Out to Review | Original | / | 3/8/2018 | MATTHEWM | MATTHEWM | Scanned// Mike from Buffalo Buildiers picked up | | Out to Review | 1044934 |
Scanned/Finished Bin | Original | / | 3/8/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1044879 |
To Be Scanned Bin | Original | / | 3/8/2018 | | MATTHEWM | Location = To Be Scanned Bin by MATTHEWM | | To Be Scanned Bin | 1044851 |
Hazmat | Original | N | 3/2/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1042669 |
CO Springs Fire | Original | A | 3/2/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1042668 |
CO Springs DRE | Original | A | 2/27/2018 | LTHELEN | LTHELEN | This plan is approved pending a final revision to the minor modification to show all offices in warehouse spaces and to revise sheet A-1 to show office and warehouse (not wood shop) for 1545 Vapor Trail. These changes need to be made prior to any final sign offs from RBD for the furnace installation. The amended sheets will be added back into the approved plan set. Parking is met on site and the uses are ok within the zone district. (see full review) | | CO Springs DRE | 1041219 |
Fire | Original | / | 2/27/2018 | | LTHELEN | Location = Fire by LTHELEN | | Fire | 1041197 |
CO Springs DRE | Original | D | 2/27/2018 | LTHELEN | LTHELEN | A minor mod was submitted, but the minor mod approved does not match the office allocation for the units shown on the building permit. (see full review) | | CO Springs DRE | 1041196 |
Out to Review | Original | / | 1/18/2018 | | CSFIRE | Location = Out to Review by CSFIRE | gailcage | Out to Review | 1029613 |
Fire | Original | / | 1/17/2018 | | MBINGMAN | Location = Fire by MBINGMAN | | Fire | 1029092 |
CO Springs DRE | Original | D | 1/17/2018 | MBINGMAN | MBINGMAN | Please fill out and submit the pre-application meeting request application to meet with a South Team planner. Modification to the approved Development Plan required. (see full review) | | CO Springs DRE | 1029091 |
Out to Review | Original | / | 1/16/2018 | MINDY | MINDY | Mike 719 640-3405 | | Out to Review | 1028582 |
Finished Bin | Original | / | 1/16/2018 | | BPHILLIPS | Location = Finished Bin by BPHILLIPS | | Finished Bin | 1028513 |
Water Division | Original | N | 12/26/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. RDS | rsolberg | Water Division | 1023910 |
Waste Water Div | Original | N | 12/26/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. RDS | rsolberg | Waste Water Div | 1023909 |
Construction | Original | A | 12/21/2017 | DANM | DANM | | | Construction | 1023554 |
Mechanical | Original | A | 12/21/2017 | DALEH | DALEH | | | Mechanical | 1023450 |
Mechanical | Original | D | 12/15/2017 | JUSTINC | JUSTINC | 200 CFM of Outside air indicated with F-1. Cannot locate on plan how providing, No ducts shown to exterior? Sheet M1.1 indicates in note number 2 outside air and furnace vent. This is not outside air, this is combustion air vent. Only show work associated with 1541 Vapor Trail for this permit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1021936 |
Construction | Original | D | 12/6/2017 | DANM | DANM | Code Study Form needs to be stamped by Colorado licensed design professional
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1019320 |
Electrical | Original | A | 12/6/2017 | SHELBY | SHELBY | | | Electrical | 1019294 |
Plumbing | Original | N | 12/6/2017 | DALEH | DALEH | | | Plumbing | 1019282 |
Mechanical | Original | D | 12/6/2017 | DALEH | DALEH | need to show o.s.a. duct to furnace (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1019281 |
Construction | Original | D | 11/22/2017 | SHELLEY | SHELLEY | still need detail for how demising wall was built - no permit on file for wall construction (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1015253 |
Electrical | Original | D | 11/22/2017 | BERTHA | BERTHA | 1. Provide conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work 2. Provide listed combinations for fuse/breaker combination - series rating. 3. Provide minor/major garage designation. 4. Clarify new and existing 5. Provide all new and existing for change of occupancy - comply ANSI 117.1.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1015251 |
Mechanical | Original | D | 11/22/2017 | JUSTINC | JUSTINC | Provide ventilation schedule for shops and shop office How heating shop office How providing ventilation to new furnace Verify ventilation schedules 92% O.S.A 730 cfm from a 800 cfm furnace? Provide letter from manafacture
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1015237 |
Electrical | Original | A | 4/6/2017 | SHELBY | SHELBY | provide electrical | | Electrical | 950175 |
Plumbing | Original | D | 4/6/2017 | DALEH | DALEH | cant have mop sink in bathroom (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 950159 |
Mechanical | Original | D | 4/6/2017 | DALEH | DALEH | provide complete mechanical (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 950158 |
Out to Review | Original | / | 4/6/2017 | BPHILLIPS | BPHILLIPS | | | Out to Review | 950107 |
Construction | Original | D | 4/6/2017 | BPHILLIPS | BPHILLIPS | Demising wall built without permit - need information on wall construction - partial change of occupancy? Clarify scope. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 950106 |
Enumeration | Original | A | 4/6/2017 | AMY | AMY | New address assignment | | Enumeration | 950052 |
Floodplain | Original | N | 4/6/2017 | AMY | AMY | | | Floodplain | 950051 |