Scanned/Finished Bin | Original | / | 3/10/2017 | | JESSICAM | Location = Scanned/Finished Bin by JESSICAM | | Scanned/Finished Bin | 942918 |
To Be Scanned Bin | Original | / | 3/9/2017 | | JLANE | Location = To Be Scanned Bin by JLANE | | To Be Scanned Bin | 942629 |
Electrical | Original | A | 3/9/2017 | SHELBY | SHELBY | | | Electrical | 942614 |
Construction | Original | A | 3/9/2017 | MICHAELA | MICHAELA | | | Construction | 942610 |
Electrical | Original | D | 3/3/2017 | BERTHA | BERTHA | 1. Comply with previous comments 3 and 4. 2. Panel LA feeder requires a disconnect on the structure. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 940979 |
Out to Review | Original | / | 3/3/2017 | NELIDA | NELIDA | picked up by Ashley | | Out to Review | 940924 |
Finished Bin | Original | / | 3/2/2017 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 940598 |
Hazmat | Original | N | 3/1/2017 | CSFIRE | CSFIRE | | dwithee | Hazmat | 940393 |
CO Springs Fire | Original | N | 2/28/2017 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 939833 |
Fire | Original | / | 2/16/2017 | | GSANDERS | Location = Fire by GSANDERS | | Fire | 937634 |
CO Springs DRE | Original | A | 2/16/2017 | GSANDERS | GSANDERS | Plans match stamped approved plans per RMT. (see full review) | | CO Springs DRE | 937633 |
Zoning/Planning | Original | / | 2/16/2017 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 937298 |
Plan Coordinator | Original | / | 2/15/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 937288 |
Electrical | Original | D | 2/15/2017 | SHELBY | SHELBY | 1. Remove parallel neutral from service lateral. 2. Show location of panel LA on H frame detail and on site plan. 3. Identify use of second service disconnect depicted on E 2.10). 4. Comply 225.30, 225.31, and 225.32 NEC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 937287 |
Electrical | Original | / | 2/8/2017 | | RITA | Location = Electrical by RITA | | Electrical | 935528 |
Mechanical | Original | N | 2/2/2017 | TCRIPPEN | TCRIPPEN | no mechanical issue no permit | | Mechanical | 934152 |
Plumbing | Original | N | 2/2/2017 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit water and waste water removed not required | | Plumbing | 934151 |
Enumeration | Original | A | 2/2/2017 | AMY | AMY | NEW SITE | | Enumeration | 934121 |
Out to Review | Original | / | 2/2/2017 | MICHAELA | MICHAELA | | | Out to Review | 934116 |
Construction | Original | D | 2/2/2017 | MICHAELA | MICHAELA | Provide through penetration firestop system for steel penetrations to existing beams V-A construction 100 MPH wind speed No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 934115 |
Floodplain | Original | N | 2/2/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 934084 |
Floodplain | Original | N | 2/2/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 934085 |