Mechanical | Original | A | 8/9/2016 | JUSTINC | JUSTINC | | | Mechanical | 894186 |
Electrical | Original | A | 7/27/2016 | SHELBY | SHELBY | Jeff Tanner | | Electrical | 890733 |
Out to Review | Original | / | 6/28/2016 | REBECCA | REBECCA | vic 719-634-3751 | | Out to Review | 883344 |
Finished Bin | Original | / | 6/24/2016 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 882332 |
Hazmat | Original | N | 6/23/2016 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 882129 |
CO Springs Fire | Original | D | 6/23/2016 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 882128 |
Fire | Original | / | 6/17/2016 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 880932 |
CO Springs DRE | Original | N | 6/17/2016 | RDCUSER | RDCUSER | interior remodel. (see full review) | | CO Springs DRE | 880931 |
Zoning/Planning | Original | / | 6/16/2016 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 880529 |
Plan Coordinator | Original | / | 6/16/2016 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 880472 |
Plumbing | Original | A | 6/16/2016 | TCRIPPEN | TCRIPPEN | okay, | | Plumbing | 880466 |
Plumbing | Original | / | 6/16/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 880426 |
Plumbing | Original | / | 6/14/2016 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 879716 |
Plan Coordinator | Original | / | 6/14/2016 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 879593 |
Electrical | Original | D | 6/14/2016 | SHELBY | SHELBY | 1. Demand factor for lighting is 1.25. 2. Remove parallel neutral between new disconnect and gutter. 3. Transformer secondary feeding new MDP supply side bonding jumper sized incorrectly. 4. For main # 6 clarify frame size VS trip size. 5. Indicate location of generator on floor plan. | | Electrical | 879591 |
Electrical | Original | / | 6/14/2016 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 879560 |
Electrical | Original | / | 6/8/2016 | | RITA | Location = Electrical by RITA | | Electrical | 878461 |
Plan Coordinator | Original | / | 6/8/2016 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 878349 |
Mechanical | Original | D | 6/8/2016 | JUSTINC | JUSTINC | Ducts shown penetrating rated wall assemblies? Indicate on plan how protecting? Added note: GAS IS AN ENGINEERED SYSTEM
SEE PLAN FOR ANY ADDITIONAL COMMENTS RETURN RED LINE COMMENT SHEETS WITH NEXT REVIEW NO WALK | | Mechanical | 878348 |
Mechanical | Original | / | 6/8/2016 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 878274 |
Mechanical | Original | / | 6/7/2016 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 878057 |
Plan Coordinator | Original | / | 6/7/2016 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 878049 |
Construction | Original | A | 6/7/2016 | MICHAELA | MICHAELA | F-1 occupancy formerly H-4 UBC - historically "Weld Shop" | | Construction | 878048 |
Construction | Original | / | 6/7/2016 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 877888 |
Construction | Original | / | 6/7/2016 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 877875 |
Plan Coordinator | Original | / | 6/7/2016 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 877840 |
Enumeration | Original | A | 6/7/2016 | BRENT | BRENT | | | Enumeration | 877839 |
Enumeration | Original | / | 6/7/2016 | | JANE | Location = Enumeration by JANE | | Enumeration | 877814 |
Out to Review | Original | / | 6/6/2016 | JANE | JANE | arch took. Will be back with plan review fee | | Out to Review | 877621 |
Floodplain | Original | N | 6/6/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 877620 |