Canceled Plans | Original | / | 5/3/2018 | | MINDY | Location = Canceled Plans by MINDY | | Canceled Plans | 1064217 |
Finished Bin | Original | / | 8/23/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 989522 |
CO Springs DRE | Original | D | 8/23/2017 | MBINGMAN | MBINGMAN | Minor modification submittal required. (see full review) | | CO Springs DRE | 989478 |
Hazmat | Original | A | 8/22/2017 | CSFIRE | CSFIRE | Plans approved. Fees of $396 are to be paid through Division of the Fire Marshal, 375 Printers Parkway. Forwarded to RBD. (see full review) | smanning | Hazmat | 989067 |
Hazmat | Original | / | 8/16/2017 | | CSFIRE | Location = Hazmat by CSFIRE | wtaylor | Hazmat | 987317 |
CO Springs Fire | Original | N | 8/16/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 987316 |
Electrical | Original | A | 8/16/2017 | BERTHA | BERTHA | | | Electrical | 987306 |
Construction | Original | N | 8/16/2017 | JAY | JAY | N/A | | Construction | 987294 |
Enumeration | Original | A | 8/16/2017 | AMY | AMY | | | Enumeration | 987293 |
Mechanical | Original | N | 8/16/2017 | TCRIPPEN | TCRIPPEN | no mechanical work issue no permit | | Mechanical | 987248 |
Plumbing | Original | N | 8/16/2017 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit, water and waste water removed not required | | Plumbing | 987247 |
Out to Review | Original | / | 8/15/2017 | BERTHA | BERTHA | Vince walking. | | Out to Review | 986891 |
Electrical | Original | D | 8/15/2017 | BERTHA | BERTHA | 1. Provide KVA rating of generator. 2. Provide Panel R2B schedule/load calc. 3. Provide compliance with 517.13 for new home runs in scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 986890 |
Floodplain | Original | N | 8/15/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 986846 |