- Not Set - | Splice 02/04/19-trusses | / | 1/29/2020 | | SCANNING | Location = Plans have been disposed of -J3- | | - Not Set - | 1281041 |
Mechanical | Splice 01/09/20 | A | 1/9/2020 | TCRIPPEN | TCRIPPEN | okay rerouted gas lines | | Mechanical | 1274418 |
Out to Review | Splice 01/09/20 | / | 1/9/2020 | BECKYA | BECKYA | | | Out to Review | 1274369 |
Electrical | Splice 11/21/19 | A | 12/11/2019 | BERTHA | BERTHA | Revised plan to indicate fault current at unit panels. | | Electrical | 1266060 |
Resubmittal 1 | Splice 11/21/19 | / | 12/11/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1266018 |
Electrical | Splice 11/21/19 | D | 11/21/2019 | BERTHA | BERTHA | Available fault current exceeds the withstand rating.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1259514 |
Out to Review | Splice 11/21/19 | / | 11/21/2019 | BECKYA | BECKYA | | | Out to Review | 1259487 |
Mechanical | Splice 10/23/19 Mech | A | 10/23/2019 | TCRIPPEN | TCRIPPEN | new splice showing gas meters and gas lines relocated | | Mechanical | 1248912 |
Out to Review | Splice 10/23/19 Mech | / | 10/23/2019 | BECKYA | BECKYA | | | Out to Review | 1248902 |
Electrical | Splice 10/23/19 | A | 10/23/2019 | BERTHA | BERTHA | Revised feeder for House Panel. | | Electrical | 1248665 |
Out to Review | Splice 10/23/19 | / | 10/23/2019 | BECKYA | BECKYA | | | Out to Review | 1248608 |
Health Dept. | Original | N | 10/21/2019 | HEALTHDEPT | HEALTHDEPT | Not applicable. | abrannon | Health Dept. | 1247652 |
- Not Set - | Splice 02/04/19-trusses | / | 10/3/2019 | JLANE | JLANE | EXPIRED PLAN: Plan is over 180 days old, they are expired. If not picked up they will be disposed on 10/31/19. Plan have been scanned into the record.- by JLANE | | - Not Set - | 1242379 |
Plumbing | Splice 08/22/19 | A | 8/22/2019 | SHANEN | SHANEN | Delta 6 revisions water pipe sizing | | Plumbing | 1226881 |
Out to Review | Splice 08/22/19 | / | 8/22/2019 | BECKYA | BECKYA | | | Out to Review | 1226855 |
Construction | Splice 08/21/19 | A | 8/21/2019 | BPHILLIPS | BPHILLIPS | Provided detail for ceiling at enclosure. | | Construction | 1226546 |
Out to Review | Splice 08/21/19 | / | 8/21/2019 | BECKYA | BECKYA | | | Out to Review | 1226512 |
Plumbing | Splice 08/14/19 L35557 L35553 | A | 8/14/2019 | SHANEN | SHANEN | 1 1/4" water mains to units B & D.1 | | Plumbing | 1223797 |
Out to Review | Splice 08/14/19 L35557 L35553 | / | 8/14/2019 | BECKYA | BECKYA | | | Out to Review | 1223785 |
Scanned/Finished Bin | Splice 05/15/19 | / | 5/16/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1191416 |
To Be Scanned Bin | Splice 05/15/19 | / | 5/16/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1191394 |
Plan Coordinator | Splice 05/15/19 | / | 5/16/2019 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1191363 |
Construction | Splice 05/15/19 | A | 5/16/2019 | SHELLEY | SHELLEY | Glass guards | | Construction | 1191362 |
Construction | Splice 05/15/19 | / | 5/16/2019 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1191356 |
Construction | Splice 05/15/19 | / | 5/15/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1191245 |
Out to Review | Splice 05/15/19 | / | 5/15/2019 | BECKYA | BECKYA | | | Out to Review | 1191221 |
Construction | Splice 04/03/19 | A | 4/3/2019 | SHELLEY | SHELLEY | Revised roof/ceiling assembly to P545; clarified stud pack encasement | | Construction | 1174222 |
Out to Review | Splice 04/03/19 | / | 4/3/2019 | BECKYA | BECKYA | | | Out to Review | 1174203 |
Construction | Splice 03/11/19 Various Permit Numbers | A | 3/18/2019 | SHELLEY | SHELLEY | Details for 3rd floor bearing/non-bearing walls and electrical/av cabinets in rated bearing walls.
Guardrails removed from splice. Separate splice will be required. | | Construction | 1168510 |
Out to Review | Splice 03/11/19 Various Permit Numbers | / | 3/18/2019 | JANE | JANE | Jessica | | Out to Review | 1168470 |
Finished Bin | Splice 03/11/19 Various Permit Numbers | / | 3/12/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1167125 |
Plan Coordinator | Splice 03/11/19 Various Permit Numbers | / | 3/12/2019 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1167096 |
Construction | Splice 03/11/19 Various Permit Numbers | D | 3/12/2019 | SHELLEY | SHELLEY | Guardrail information must be stamped by Colorado licensed design professional. Apply fee to L35564 Walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1167095 |
Construction | Splice 03/11/19 Various Permit Numbers | / | 3/12/2019 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1167075 |
Construction | Splice 03/11/19 Various Permit Numbers | / | 3/11/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1166944 |
Scanned/Finished Bin | Splice 02/04/19-trusses | / | 2/26/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1162971 |
To Be Scanned Bin | Splice 02/04/19-trusses | / | 2/26/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1162954 |
Plan Coordinator | Splice 02/04/19-trusses | / | 2/26/2019 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1162814 |
Construction | Splice 02/04/19-trusses | A | 2/26/2019 | SHELLEY | SHELLEY | TRUSSES | | Construction | 1162813 |
Construction | Splice 02/04/19-trusses | / | 2/26/2019 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1162785 |
Construction | Splice 02/04/19-trusses | / | 2/26/2019 | | GITA | Location = Construction by GITA | | Construction | 1162749 |
Resubmittal 1 | Splice 02/04/19-trusses | / | 2/26/2019 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1162748 |
Finished Bin | Splice 02/04/19-trusses | / | 2/5/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1156183 |
Plan Coordinator | Splice 02/04/19-trusses | / | 2/5/2019 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1156110 |
Construction | Splice 02/04/19-trusses | D | 2/5/2019 | SHELLEY | SHELLEY | Please follow trusses pending submittal procedures as indicated on plans; buildings should be structurally identical - clarify why there are different trusses for accessible buildings. No walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1156109 |
Construction | Splice 02/04/19-trusses | / | 2/5/2019 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1156087 |
Construction | Splice 02/04/19-trusses | / | 2/4/2019 | | GITA | Location = Construction by GITA | | Construction | 1155696 |
Electrical | Splice 8/15/18 | A | 8/15/2018 | SHELBY | SHELBY | | | Electrical | 1100280 |
Construction | Splice 8/15/18 | A | 8/15/2018 | SHELLEY | SHELLEY | Structural and section details | | Construction | 1100257 |
Out to Review | Original | / | 2/15/2018 | NELIDA | NELIDA | Ride along with Joel - plumbing | | Out to Review | 1038161 |
Scanned/Finished Bin | Original | / | 2/14/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1037654 |
To Be Scanned Bin | Original | / | 2/14/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1037444 |
City Engr | Original | A | 2/13/2018 | CSENGINEER | CSENGINEER | Walk through approval. jad | csengineer | City Engr | 1037384 |
CSU Contract Admin. | Original | A | 2/13/2018 | CSUAPPSPRM | CSUAPPSPRM | Development charges/fees paid. LMP | lmpope | CSU Contract Admin. | 1037302 |
Health Dept. | Original | A | 2/13/2018 | HEALTHDEPT | HEALTHDEPT | Construction Activity Permit PT0040443 is valid from 2/15/18-8/15/18. Danielle Hannaly-Gentle, 719-575-8426 | abrannon | Health Dept. | 1037241 |
Out to Review | Original | / | 2/13/2018 | NELIDA | NELIDA | Emery 520-907-2807 | | Out to Review | 1037117 |
Finished Bin | Original | / | 1/17/2018 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 1029279 |
Construction | Original | A | 1/17/2018 | BPHILLIPS | BPHILLIPS | revised site plan, draft stop attic access door details | | Construction | 1029260 |
CSU Contract Admin. | Original | D | 1/17/2018 | CSUAPPSPRM | CSUAPPSPRM | CWMSF Approved. Requires Payment of Development Charges and Fees.ZJS | zshearer | CSU Contract Admin. | 1029029 |
Out to Review | Original | / | 1/11/2018 | RITA | RITA | Jessica 473-8400 | | Out to Review | 1027905 |
Finished Bin | Original | / | 12/14/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1021552 |
Health Dept. | Original | D | 12/14/2017 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required for > 1 acre. Contact 578-3199 option #3. AB 352-1842 | abrannon | Health Dept. | 1021534 |
Health Dept. | Original | / | 12/12/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1020651 |
City Engr | Original | D | 12/12/2017 | CSENGINEER | CSENGINEER | Include a copy of the Water Resources Engineering Division approved Grading & Erosion Control Plan in the building permit set. Plan set route to RBD. pvm | csengineer | City Engr | 1020631 |
City Engr | Original | / | 12/12/2017 | | CSFIRE | Location = City Engr by CSFIRE | fdjah74 | City Engr | 1020495 |
CO Springs Fire | Original | A | 12/12/2017 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A CSFD plan review fee is $497.20 per building. (see full review) | csfdit | CO Springs Fire | 1020492 |
Water Division | Original | A | 12/6/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Water Division | 1019290 |
Waste Water Div | Original | A | 12/6/2017 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Waste Water Div | 1019289 |
Out to Review | Original | / | 9/6/2017 | RITA | RITA | Jessica 719-473-8400 | | Out to Review | 993297 |
Finished Bin | Original | / | 8/22/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 989139 |
Plan Coordinator | Original | / | 8/22/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 989130 |
Mechanical | Original | A | 8/22/2017 | DALEH | DALEH | | | Mechanical | 989129 |
Mechanical | Original | / | 8/22/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 989085 |
Mechanical | Original | / | 8/22/2017 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 989042 |
Resubmittal 2 | Original | / | 8/22/2017 | MINDY | MINDY | Resubmittal #2 Mechanical only | | Resubmittal 2 | 989041 |
Construction | Original | A | 8/11/2017 | MICHAELA | MICHAELA | | | Construction | 986169 |
Out to Review | Original | / | 8/11/2017 | | CSUAPPSPRM | Location = Out to Review by CSUAPPSPRM | zshearer | Out to Review | 986155 |
CSU Contract Admin. | Original | / | 8/10/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 985478 |
Plan Coordinator | Original | / | 8/10/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 985462 |
Mechanical | Original | D | 8/10/2017 | DALEH | DALEH | options not allowed remove sheet notes that don't apply to the sheet their on see comments needed on plan in regards to rated assemblies and penetration protection return all green line comments
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 985458 |
Mechanical | Original | / | 8/8/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 984849 |
Mechanical | Original | / | 8/7/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 984340 |
Plan Coordinator | Original | / | 8/7/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 984330 |
Construction | Original | D | 8/7/2017 | SHELLEY | SHELLEY | Detail 3/A23 is referenced as a detail for the fire barrier at the exit enclosure on A19 - detail must show how fire barrier continuity is being maintained, or correct reference. See plans; walk oik. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 984329 |
Construction | Original | / | 8/7/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 984305 |
Construction | Original | / | 8/7/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 984304 |
Resubmittal 1 | Original | / | 8/4/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 984078 |
Electrical | Original | A | 8/4/2017 | SHELBY | SHELBY | | | Electrical | 984064 |
Enumeration | Original | A | 8/2/2017 | BRENT | BRENT | Final plat has been recorded. Secondary addressing has been corrected. | | Enumeration | 983385 |
Plumbing | Original | A | 8/2/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 983375 |
Out to Review | Original | / | 7/7/2017 | GITA | GITA | 719-473-8400 By jessica | | Out to Review | 976069 |
Finished Bin | Original | / | 7/7/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 976055 |
Health Dept. | Original | D | 7/7/2017 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required. Contact 578-3199 option #3 for more information regarding construction activity permits. GA 578-3295 | galvarez | Health Dept. | 976040 |
Health Dept. | Original | / | 7/3/2017 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 975096 |
Hazmat | Original | N | 7/3/2017 | SCANNING | SCANNING | 07/03/2017 DEW | | Hazmat | 975095 |
City Engr | Original | D | 7/3/2017 | CSENGINEER | CSENGINEER | Include a copy of the City Engineering approved Grading & Erosion Control Plan in the building permit set. Plan set routed to RBD. jad | csengineer | City Engr | 975078 |
CO Springs Fire | Original | D | 7/3/2017 | CSFIRE | CSFIRE | Submitted By: Withee, Doreen E (see full review) | csfdit | CO Springs Fire | 975058 |
Water Division | Original | D | 6/29/2017 | CSUREVIEW | CSUREVIEW | Requires approved CSU mainline Construction Plans and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. CQ | cquinn_ds | Water Division | 974088 |
Waste Water Div | Original | D | 6/29/2017 | CSUREVIEW | CSUREVIEW | Requires approved CSU mainline Construction Plans and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. CQ | cquinn_ds | Waste Water Div | 974085 |
Gas/Elec. Utils | Original | A | 6/29/2017 | CSUREVIEW | CSUREVIEW | CQ | cquinn_ds | Gas/Elec. Utils | 974084 |
Fire | Original | / | 6/29/2017 | | CSUREVIEW | Location = Fire by CSUREVIEW | hfranson | Fire | 974076 |
CO Springs DRE | Original | A | 6/29/2017 | HVANNIMWEGEN | HVANNIMWEGEN | Final Landscape and Final Irrigation Plans due 30-days after building permit issuance. Contact Connie Perry to set up a submittal meeting 719-385-5375 (see full review) | | CO Springs DRE | 974069 |
CSU Utilities | Original | / | 6/28/2017 | | CSUAPPSPRM | Location = CSU Utilities by CSUAPPSPRM | Benglish | CSU Utilities | 973692 |
CSU Contract Admin. | Original | D | 6/28/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires an approved Commercial Water Meter Sizing Form (CWMSF) for each building/address and payment of applicable utility charges and fees. Final calculation of any applicable water and/or wastewater recovery fees and payment is subject to review and verification of lot acreage on the final recorded plat.
Please contact Utilities Development Services at 719-668-8111 for questions, assistance or to request an estimate.
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf
Plan taken to Water/Wastewater/Gas/Elec (CSU Utilities) for review. BTE | Benglish | CSU Contract Admin. | 973689 |
CSU Contract Admin. | Original | / | 6/27/2017 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 972960 |
Plan Coordinator | Original | / | 6/27/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 972951 |
Mechanical | Original | D | 6/27/2017 | DALEH | DALEH | darken up backgrounds slightly increase font size see plans for all red lines return red lines incomplete review at this time no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 972950 |
Mechanical | Original | / | 6/27/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 972933 |
Mechanical | Original | / | 6/26/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 972557 |
Plan Coordinator | Original | / | 6/26/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 972533 |
Electrical | Original | D | 6/26/2017 | SHELBY | SHELBY | 1. Label all accessible units per chapter 10 ANSI 117.1 . 2. For common GEC show compliance or methodology for complying with 250.64 (D) NEC NOTE Two plans in this series 98183, and 98184 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 972524 |
Electrical | Original | / | 6/23/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 972398 |
Plumbing | Original | D | 6/20/2017 | TCRIPPEN | TCRIPPEN | provide an water pipe size analysis data on plans show H.C. units on plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 970727 |
Electrical | Original | / | 6/20/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 970616 |
Plan Coordinator | Original | / | 6/20/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 970601 |
Construction | Original | D | 6/20/2017 | SHELLEY | SHELLEY | Rescheck required - missing slab on grade; specify systems for L528 and L516; show imaginary property lines between buildings and compliance for fire separation distance and exterior wall openings; stairs are exit enclosures and must have 2-sided assemblies; provide proper fire barrier continuity; clear floor spaces for laundry appliances must be centered on each appliance; lavatory cannot be in clear space for tub in Type A units, and water closet requires 66" with sink encroachment; show exterior wall continuity through floor cavity; show proper termination of rating at balcony floor; see plans for all comments; no walk TRUSSES PENDING
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 970599 |
Construction | Original | / | 6/19/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 970266 |
Construction | Original | / | 6/15/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 969735 |
Out to Review | Original | / | 6/15/2017 | AMY | AMY | | | Out to Review | 969723 |
Enumeration | Original | D | 6/15/2017 | AMY | AMY | SITE PLAN SHOWING ALL ADDRESSING TO 10 APT BUILDINGS PAGE-SP1 OF 2.
3-TRASH ENCLOSURES-FENCING AT 6FT NO PERMIT OR ADDRESS REQUIRED.
SECONDARY ADDRESSING PAGE-GENERAL 1.
MONUMENT SIGN REFERENCE CAN BE CROSSED OFF-SEPARATE PLAN & PERMIT REQUIRED.
ENUMERATIONS WILL REVIEW THE MYLAR PRIOR TO PLAT FOR ADDRESS PLACEMENT, STREET NAME, TITLE BLOCK AND FLOODPLAIN STATEMENT. $10.00 PER LOT & TRACT FEE DUE AT THE TIME OF THE REVIEW OF THE MYLAR. CHECK SHOULD BE MADE OUT TO REGIONAL BUILDING DEPT. A COPY OF THE FINAL RECORDED PLAT IS REQUIRED PRIOR TO APPROVAL IN THIS DEPARTMENT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 969722 |
Floodplain | Original | N | 6/15/2017 | AMY | AMY | ONCE PLATTED THERE IS NO FLOODPLAIN ON THIS LOT. | | Floodplain | 969714 |
Enumeration | Original | / | 6/15/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 969711 |