Enumeration | Original | D | 11/12/2019 | AMY | AMY | Spoke with Phillip regarding new suite spaces in the building that will affect this address. Plan need to be corrected to what Phillip discussed with Amy in Enumerations regarding separation of space and new address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1255669 |
Out to Review | Original | / | 8/6/2018 | RITA | RITA | Mike | | Out to Review | 1097160 |
Finished Bin | Original | / | 7/18/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1091020 |
Hazmat | Original | D | 7/17/2018 | CSFIRE | CSFIRE | Hazmat disapproved. Please read disapproved comments. Plansforwarded to RBD. (see full review) | smanning | Hazmat | 1090434 |
Construction | Original | A | 7/6/2018 | BPHILLIPS | BPHILLIPS | | | Construction | 1086910 |
Out to Review | Original | / | 4/3/2018 | RITA | RITA | Mike | | Out to Review | 1053409 |
Finished Bin | Original | / | 4/2/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1053013 |
Water Division | Original | D | 4/2/2018 | CSUREVIEW | CSUREVIEW | Need to provide a Backflow Assembly Plan Review Form. It can be found at https://www.csu.org/CSUDocuments/backflowdomesticform.pdf. An approved reduced pressure backflow device is required, and must be provided if not already existing. Please contact Holly Link at 719-668-4733 or Chelsa Shull at 719-668-8755 to discuss proper backflow requirements. JPN | jnoble | Water Division | 1052968 |
Waste Water Div | Original | N | 4/2/2018 | CSUREVIEW | CSUREVIEW | No utility work proposed outside the building. JPN | jnoble | Waste Water Div | 1052967 |
CSU Utilities | Original | / | 3/29/2018 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 1052082 |
Hazmat | Original | D | 3/29/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1052081 |
CO Springs Fire | Original | D | 3/29/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1052080 |
CO Springs DRE | Original | A | 3/28/2018 | RDCUSER | RDCUSER | INTERIOR REMODEL/CHANGE OF OCC. CBD OIL EXTRACTION - THIS IS CLASSIFIED AS MANUFACTURING AND IS ALLOWED WITHIN THE PIP2 ZONE DISTRICT. SRD PER MGM. PRE APP NUMBER 17-095 (see full review) | | CO Springs DRE | 1051535 |
Fire | Original | / | 3/26/2018 | | SDALSING | Location = Fire by SDALSING | | Fire | 1050574 |
CO Springs DRE | Original | D | 3/26/2018 | SDALSING | SDALSING | Please highlight scope of work SRD per MGM (see full review) | | CO Springs DRE | 1050573 |
Zoning/Planning | Original | / | 3/16/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1047934 |
Plan Coordinator | Original | / | 3/16/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1047814 |
Mechanical | Original | D | 3/16/2018 | DALEH | DALEH | see blue lines for comments return blue lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1047813 |
Mechanical | Original | / | 3/16/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1047769 |
Mechanical | Original | / | 3/14/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1047118 |
Plan Coordinator | Original | / | 3/14/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1047047 |
Electrical | Original | D | 3/14/2018 | BERTHA | BERTHA | 1. Clarify system voltage. 2. Homogenize panel name on one-line, panel schedule and floor plan. 3. Provide a single one-line diagram. There are two with this set. 4. Clarify scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1047046 |
Electrical | Original | / | 3/14/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1046994 |
Electrical | Original | / | 3/9/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1045197 |
Plan Coordinator | Original | / | 3/9/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1045163 |
Construction | Original | D | 3/9/2018 | MICHAELA | MICHAELA | Shoe sink and dishwasher on architectural pages - must be ANSI compliant Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1045162 |
Out to Review | Original | / | 3/9/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Out to Review | 1045159 |
Resubmittal 2 | Original | / | 3/8/2018 | MATTHEWM | MATTHEWM | Resubmittal #2 | | Resubmittal 2 | 1044935 |
Electrical | Original | A | 8/25/2017 | BERTHA | BERTHA | | | Electrical | 990260 |
Out to Review | Original | / | 8/14/2017 | | CSFIRE | Location = Out to Review by CSFIRE | rpeterson | Out to Review | 986430 |
Fire | Original | / | 8/10/2017 | | SDALSING | Location = Fire by SDALSING | | Fire | 985669 |
CO Springs DRE | Original | D | 8/10/2017 | SDALSING | SDALSING | Please fill out pre-application form to further discuss this proposal and a potential conditional use. (see full review) | | CO Springs DRE | 985668 |
Zoning/Planning | Original | / | 8/7/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 984363 |
Plan Coordinator | Original | / | 8/7/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 984358 |
Plumbing | Original | A | 8/7/2017 | TCRIPPEN | TCRIPPEN | okay, | | Plumbing | 984357 |
Plumbing | Original | / | 8/3/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 983642 |
Plan Coordinator | Original | / | 8/3/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 983617 |
Mechanical | Original | D | 8/3/2017 | DALEH | DALEH | previous comment not addressed please respond and resubmit (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 983616 |
Mechanical | Original | / | 8/3/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 983526 |
Mechanical | Original | / | 8/2/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 983338 |
Plan Coordinator | Original | / | 8/2/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 983284 |
Electrical | Original | D | 8/2/2017 | BERTHA | BERTHA | 1. Homogenize panel name on floor plan, panel schedule and one-line diagram. 2. Provide load for both sections of 2 section panel 3. Clarify 4880V switchboard.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 983283 |
Electrical | Original | / | 8/1/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 982937 |
Electrical | Original | / | 7/31/2017 | | JESSICAM | Location = Electrical by JESSICAM | | Electrical | 982639 |
Plan Coordinator | Original | / | 7/31/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 982614 |
Construction | Original | A | 7/31/2017 | MICHAELA | MICHAELA | | | Construction | 982613 |
Construction | Original | / | 7/31/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 982596 |
Construction | Original | / | 7/31/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 982472 |
Resubmittal 1 | Original | / | 7/31/2017 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 982470 |
Zoning/Planning | Original | / | 7/26/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 981275 |
Plan Coordinator | Original | / | 7/26/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 981257 |
Plumbing | Original | D | 7/26/2017 | TCRIPPEN | TCRIPPEN | plan reads new sink,vent and hot water heater provide a plumbing sheet all so restrooms on plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 981256 |
Plumbing | Original | / | 7/25/2017 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 980956 |
Out to Review | Original | / | 7/25/2017 | MINDY | MINDY | Mike Morley | | Out to Review | 980943 |
Plumbing | Original | / | 7/25/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 980914 |
Plan Coordinator | Original | / | 7/25/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 980873 |
Mechanical | Original | D | 7/25/2017 | DALEH | DALEH | provide a complete set of mechanical drawings (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 980871 |
Mechanical | Original | / | 7/25/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 980847 |
Mechanical | Original | / | 7/24/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 980479 |
Plan Coordinator | Original | / | 7/24/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 980451 |
Electrical | Original | D | 7/24/2017 | BERTHA | BERTHA | Provide electrical. Indicate compliance with 210.8 NEC and ANSI 117.1.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 980450 |
Electrical | Original | / | 7/20/2017 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 979721 |
Electrical | Original | / | 7/17/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 978444 |
Plan Coordinator | Original | / | 7/17/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 978421 |
Construction | Original | D | 7/17/2017 | MICHAELA | MICHAELA | Code Study says separated use Provide sum of ratios, etc. Walk-through with Michael only (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 978420 |
Construction | Original | / | 7/17/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 978362 |
Construction | Original | / | 7/14/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 977938 |
Plan Coordinator | Original | / | 7/14/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 977915 |
Enumeration | Original | A | 7/14/2017 | BRENT | BRENT | | | Enumeration | 977914 |
Floodplain | Original | N | 7/12/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 977261 |