Out to Review | Original | / | 6/26/2017 | NELIDA | NELIDA | David Woody 719-531-9018 | | Out to Review | 972879 |
Finished Bin | Original | / | 6/26/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 972846 |
Health Dept. | Original | D | 6/26/2017 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required. Contact 578-3199 option #3 for more information regarding construction activity permits. AP 578-3278 | Aparikh | Health Dept. | 972808 |
Health Dept. | Original | / | 6/23/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 972371 |
Water Division | Original | D | 6/23/2017 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. RDS | cquinn_ds | Water Division | 972368 |
Waste Water Div | Original | D | 6/23/2017 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. RDS | cquinn_ds | Waste Water Div | 972367 |
Gas/Elec. Utils | Original | A | 6/23/2017 | CSUREVIEW | CSUREVIEW | No concerns. RDS | cquinn_ds | Gas/Elec. Utils | 972366 |
CSU Utilities | Original | / | 6/23/2017 | | CSUREVIEW | Location = CSU Utilities by CSUREVIEW | hfranson | CSU Utilities | 972358 |
Hazmat | Original | N | 6/23/2017 | CSFIRE | CSFIRE | | dwithee | Hazmat | 972344 |
City Engr | Original | D | 6/23/2017 | CSENGINEER | CSENGINEER | Include a copy of the City Engineering approved Grading & Erosion Control Plan in the building permit set. Plan set route to CSU Utilities. pvm | csengineer | City Engr | 972133 |
CO Springs Fire | Original | D | 6/21/2017 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 971446 |
Fire | Original | / | 6/15/2017 | | KCARLEO | Location = Fire by KCARLEO | | Fire | 969679 |
CO Springs DRE | Original | D | 6/15/2017 | KCARLEO | KCARLEO | Must include stamped approved copy of Development Plan. AR PUD 17-00114 (see full review) | | CO Springs DRE | 969678 |
Zoning/Planning | Original | / | 6/14/2017 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | zshearer | Zoning/Planning | 969184 |
CSU Contract Admin. | Original | D | 6/14/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires approved commercial water meter sizing form and payment of development charges and fees. call 719-668-8111 to inquire. ZJS | zshearer | CSU Contract Admin. | 969181 |
CSU Contract Admin. | Original | / | 6/14/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 968986 |
Plan Coordinator | Original | / | 6/14/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 968957 |
Plumbing | Original | D | 6/14/2017 | TCRIPPEN | TCRIPPEN | back grounds to match A-pages we do not use mirror images show on plans as it is to be built all so provide vertical stacks provide drainage fixture units at building exit of sanitary line can`t read water pressure calculation ///// 2 plans 97686, 97687
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 968956 |
Plumbing | Original | / | 6/13/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 968828 |
Plumbing | Original | / | 6/13/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 968798 |
Plan Coordinator | Original | / | 6/13/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 968752 |
Mechanical | Original | D | 6/13/2017 | JUSTINC | JUSTINC | Mechanical review incomplete
Clarify how elevator hoistway ventilation complies with 09' IBC 3004. (TYP.)
Ducts associated with HRV shown penetrating rated exit enclosure. Clarify how complying with 09' IBC 1022.4. When intent is to provide penetrations thru rated assemblies without protection. Provide a detail or sheet note indicating code sections and any exceptions used.
Provide section view of how duct will be run in units. Note indicates to run duct in floor joist space. No protection is indicated where duct will penetrate membrane of floor/ ceiling assembly. When intent is to provide penetrations thru rated assemblies without protection. Provide a detail or sheet note indicating code sections and any exceptions used.
Provide section view of how furnace and associated duct will be installed in relation to floor ceiling assembly.No protection is indicated where duct penetrates membrane to run duct in joist space. When intent is to provide penetrations thru rated assemblies without protection. Provide a detail or sheet note indicating code sections and any exceptions used.
Add note: Gas is an engineered system.
Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection
NO WALK
PLANS IN SERIES - (97686), (97687) (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 968750 |
Mechanical | Original | / | 6/13/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 968696 |
Mechanical | Original | / | 6/12/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 968135 |
Plan Coordinator | Original | / | 6/12/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 968065 |
Electrical | Original | D | 6/12/2017 | BERTHA | BERTHA | 1. Clearly indicate accessibility on overall floor plan using nomenclature from ANSI 117.1, Chapter 10 (Fully, Type A, Type B). 2. Provide available fault current. Clarify use of > Panel B2 and elevators. 3. Remove parallel neutral - feeders 3003, 4503, 6004 - from wiring gutter to disconnects. 4. Show method of 240.87 NEC compliance. 5. Label electric meters on one line with the enumerated addresses each meter serves. 6. Provide an elevator detail showing all required disconnects and circuits and showing compliance with elevator review comments. 7. Show all disconnects serving the structure on site plan. 8. Clarify Main Sw #3 and Main Sw #4 on one-line.
Plans in series: 97686, 97687
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 968064 |
Electrical | Original | / | 6/8/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 967278 |
Electrical | Original | / | 6/6/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 966351 |
Plan Coordinator | Original | / | 6/6/2017 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 966269 |
Elevators | Original | D | 6/6/2017 | ERIC | ERIC | Provide elevator manufacturers specs/build sheets, Need pit and hoistway details, Provide hoistway ventilation to code, equipment disconnects can not be located in hoistway (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 966268 |
Elevators | Original | / | 6/6/2017 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 966123 |
Plan Coordinator | Original | / | 6/6/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 966106 |
Construction | Original | D | 6/6/2017 | DANM | DANM | Residential IECC Certificate required Provide accessible unit calculation requirements - identify all Type A & B Units on all floor plans on all levels Identify location of elevator equipment rooms Provide section(s) through elevator shaft Multiple listed assemblies not properly denoted throughout Stair landing at short run by angled wall not adequate on all levels Second half of fourth floor plan seems to be missing Multiple floor clearance redlines on enlarged unit plans Clarify how knee and toe clearance at kitchen and bathroom sinks is being met in Type A units Clarify location of kitchen work surface in Type A units Multiple scales shown for elevations Address reduced vertical clearance at stair per ICC/ANSI 307.4 Identify sections on all plans Referenced listed assemblies do not match section details Legibility of listed assemblies is poor Structural sheets do not seem to match this building No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 966105 |
Construction | Original | / | 6/1/2017 | DANM | DANM | In Current Review by DANM | | Construction | 964930 |
Construction | Original | / | 5/30/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 964151 |
Plan Coordinator | Original | / | 5/30/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 964107 |
Enumeration | Original | D | 5/30/2017 | BRENT | BRENT | Show secondary addressing for all apartment units. Secondary addressing guidelines can be found on our website www.pprbd.org ->addressing-secondary addressing guide. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 964106 |
Floodplain | Original | N | 5/25/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 963653 |