Mechanical | Original | A | 6/16/2017 | JUSTINC | JUSTINC | | | Mechanical | 969949 |
Construction | Original | A | 6/16/2017 | SHELLEY | SHELLEY | | | Construction | 969925 |
Electrical | Original | A | 6/16/2017 | BERTHA | BERTHA | | | Electrical | 969909 |
Out to Review | Original | / | 5/22/2017 | GITA | GITA | darin 719-623-3314 | | Out to Review | 962283 |
Finished Bin | Original | / | 5/22/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 962033 |
County Zoning | Original | N | 5/19/2017 | DSDRANGEL | DSDRANGEL | | | County Zoning | 961987 |
Zoning/Planning | Original | / | 5/19/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 961928 |
Plan Coordinator | Original | / | 5/19/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 961894 |
Plumbing | Original | A | 5/19/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 961890 |
Plumbing | Original | / | 5/19/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 961649 |
Plan Coordinator | Original | / | 5/19/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 961592 |
Mechanical | Original | D | 5/19/2017 | JUSTINC | JUSTINC | Per the first review a change of occupancy will require a complete ventilation schedule for all associated spaces. It will also require a complete mechanical drawing showing all of the HVAC system and all existing elements are also to be included. All new penetrations of rated ceiling will need to be compliant. Provide detail of any new penetrations.
RETURN ALL COMMENT SHEETS WITH NEXT REVIEW WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 961590 |
Mechanical | Original | / | 5/19/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 961589 |
Mechanical | Original | / | 5/15/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 960238 |
Plan Coordinator | Original | / | 5/15/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 960217 |
Electrical | Original | D | 5/15/2017 | BERTHA | BERTHA | Specify heights of all existing and new electrical devices. Indicate compliance with 210.8 NEC and ANSI 117.1.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 960216 |
Electrical | Original | / | 5/11/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 959504 |
Electrical | Original | / | 5/11/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 959491 |
Plan Coordinator | Original | / | 5/11/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 959474 |
Construction | Original | D | 5/11/2017 | MICHAELA | MICHAELA | Change of occupancy requires all toilet rooms to be made accessible Swing-up grab bars are only permitted in residential or institutional Type B sleeping rooms. Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 959473 |
Construction | Original | / | 5/10/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 958980 |
Construction | Original | / | 5/8/2017 | | JANE | Location = Construction by JANE | | Construction | 958476 |
Resubmittal 2 | Original | / | 5/8/2017 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 958475 |
Out to Review | Original | / | 3/2/2017 | NELIDA | NELIDA | Darin 623-3314 | | Out to Review | 940579 |
Finished Bin | Original | / | 2/24/2017 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 939326 |
Plan Coordinator | Original | / | 2/24/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 939214 |
Construction | Original | D | 2/24/2017 | MICHAELA | MICHAELA | This is an unlimited area building. An I-4 occupancy is not permitted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 939213 |
Construction | Original | / | 2/24/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 939096 |
Construction | Original | / | 2/22/2017 | | NELIDA | Location = Construction by NELIDA | | Construction | 938626 |
Resubmittal 1 | Original | / | 2/22/2017 | NELIDA | NELIDA | Resubmittal #1 2/22/17 | | Resubmittal 1 | 938624 |
Enumeration | Original | A | 1/27/2017 | BRENT | BRENT | | | Enumeration | 933040 |
Mechanical | Original | D | 1/27/2017 | JUSTINC | JUSTINC | Provide ventilation schedule per 09' IMC 403.3
WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 933035 |
Out to Review | Original | / | 1/23/2017 | NELIDA | NELIDA | Darin walking 623-3314 | | Out to Review | 931534 |
Floodplain | Original | N | 1/23/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 931533 |