Canceled Plans | Original | / | 7/29/2018 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 1094203 |
Hazmat | Original | D | 2/7/2018 | CSFIRE | CSFIRE | Previous Review comments not addressed. Plans still disapproved. Please read disapproved comments, provide the required documentation in hard copy to the Division of the Fire Marshal, and provide a comment response letter indicating how comments have been resolved. (see full review) | smanning | Hazmat | 1035783 |
Electrical | Original | A | 1/31/2018 | SHELBY | SHELBY | | | Electrical | 1033421 |
CO Springs Fire | Original | A | 1/30/2018 | CSFIRE | CSFIRE | reference review report online for inspection information. 3rd review fee imposed. (see full review) | csfdit | CO Springs Fire | 1032852 |
CO Springs DRE | Original | D | 1/29/2018 | MBINGMAN | MBINGMAN | Same comment (see full review) | | CO Springs DRE | 1032614 |
Resubmittal 4 | Original | / | 1/29/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1032544 |
Mechanical | Original | A | 1/25/2018 | DALEH | DALEH | | | Mechanical | 1031638 |
Hazmat | Original | D | 1/23/2018 | CSFIRE | CSFIRE | The previously disapproved plan comments have not been addressed; please provide a comment response page indicating how these comments have been addressed. Please note that this is the 4th time that this plan has been disapproved by Hazmat. Please do not submit plans unless they address disapproved comments as additional plan review fees will apply. (see full review) | smanning | Hazmat | 1030785 |
CO Springs Fire | Original | D | 1/12/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1028322 |
Electrical | Original | D | 1/11/2018 | SHELBY | SHELBY | Please specify height of the class 1 division 2 area. The height of the classified area is not the ceiling or roof or deck. Specify the height of the classified area. An example would be " Class 1 Division 2 area extends three feet from floor". (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1028123 |
CO Springs DRE | Original | D | 1/11/2018 | MBINGMAN | MBINGMAN | 4th denial for the same comment. (see full review) | | CO Springs DRE | 1028086 |
Zoning/Planning | Original | / | 1/11/2018 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 1028085 |
Resubmittal 3 | Original | / | 1/11/2018 | SHELLEY | SHELLEY | Resubmittal #3 | | Resubmittal 3 | 1028082 |
Hazmat | Original | D | 1/8/2018 | CSFIRE | CSFIRE | Plans disapproved. Previously disapproved hazmat comments not addressed. (see full review) | smanning | Hazmat | 1026687 |
CO Springs Fire | Original | D | 12/29/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1024799 |
Electrical | Original | D | 12/18/2017 | SHELBY | SHELBY | Please indicate the height of the class 1 Division 2 area . ( Note added specifies ceiling height). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1022363 |
CO Springs DRE | Original | D | 12/13/2017 | MBINGMAN | MBINGMAN | Same comment as 6/12/17, 9/18/2017, & 9/29/2017 . Must provide all licensing documentation from the City Clerks office to show modification of premises approval. Shall include approved application and interior layout that was approved by City Clerk. Please call Matt Bingman at 719.385.5602 or email at mbingman@springsgov.com with questions. (see full review) | | CO Springs DRE | 1021277 |
Zoning/Planning | Original | / | 12/13/2017 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 1021274 |
Mechanical | Original | D | 12/13/2017 | DALEH | DALEH | not all previous green lines were addressed respond to all blue lines and resubmit (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1021181 |
Electronic Plan | Original | / | 12/13/2017 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1020991 |
Resubmittal 2 | Original | / | 12/13/2017 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1020948 |
Hazmat | Original | D | 10/13/2017 | CSFIRE | CSFIRE | The previously disapproved plan comments have not been addressed; please provide a comment response page indicating how these comments have been addressed. Plans disapproved. Please read "full review" comments. Please recall CSFD extraction submittal requirements as most have still not been met - see https://csfd.coloradosprings.gov/sites/default/files/fire/files/DFM/Hazmat/MMJ/mmj_process_submittal_requirements_15.pdf (see full review) | smanning | Hazmat | 1003815 |
CO Springs Fire | Original | D | 10/12/2017 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1003325 |
Mechanical | Original | D | 10/3/2017 | DALEH | DALEH | Need to respond to all previous red line comments and current green line comments no further review incomplete review
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1000679 |
Electrical | Original | D | 10/2/2017 | SHELBY | SHELBY | Please address previous review comment 1.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1000489 |
Plumbing | Original | A | 10/2/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1000109 |
CO Springs DRE | Original | D | 9/29/2017 | MBINGMAN | MBINGMAN | Same comment as 6/12/17 & 9/18/2017. Must provide all licensing documentation from the City Clerks office to show modification of premises approval. Shall include approved application and interior layout that was approved by City Clerk. (see full review) | | CO Springs DRE | 999864 |
Hazmat | Original | D | 9/26/2017 | CSFIRE | CSFIRE | Plans remain disapproved; comments have not been addressed. Please provide comment responses upon next submittal. Please read disapproval comments. (see full review) | smanning | Hazmat | 998568 |
CO Springs Fire | Original | D | 9/22/2017 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 997974 |
Electrical | Original | D | 9/21/2017 | SHELBY | SHELBY | 1. Specify height of class 1 division 2 area. 2. Remove parallel neutral(ground wire) from conductor between C/T can and new disconnect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 997446 |
Mechanical | Original | D | 9/20/2017 | DALEH | DALEH | Structural letter for RTU and MUA ? provide manufacturers hood specs how protecting penetrations through rated assembly's ? see plans for all red lines
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 996904 |
Plumbing | Original | D | 9/18/2017 | TCRIPPEN | TCRIPPEN | drinking fountain lift station to be direct connection to the sanitary waste (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 996433 |
CO Springs DRE | Original | D | 9/18/2017 | MBINGMAN | MBINGMAN | Same comment as 6/12/17 (see full review) | | CO Springs DRE | 996192 |
Construction | Original | A | 9/18/2017 | DANM | DANM | | | Construction | 996140 |
Electronic Plan | Original | / | 9/15/2017 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 996096 |
Resubmittal 1 | Original | / | 9/15/2017 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 995988 |
Hazmat | Original | D | 6/28/2017 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproval comments. (see full review) | smanning | Hazmat | 973458 |
CO Springs Fire | Original | D | 6/15/2017 | CSFIRE | CSFIRE | reference review report online for comments (see full review) | csfdit | CO Springs Fire | 969431 |
Mechanical | Original | D | 6/15/2017 | DALEH | DALEH | separate m and p pages no review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 969391 |
Electronic Plan | Original | / | 6/15/2017 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 969390 |
Electrical | Original | D | 6/13/2017 | SHELBY | SHELBY | 1. Approval in electrical will be dependent on Hazmat approval. 2. Clearly label Class 1 Division 1 area. 3. Clearly show the extent of the classified area adjacent to the Class 1 Division 1 area [see 500.5(B)(2)(3) NEC ]. 4. Clearly show and label all existing and new electrical equipment on floor plan ( C/T can, new disconnect etc) comply 240.21 NEC. 5. Use 2009 IECC the 2015 has not been adopted. 6. For service load calculation; obtain peak demand from serving utility ( Excel does not serve this area). 7. Feeder tap ground conductor is incorrect ( see 250.122G NEC). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 968624 |
CO Springs DRE | Original | D | 6/12/2017 | MBINGMAN | MBINGMAN | All MMJ improvements require a modification of premises application to be filed with the City Clerk's office. If this has been done please provide City Clerk paperwork for the modification of premises as part of the electronic submittal. We will need this documentation before we release the plan review. (see full review) | | CO Springs DRE | 968160 |
Zoning/Planning | Original | / | 6/12/2017 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 968061 |
Water Division | Original | N | 6/12/2017 | CSUREVIEW | CSUREVIEW | No new water service line proposed outside the building. Minor plumbing work proposed. Backflow survey completed by Vince. OK per Holly Link. HSF | hfranson | Water Division | 968058 |
Waste Water Div | Original | N | 6/12/2017 | CSUREVIEW | CSUREVIEW | No new wastewater service line proposed outside the building. HSF | hfranson | Waste Water Div | 968053 |
Plumbing | Original | D | 6/12/2017 | TCRIPPEN | TCRIPPEN | plumbing and mechanical to be on separate page per our web site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 968020 |
Electronic Plan | Original | / | 6/12/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 968014 |
Construction | Original | D | 6/9/2017 | DANM | DANM | Revise occupant load on Code Study Form and drawings based on occupant load factor for all Grow areas to be 1 occ/200 sf Actual areas shown in sum of the ratios calculations do not match what is on Code Study Form Demo Floor Plan does not match plan permitted in 2012 (see Other category for PDF of permitted floor plan)
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 967921 |
Electronic Plan | Original | / | 6/7/2017 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 966901 |
Enumeration | Original | A | 6/6/2017 | BRENT | BRENT | | | Enumeration | 966419 |
Floodplain | Original | N | 6/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 965240 |
Floodplain | Original | N | 6/1/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 965239 |