CO Springs DRE | Original | A | 7/12/2018 | SDALSING | SDALSING | Approved for addition per AR DO 97-00576-MM01 (see full review) | | CO Springs DRE | 1088947 |
Electrical | Original | A | 7/11/2018 | SHELBY | SHELBY | | | Electrical | 1088206 |
Mechanical | Original | A | 7/9/2018 | JUSTINC | JUSTINC | | | Mechanical | 1087470 |
Zoning/Planning | Original | / | 7/9/2018 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1087336 |
Plumbing | Original | A | 7/9/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1087275 |
Electronic Plan | Original | / | 7/9/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1087268 |
Construction | Original | A | 7/9/2018 | MICHAELA | MICHAELA | | | Construction | 1087241 |
Enumeration | Original | A | 7/6/2018 | BRENT | BRENT | | | Enumeration | 1087138 |
Resubmittal 3 | Original | / | 7/6/2018 | SHELLEY | SHELLEY | Resubmittal #3 | | Resubmittal 3 | 1087061 |
CO Springs DRE | Original | A | 3/1/2018 | SDALSING | SDALSING | Approved for addition per AR DP 97-000576-MM01 (see full review) | | CO Springs DRE | 1042393 |
CO Springs Fire | Original | A | 3/1/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1042119 |
Electrical | Original | A | 2/27/2018 | SHELBY | SHELBY | New sheet E 1.5 | | Electrical | 1041493 |
Mechanical | Original | A | 2/27/2018 | JUSTINC | JUSTINC | | | Mechanical | 1041302 |
Zoning/Planning | Original | / | 2/26/2018 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1040977 |
Construction | Original | A | 2/26/2018 | MICHAELA | MICHAELA | | | Construction | 1040651 |
Enumeration | Original | A | 2/22/2018 | AMY | AMY | | | Enumeration | 1040013 |
Electronic Plan | Original | / | 2/22/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1040008 |
Resubmittal 2 | Original | / | 2/22/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1039987 |
Hazmat | Original | N | 1/24/2018 | CSFIRE | CSFIRE | Hazmat N/A. Chemicals are existing and are not affected by scope of work. (see full review) | smanning | Hazmat | 1031200 |
CO Springs DRE | Original | D | 1/22/2018 | SDALSING | SDALSING | Exterior work needs to be approved through a minor mod to the development plan. (see full review) | | CO Springs DRE | 1030724 |
CO Springs Fire | Original | D | 1/22/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1030596 |
Mechanical | Original | D | 1/19/2018 | JUSTINC | JUSTINC | Indicate on plan how protecting penetrations through rated assembilies. See plan Provide refrigeration calculation for CRAC unit Verify ventilation of locker rooms in ventilation schedule
SEE PLAN FOR ALL COMMENTS
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1030094 |
Electronic Plan | Original | / | 1/18/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1029857 |
Zoning/Planning | Original | / | 1/17/2018 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1029300 |
Plumbing | Original | A | 1/17/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1029289 |
Electronic Plan | Original | / | 1/17/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1029159 |
Electrical | Original | A | 1/17/2018 | SHELBY | SHELBY | | | Electrical | 1029112 |
Construction | Original | D | 1/17/2018 | MICHAELA | MICHAELA | Provide a listed assembly for wall type PN or an IBC item # Doors in series are not compliant Showers at new toilet rooms must be 50% accessible.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1029011 |
Electronic Plan | Original | / | 1/11/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1027799 |
Enumeration | Original | A | 1/10/2018 | AMY | AMY | | | Enumeration | 1027737 |
Electronic Plan | Original | / | 1/10/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1027736 |
Resubmittal 1 | Original | / | 1/10/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1027581 |
Canceled Plans | Original | / | 1/3/2018 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 1025358 |
Mechanical | Original | D | 8/5/2017 | JUSTINC | JUSTINC | Wall ratings have not been reviewed.Pending construction reviewer comments. Multiple locations require clarification of how providing makeup air. Multiple locations require clarification of how providing a return air path. Indicate on range hood that range will be for warming purposes only. Or indicate how complying with 09' IMC 506. Provide refrigeration calculation per 09' IMC 1103.1 for CRAC-1.
REVIEW INCOMPLETE
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 984132 |
Hazmat | Original | D | 8/3/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 983722 |
CO Springs Fire | Original | D | 8/3/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 983721 |
Water Division | Original | N | 7/28/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Water Division | 982136 |
Waste Water Div | Original | N | 7/28/2017 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Waste Water Div | 982134 |
Electrical | Original | D | 7/28/2017 | SHELBY | SHELBY | 1. For new luminaires in pool area indicate horizontal distance from the inside wall of the pool and height of luminaires above maximum water level of the pool. See E 2.1. 2. Provide complete one line showing all conductor size, type, and ,quantities. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 982083 |
Plumbing | Original | D | 7/27/2017 | TCRIPPEN | TCRIPPEN | missing notes on pages drinking fountain shall not be in the restrooms (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 981879 |
CO Springs DRE | Original | D | 7/27/2017 | SDALSING | SDALSING | Exterior work needs to be approved through a minor modification or minor amendment to the development plan. Please see email for further details. Susanna Dalsing 719-385-5080 (see full review) | | CO Springs DRE | 981650 |
Electronic Plan | Original | / | 7/25/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 980997 |
Zoning/Planning | Original | / | 7/25/2017 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 980990 |
Construction | Original | D | 7/25/2017 | MICHAELA | MICHAELA | See plan (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 980957 |
Electronic Plan | Original | / | 7/21/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 980068 |
Enumeration | Original | A | 7/19/2017 | AMY | AMY | | | Enumeration | 979266 |
Electronic Plan | Original | / | 7/19/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 979244 |
Floodplain | Original | N | 7/7/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 975881 |
Floodplain | Original | N | 7/7/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 975882 |