Finished Bin | Original | / | 7/26/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 981114 |
Plan Coordinator | Original | / | 7/26/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 981088 |
Electrical | Original | A | 7/26/2017 | SHELBY | SHELBY | | | Electrical | 981087 |
Finished Bin | Original | / | 7/25/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Finished Bin | 980717 |
Finished Bin | Original | / | 7/14/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 977998 |
Water Division | Original | N | 7/11/2017 | CSUREVIEW | CSUREVIEW | mjg 7/11/17 | mgackle | Water Division | 976891 |
Waste Water Div | Original | N | 7/11/2017 | CSUREVIEW | CSUREVIEW | mjg 7/11/17 | mgackle | Waste Water Div | 976890 |
CSU Utilities | Original | / | 7/7/2017 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 976142 |
Hazmat | Original | N | 7/7/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 976141 |
CO Springs Fire | Original | N | 7/7/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L | csfdit | CO Springs Fire | 976140 |
Fire | Original | / | 7/3/2017 | | GSANDERS | Location = Fire by GSANDERS | | Fire | 974861 |
CO Springs DRE | Original | D | 7/3/2017 | GSANDERS | GSANDERS | Antenna is larger than 4 square feet and ground equipment is proposed. Please set up a pre-application meeting to discuss a CMRS application. https://coloradosprings.gov/planning/webform/pre-application-meeting-request (see full review) | | CO Springs DRE | 974860 |
Zoning/Planning | Original | / | 6/29/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 974033 |
Plumbing | Original | N | 6/29/2017 | DALEH | DALEH | | | Plumbing | 974014 |
Plan Coordinator | Original | / | 6/29/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 974004 |
Mechanical | Original | N | 6/29/2017 | DALEH | DALEH | | | Mechanical | 974003 |
Mechanical | Original | / | 6/29/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 973998 |
Mechanical | Original | / | 6/29/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 973952 |
Plan Coordinator | Original | / | 6/28/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 973942 |
Electrical | Original | D | 6/28/2017 | SHELBY | SHELBY | Please supply fault current and load calculations for the present installation ( this plan references core and shell/existing drawings which may or may not coincide with present day conditions). NOTE Five plans in this series 98469, 98470, 98471,98472, 98474 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 973939 |
Electrical | Original | / | 6/27/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 973267 |
Plan Coordinator | Original | / | 6/27/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 973253 |
Construction | Original | N | 6/27/2017 | SHELLEY | SHELLEY | No construction work | | Construction | 973252 |
Construction | Original | / | 6/27/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 973237 |
Construction | Original | / | 6/27/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 972987 |
Plan Coordinator | Original | / | 6/27/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 972949 |
Enumeration | Original | A | 6/27/2017 | BRENT | BRENT | Equipment to be mounted to building and utilitze existing electric service so no separate address is required. | | Enumeration | 972948 |
Floodplain | Original | N | 6/27/2017 | BRENT | BRENT | Floodplain on parcel, not near area of work. | | Floodplain | 972947 |