CO Springs DRE | Original | A | 3/21/2017 | DSEXTON | DSEXTON | Approved. DJS 3/21/2017. (see full review) | | CO Springs DRE | 945088 |
Electrical | Original | A | 3/20/2017 | SHELBY | SHELBY | | | Electrical | 944795 |
Zoning/Planning | Original | / | 3/17/2017 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 944414 |
Resubmittal 2 | Original | / | 3/16/2017 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 944207 |
Electrical | Original | D | 12/9/2016 | BERTHA | BERTHA | 1. Provide conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work.
2. Provide panel and circuit number on all electrical equipment (new and relocated)
3. Provide light fixture schedule including fixture type and lamp wattage
4. Provide 2009 IECC.
5. All information must be supplied and verified by engineer at time of plan submittal.
See checklist - http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 923062 |
CO Springs DRE | Original | D | 12/6/2016 | DSEXTON | DSEXTON | The building permit packet does not include complete copies of the plans approved by City Planning. Full sized copies of the amended development plans should be included within the building permit plan set. DJS 12/6/2016 (see full review) | | CO Springs DRE | 922361 |
Zoning/Planning | Original | / | 12/6/2016 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 922312 |
Construction | Original | A | 12/6/2016 | SHELLEY | SHELLEY | | | Construction | 922174 |
Enumeration | Original | A | 12/5/2016 | AMY | AMY | | | Enumeration | 922078 |
Resubmittal 1 | Original | / | 12/2/2016 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 921812 |
Plumbing | Original | N | 11/4/2016 | TCRIPPEN | TCRIPPEN | No plumbing work issue no permit | | Plumbing | 915821 |
Electronic Plan | Original | / | 11/4/2016 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 915807 |
CO Springs Fire | Original | N | 11/3/2016 | CSFIRE | CSFIRE | | dwithee | CO Springs Fire | 915615 |
Hazmat | Original | N | 11/3/2016 | CSFIRE | CSFIRE | | dwithee | Hazmat | 915614 |
CO Springs DRE | Original | D | 10/25/2016 | MBINGMAN | MBINGMAN | This site has an approved development plan that includes elevations. A minor modification to the approved plan needs to be completed before approval of the building permit. Please fill out the form in the following link to request a meeting with the area planner: https://coloradosprings.gov/planning/webform/request-schedule-pre-application-meeting (see full review) | | CO Springs DRE | 913073 |
Zoning/Planning | Original | / | 10/25/2016 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 912974 |
Mechanical | Original | A | 10/25/2016 | JUSTINC | JUSTINC | See sheet A-1.0 | | Mechanical | 912962 |
Water Division | Original | N | 10/25/2016 | CSUREVIEW | CSUREVIEW | No concerns CQ | cquinn_ds | Water Division | 912954 |
Waste Water Div | Original | N | 10/25/2016 | CSUREVIEW | CSUREVIEW | No concerns CQ | cquinn_ds | Waste Water Div | 912953 |
Electrical | Original | D | 10/24/2016 | BERTHA | BERTHA | Provide electrical sheets. See checklist http://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202015a.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 912927 |
Construction | Original | D | 10/24/2016 | SHELLEY | SHELLEY | Code study from needs to be signed and dated. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 912722 |
Electronic Plan | Original | / | 10/24/2016 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 912664 |
Enumeration | Original | A | 10/21/2016 | AMY | AMY | | | Enumeration | 912499 |
Electronic Plan | Original | / | 10/21/2016 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 912497 |
Floodplain | Original | N | 10/20/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 912229 |
Floodplain | Original | N | 10/20/2016 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 912230 |