- Not Set - | Splice 02/04/19 -trusses | / | 1/29/2020 | | SCANNING | Location = Plans have been disposed of -J3- | | - Not Set - | 1281039 |
- Not Set - | Splice 02/04/19 -trusses | / | 10/3/2019 | JLANE | JLANE | EXPIRED PLAN: Plan is over 180 days old, they are expired. If not picked up they will be disposed on 10/31/19. Plan have been scanned into the record.- by JLANE | | - Not Set - | 1242378 |
Mechanical | Splice 08/14/19 | A | 8/14/2019 | JUSTINC | JUSTINC | Revised water heater vent routing | | Mechanical | 1223807 |
Out to Review | Splice 08/14/19 | / | 8/14/2019 | BECKYA | BECKYA | | | Out to Review | 1223782 |
Construction | Splice 04/04/19 | A | 4/4/2019 | LBENNETT | LBENNETT | Revised roof/ceiling from UL P522 to UL P5454 | | Construction | 1174795 |
Out to Review | Splice 04/04/19 | / | 4/4/2019 | BECKYA | BECKYA | | | Out to Review | 1174790 |
Mechanical | Splice 02/15/19 | A | 2/28/2019 | JUSTINC | JUSTINC | Revised gas | | Mechanical | 1163833 |
Resubmittal 1 | Splice 02/15/19 | / | 2/28/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1163811 |
Scanned/Finished Bin | Splice 02/04/19 -trusses | / | 2/26/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1162972 |
To Be Scanned Bin | Splice 02/04/19 -trusses | / | 2/26/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1162953 |
Plan Coordinator | Splice 02/04/19 -trusses | / | 2/26/2019 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1162812 |
Construction | Splice 02/04/19 -trusses | A | 2/26/2019 | SHELLEY | SHELLEY | TRUSSES | | Construction | 1162811 |
Construction | Splice 02/04/19 -trusses | / | 2/26/2019 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1162784 |
Construction | Splice 02/04/19 -trusses | / | 2/26/2019 | | GITA | Location = Construction by GITA | | Construction | 1162747 |
Resubmittal 1 | Splice 02/04/19 -trusses | / | 2/26/2019 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1162658 |
Out to Review | Splice 02/04/19 -trusses | / | 2/19/2019 | RITA | RITA | Mike 303-434-5192 | | Out to Review | 1160279 |
Mechanical | Splice 02/15/19 | D | 2/15/2019 | JUSTINC | JUSTINC | Only cloud revisions associated with splice. See note on plan sheet for more detail. Clarify delta tags. See note on floor plan
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1159725 |
Out to Review | Splice 02/15/19 | / | 2/15/2019 | BECKYA | BECKYA | | | Out to Review | 1159694 |
Finished Bin | Splice 02/04/19 -trusses | / | 2/5/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1156181 |
Plan Coordinator | Splice 02/04/19 -trusses | / | 2/5/2019 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1156112 |
Construction | Splice 02/04/19 -trusses | D | 2/5/2019 | SHELLEY | SHELLEY | Please follow trusses pending submittal procedures as indicated on plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1156111 |
Construction | Splice 02/04/19 -trusses | / | 2/5/2019 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1156086 |
Construction | Splice 02/04/19 -trusses | / | 2/4/2019 | | GITA | Location = Construction by GITA | | Construction | 1155698 |
Out to Review | Original | / | 2/15/2018 | NELIDA | NELIDA | Ride along with Joel - plumbing | | Out to Review | 1038157 |
Scanned/Finished Bin | Original | / | 2/14/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1037650 |
To Be Scanned Bin | Original | / | 2/14/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1037445 |
City Engr | Original | A | 2/13/2018 | CSENGINEER | CSENGINEER | Walk through approval. jad | csengineer | City Engr | 1037391 |
CSU Contract Admin. | Original | A | 2/13/2018 | CSUAPPSPRM | CSUAPPSPRM | Development charges/fees paid. LMP | lmpope | CSU Contract Admin. | 1037303 |
Out to Review | Original | / | 2/13/2018 | NELIDA | NELIDA | Emery 520-907-2807 | | Out to Review | 1037118 |
Finished Bin | Original | / | 1/17/2018 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 1029280 |
Construction | Original | A | 1/17/2018 | BPHILLIPS | BPHILLIPS | revised site plan | | Construction | 1029263 |
Out to Review | Original | / | 1/17/2018 | JUSTINC | JUSTINC | Jessica - 719-473-8400 | | Out to Review | 1029237 |
Mechanical | Original | A | 1/17/2018 | JUSTINC | JUSTINC | New sheets added before permit for additional gas | | Mechanical | 1029236 |
CSU Contract Admin. | Original | D | 1/17/2018 | CSUAPPSPRM | CSUAPPSPRM | CWMSF Approved. Requires Payment of Development Charges and Fees.ZJS | zshearer | CSU Contract Admin. | 1029030 |
City Engr | Original | / | 1/17/2018 | | CSUAPPSPRM | Location = City Engr by CSUAPPSPRM | zshearer | City Engr | 1029028 |
Out to Review | Original | / | 1/11/2018 | RITA | RITA | Jessica 473-8400 | | Out to Review | 1027906 |
Finished Bin | Original | / | 12/18/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1022317 |
Health Dept. | Original | N | 12/18/2017 | HEALTHDEPT | HEALTHDEPT | Plan review is not needed - Not applicable. AP 578-3278 | Aparikh | Health Dept. | 1022306 |
Health Dept. | Original | / | 12/15/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1021888 |
City Engr | Original | D | 12/15/2017 | CSENGINEER | CSENGINEER | See previous comment - Include a copy Water Resources Engineering approved Grading & Erosion Control Plan in the building permit set. Plan set routed to RBD. jad | csengineer | City Engr | 1021865 |
City Engr | Original | / | 12/15/2017 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 1021592 |
Hazmat | Original | N | 12/14/2017 | CSFIRE | CSFIRE | Hazmat N/A. Chemicals under permit quantities. No inspection required. Plans forwarded to RBD. (see full review) | smanning | Hazmat | 1021539 |
Hazmat | Original | / | 12/11/2017 | | CSFIRE | Location = Hazmat by CSFIRE | fdjah74 | Hazmat | 1020186 |
CO Springs Fire | Original | A | 12/11/2017 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1020173 |
Water Division | Original | A | 12/6/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Water Division | 1019288 |
Waste Water Div | Original | A | 12/6/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Waste Water Div | 1019287 |
Out to Review | Original | / | 9/6/2017 | RITA | RITA | Jessica 719-473-8400 | | Out to Review | 993298 |
Finished Bin | Original | / | 8/22/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 989134 |
Plan Coordinator | Original | / | 8/22/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 989123 |
Mechanical | Original | A | 8/22/2017 | DALEH | DALEH | | | Mechanical | 989122 |
Mechanical | Original | / | 8/22/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 989084 |
Mechanical | Original | / | 8/22/2017 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 989040 |
Resubmittal 2 | Original | / | 8/22/2017 | MINDY | MINDY | Resubmittal #2 Mechanical only | | Resubmittal 2 | 989039 |
Out to Review | Original | / | 8/11/2017 | GITA | GITA | jessica 719-4738400 | | Out to Review | 986151 |
Finished Bin | Original | / | 8/10/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 985487 |
Plan Coordinator | Original | / | 8/10/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 985394 |
Mechanical | Original | D | 8/10/2017 | DALEH | DALEH | why radiation dampers in unrated ceiling ? Just a question it appears there are no horizontal assembles.. see plan red line for range in clubhouse see comment about installation of dampers see comments on gas piping see plans for complete red lines return red lines with next review no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 985389 |
Mechanical | Original | / | 8/8/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 984850 |
Mechanical | Original | / | 8/7/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 984339 |
Plan Coordinator | Original | / | 8/7/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 984320 |
Construction | Original | A | 8/7/2017 | SHELLEY | SHELLEY | TRUSSES PENDING | | Construction | 984319 |
Construction | Original | / | 8/7/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 984283 |
Construction | Original | / | 8/7/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 984282 |
Resubmittal 1 | Original | / | 8/4/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 984077 |
Electrical | Original | A | 8/2/2017 | SHELBY | SHELBY | Revisions prior to permit | | Electrical | 983400 |
Enumeration | Original | A | 8/2/2017 | BRENT | BRENT | Final plat has been recorded | | Enumeration | 983387 |
Plumbing | Original | A | 8/2/2017 | TCRIPPEN | TCRIPPEN | approved as noted freeze protection and blow down required for outside sink. | | Plumbing | 983386 |
Out to Review | Original | / | 7/7/2017 | GITA | GITA | 719-473-8400 By jessica | | Out to Review | 976068 |
Finished Bin | Original | / | 7/7/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 976054 |
Health Dept. | Original | D | 7/7/2017 | HEALTHDEPT | HEALTHDEPT | El Paso County Public Health plan review required for swimming pool. Contact Neil Mayes at 719-578-3199 option #3. GA 578-3295 Air quality construction activity permit required. Contact 578-3199 option #3 for more information regarding construction activity permits. GA 578-3295 | galvarez | Health Dept. | 976041 |
Health Dept. | Original | / | 7/5/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 975384 |
Water Division | Original | D | 7/5/2017 | CSUREVIEW | CSUREVIEW | Requires an approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. RDS | rsolberg | Water Division | 975355 |
Waste Water Div | Original | D | 7/5/2017 | CSUREVIEW | CSUREVIEW | Requires an approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. RDS | rsolberg | Waste Water Div | 975354 |
Gas/Elec. Utils | Original | A | 7/5/2017 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Gas/Elec. Utils | 975353 |
City Engr | Original | D | 7/3/2017 | CSENGINEER | CSENGINEER | Include a copy of the City Engineering approved Grading & Erosion Control Plan in the building permit set. Plan set routed to CSU Utilities. jad | csengineer | City Engr | 975090 |
CSU Utilities | Original | / | 7/3/2017 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 974922 |
Hazmat | Original | D | 7/3/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 974917 |
CO Springs Fire | Original | D | 7/3/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 974914 |
Fire | Original | / | 6/29/2017 | | HVANNIMWEGEN | Location = Fire by HVANNIMWEGEN | | Fire | 974065 |
CO Springs DRE | Original | A | 6/29/2017 | HVANNIMWEGEN | HVANNIMWEGEN | Final Landscape and Final Irrigation Plans are due within 30 days of building permit issuance. Contact Connie Perry to set up a submittal meeting 719-385-5375 (see full review) | | CO Springs DRE | 974064 |
Zoning/Planning | Original | / | 6/28/2017 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | lmpope | Zoning/Planning | 973350 |
CSU Contract Admin. | Original | D | 6/28/2017 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form spliced into plan is not signed. Please resubmit a signed copy to cca@csu.org. Requires payment of development charges/fees. LMP | lmpope | CSU Contract Admin. | 973349 |
CSU Contract Admin. | Original | / | 6/27/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 972959 |
Plan Coordinator | Original | / | 6/27/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 972942 |
Mechanical | Original | D | 6/27/2017 | DALEH | DALEH | increase font size darken up backgrounds slightly schedule pool boilers no further review incomplete review no walk
Apartment plan associated to pool is plan number 98184
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 972941 |
Mechanical | Original | / | 6/27/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 972918 |
Mechanical | Original | / | 6/26/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 972551 |
Plan Coordinator | Original | / | 6/26/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 972518 |
Electrical | Original | A | 6/26/2017 | SHELBY | SHELBY | Note: Two plans in this series 98184, 98184 | | Electrical | 972517 |
Electrical | Original | / | 6/23/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 972397 |
Plumbing | Original | D | 6/21/2017 | TCRIPPEN | TCRIPPEN | provide an water pipe size analysis data on plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 971062 |
Electrical | Original | / | 6/20/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 970619 |
Plan Coordinator | Original | / | 6/20/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 970606 |
Construction | Original | D | 6/20/2017 | SHELLEY | SHELLEY | Comcheck missing slab on grade; add A-2 to occupancy classification due to kitchen; show imaginary property line with bulding 2 and show compliance with exterior wall openings accordingly; see plans; walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 970605 |
Construction | Original | / | 6/19/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 970267 |
Construction | Original | / | 6/15/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 969724 |
Plan Coordinator | Original | / | 6/15/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 969704 |
Enumeration | Original | D | 6/15/2017 | AMY | AMY | MAINTENANCE/POOL EQUIPMENT BUILDING -1 STRUCTURE PER ROOF TO CLUBHOUSE.
ENUMERATIONS WILL REVIEW THE MYLAR PRIOR TO PLAT FOR ADDRESS PLACEMENT, STREET NAME, TITLE BLOCK AND FLOODPLAIN STATEMENT. $10.00 PER LOT & TRACT FEE DUE AT THE TIME OF THE REVIEW OF THE MYLAR. CHECK SHOULD BE MADE OUT TO REGIONAL BUILDING DEPT.
A COPY OF THE FINAL RECORDED PLAT IS REQUIRED PRIOR TO APPROVAL IN THIS DEPARTMENT. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 969703 |
Floodplain | Original | N | 6/15/2017 | AMY | AMY | ONCE PLATTED THERE IS NO FLOODPLAIN ON THIS LOT. | | Floodplain | 969667 |
Enumeration | Original | / | 6/15/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 969666 |