC) | | Electrical | 838590 |
Electrical | Original | / | 12/29/2015 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 838416 |
Electrical | Original | / | 12/22/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 837469 |
Plan Coordinator | Original | / | 12/22/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 837432 |
Plumbing | Original | D | 12/22/2015 | TCRIPPEN | TCRIPPEN | See section 802 only clear water waste and food prep. to be indirect waste,floor sinks are sized by p-trap size not provided on plans, provide D.F.U.S. in red circles on P-1. Per your occupant load of 1302 two (ADA) ANSI drinking fountains are required. Missing engineers stamps on all pages.See all red lines return red lines with next review. No walk through. | | Plumbing | 837431 |
Plumbing | Original | / | 12/22/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 837362 |
Plumbing | Original | / | 12/21/2015 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 837133 |
Plan Coordinator | Original | / | 12/21/2015 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 837100 |
Mechanical | Original | D | 12/21/2015 | JUSTINC | JUSTINC | Need P.E stamp on all commercial drawings Enlarge text on CaptiveAire drawings and darken text Verify RTU S/A rates? 5 ton = 2000cfm Verify walls at grease hood location are rated construction materials | | Mechanical | 837099 |
Mechanical | Original | / | 12/18/2015 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 836814 |
Mechanical | Original | / | 12/17/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 836709 |
Plan Coordinator | Original | / | 12/17/2015 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 836622 |
Construction | Original | D | 12/17/2015 | MICHAELA | MICHAELA | Provide dimensioned site plan - locate trash enclosure Provide soils report Provide IECC (ComCheck) for envelope compliance Provide shop drawings for "canopy" or separate permit will be required to install Walk-through OK | | Construction | 836621 |
Construction | Original | / | 12/17/2015 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 836564 |
Construction | Original | / | 12/14/2015 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 835984 |
Plan Coordinator | Original | / | 12/14/2015 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 835975 |
Enumeration | Original | D | 12/14/2015 | JEANNINE | JEANNINE | Address appears to have been assigned; however, the final plat has not been submitted for approval. Enumerations will need a pdf copy of the final recorded plat. Provide copy of the legal description of the parcel after it has been platted. The current schedule number will change after the plat is recorded. | | Enumeration | 835974 |
Floodplain | Original | N | 12/14/2015 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 835918 |