- Not Set - | Original | / | 7/9/2019 | SCANNING | SCANNING | Location : EXPIRED LG PLANS BIN: 7/9/19 by JLANE Plans are over 180 days old. They will be disposed of if not picked up by 7/19/19 Friday. Electronic approved copy will still be available | | - Not Set - | 1210593 |
Scanned/Finished Bin | Original | / | 9/17/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1110524 |
To Be Scanned Bin | Original | / | 9/13/2018 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1109853 |
Out to Review | Original | / | 9/13/2018 | PMORRIS | PMORRIS | | | Out to Review | 1109814 |
City Engr | Original | A | 9/13/2018 | PMORRIS | PMORRIS | | | City Engr | 1109812 |
CO Springs Fire | Original | A | 9/10/2018 | CSFIRE | CSFIRE | Fee is per address. | rpeterson | CO Springs Fire | 1108313 |
Gas/Elec. Utils | Original | A | 9/10/2018 | CSUREVIEW | CSUREVIEW | All comments addressed AJ 9/10/18 | ajuvera | Gas/Elec. Utils | 1108110 |
Water Division | Original | A | 9/10/2018 | CSUREVIEW | CSUREVIEW | All comments addressed AJ 9/10/18 | ajuvera | Water Division | 1108109 |
Waste Water Div | Original | A | 9/10/2018 | CSUREVIEW | CSUREVIEW | All comments addressed AJ 9/10/18 | ajuvera | Waste Water Div | 1108108 |
Fire | Original | / | 8/15/2018 | | SCANNING | Location = Fire by SCANNING | | Fire | 1100083 |
Plan Coordinator | Original | / | 8/15/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1100032 |
Mechanical | Original | A | 8/15/2018 | DALEH | DALEH | | | Mechanical | 1100030 |
Mechanical | Original | / | 8/15/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1099989 |
Mechanical | Original | / | 8/13/2018 | | MATTHEWM | Location = Mechanical by MATTHEWM | | Mechanical | 1099452 |
Resubmittal 4 | Original | / | 8/13/2018 | MATTHEWM | MATTHEWM | Resubmittal #4 | | Resubmittal 4 | 1099451 |
Out to Review | Original | / | 8/10/2018 | JANE | JANE | mike 719 313 7612 | | Out to Review | 1099015 |
Finished Bin | Original | / | 8/10/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1098890 |
Plan Coordinator | Original | / | 8/10/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1098733 |
Mechanical | Original | D | 8/10/2018 | DALEH | DALEH | need lower level manual d showing furnace location provide separate equipment certificates one for 80% and one for 93% all sheets need to indicate the address need the equipment spec sheets for the 80% equipment sheet M1 shows friction loss at .19 and spec sheets are circled at .17 designer needs to evaluate the entire submittal for accuracy prior to resubmitting no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1098732 |
Mechanical | Original | / | 8/3/2018 | | RITA | Location = Mechanical by RITA | | Mechanical | 1096738 |
Out to Review | Original | / | 8/2/2018 | | CSFIRE | Location = Out to Review by CSFIRE | rpeterson | Out to Review | 1096075 |
CO Springs Fire | Original | D | 8/2/2018 | CSFIRE | CSFIRE | Mike Fenton 719-492-3227 | rpeterson | CO Springs Fire | 1096073 |
CSU Utilities | Original | / | 8/2/2018 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 1096014 |
CO Springs Fire | Original | D | 8/2/2018 | CSFIRE | CSFIRE | | wtaylor | CO Springs Fire | 1096013 |
Fire | Original | / | 7/27/2018 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1094064 |
CO Springs DRE | Original | A | 7/27/2018 | RDCUSER | RDCUSER | (see full review) | | CO Springs DRE | 1094063 |
Zoning/Planning | Original | / | 7/23/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1092287 |
Plan Coordinator | Original | / | 7/23/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1092225 |
Enumeration | Original | A | 7/23/2018 | AMY | AMY | RECEIVED COPY OF THE FINAL PLAT | | Enumeration | 1092224 |
Enumeration | Original | / | 7/23/2018 | | SCANNING | Location = Enumeration by SCANNING | | Enumeration | 1092211 |
Plan Coordinator | Original | / | 7/23/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1092114 |
Mechanical | Original | D | 7/23/2018 | DALEH | DALEH | why does 960 inner unit show 44K furnace and there are no 44K furnaces shown on duct design ? why do the calcs show duct losses ..none of the ducts are outside the buildings thermal envelope ? why such a large discrepancy in heat calcs between 950 inner and 960 inner ? 960 inner unit calcs show no O.S.A., but shown on duct design ? need to indicate on heat calcs end units not just with a sticky note. 960 inner unit shows 737 BTU loss for humidification and 950 unit shows 4,109 BTU loss ???????? designer to evaluate submittal and resubmit no walk
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1092113 |
Mechanical | Original | / | 7/23/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1092080 |
Plumbing | Original | A | 7/23/2018 | TCRIPPEN | TCRIPPEN | Living areas are not reviewed but must comply with currently adopted codes | | Plumbing | 1092051 |
Mechanical | Original | / | 7/20/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1091806 |
Plan Coordinator | Original | / | 7/20/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1091754 |
Electrical | Original | A | 7/20/2018 | SHELBY | SHELBY | | | Electrical | 1091751 |
Electrical | Original | / | 7/20/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1091722 |
Electrical | Original | / | 7/20/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1091567 |
Plan Coordinator | Original | / | 7/20/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1091515 |
Construction | Original | A | 7/20/2018 | DANM | DANM | | | Construction | 1091514 |
Construction | Original | / | 7/18/2018 | | GITA | Location = Construction by GITA | | Construction | 1090947 |
Resubmittal 3 | Original | / | 7/18/2018 | GITA | GITA | Resubmittal #3 | | Resubmittal 3 | 1090946 |
Out to Review | Original | / | 6/27/2018 | RITA | RITA | Mike 719-645-8970 | | Out to Review | 1084133 |
Finished Bin | Original | / | 6/27/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1084048 |
Plumbing | Original | / | 6/27/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1084041 |
Plan Coordinator | Original | / | 6/27/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1084038 |
Enumeration | Original | D | 6/27/2018 | AMY | AMY | Plat pending (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1084036 |
Enumeration | Original | / | 6/27/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1084022 |
Enumeration | Original | / | 6/26/2018 | | SCANNING | Location = Enumeration by SCANNING | | Enumeration | 1083924 |
Plan Coordinator | Original | / | 6/26/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1083891 |
Mechanical | Original | D | 6/26/2018 | DALEH | DALEH | provide interior unit calcs and duct design see red line on equipment certificate for clarification no further review no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1083889 |
Mechanical | Original | / | 6/25/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1083058 |
Plan Coordinator | Original | / | 6/22/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1083028 |
Electrical | Original | D | 6/22/2018 | SHELBY | SHELBY | Please address previous review comments 1 and 2. For comment 1 Electrical meters are shown electrical panels are not. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1083027 |
Electrical | Original | / | 6/20/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1081835 |
Plan Coordinator | Original | / | 6/20/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1081818 |
Construction | Original | D | 6/20/2018 | DANM | DANM | Various redlines not addressed from first review - carefully review all sheets and address all redlines All accessibility details on Sheet A0.23 should reference and reflect ICC/ANSI A117.1 - 2003 Specify location of fire rating detail B - if not being used, remove from submittal Detail marker D on building sections do not seem to match the actual detail Clarify how vertical continuity is being addressed on Detail 7/A0.45 Sheet A0.50 - Include addresses for all units; clearly identify accessible units Window type B does not seem to meet 5.7 sf clear opening requirement 31 3/4" clear width required at powder room doors No walk-through review allowed (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1081817 |
Construction | Original | / | 6/20/2018 | DANM | DANM | In Current Review by DANM | | Construction | 1081677 |
Construction | Original | / | 6/20/2018 | | JANE | Location = Construction by JANE | | Construction | 1081599 |
Resubmittal 2 | Original | / | 6/20/2018 | JANE | JANE | Resubmittal #2 rbd departments only | | Resubmittal 2 | 1081598 |
Finished Bin | Original | / | 6/15/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1080299 |
Fire | Original | / | 6/15/2018 | | CSUAPPSPRM | Location = Fire by CSUAPPSPRM | lmpope | Fire | 1080254 |
CSU Contract Admin. | Original | N | 6/15/2018 | CSUAPPSPRM | CSUAPPSPRM | Payment of development charges/fees due at building permit. LMP | lmpope | CSU Contract Admin. | 1080249 |
CSU Contract Admin. | Original | / | 6/15/2018 | | CSUREVIEW | Location = CSU Contract Admin. by CSUREVIEW | jnoble | CSU Contract Admin. | 1080207 |
Water Division | Original | D | 6/15/2018 | CSUREVIEW | CSUREVIEW | Requires approved CSU Mainline Construction Drawings and approved Utility Service Plan(USP). Contact Utilities Development Services at 719-668-8111 with questions. Once approved, provide a copy of the approved plans in the permit set. JPN | jnoble | Water Division | 1080203 |
Waste Water Div | Original | D | 6/15/2018 | CSUREVIEW | CSUREVIEW | Requires approved CSU Mainline Construction Drawings and approved Utility Service Plan(USP). Contact Utilities Development Services at 719-668-8111 with questions. Once approved, provide a copy of the approved plans in the permit set. JPN | jnoble | Waste Water Div | 1080202 |
Gas/Elec. Utils | Original | D | 6/15/2018 | CSUREVIEW | CSUREVIEW | The gas regulator vent must be at least 3ft away from any electric meter socket, ct cabinet (not including cables in riser pipe or gutter) and openings like windows, doors, and garage doors. Show and label gas and electric meter locations on the elevations. JPN | jnoble | Gas/Elec. Utils | 1080199 |
City Engr | Original | D | 6/14/2018 | CSENGINEER | CSENGINEER | Include a copy of the approved amended Development Plan and a copy of the Water Resources Engineering approved Grading & Erosion Control Plan in the building permit set. Plan set route to CSU Utilities. pvm | csengineer | City Engr | 1079711 |
Fire | Original | / | 6/4/2018 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 1075846 |
CO Springs DRE | Original | D | 6/4/2018 | RDCUSER | RDCUSER | Development Plan has not yet been approved - per MDS. (see full review) | | CO Springs DRE | 1075845 |
Zoning/Planning | Original | / | 6/4/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1075836 |
Plan Coordinator | Original | / | 6/4/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1075811 |
Plumbing | Original | D | 6/4/2018 | TCRIPPEN | TCRIPPEN | Plans to show separate utility's into each unit, show all meter locations on plans gas, water electric, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1075810 |
Plumbing | Original | / | 6/4/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1075803 |
Plumbing | Original | / | 6/4/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1075714 |
Plan Coordinator | Original | / | 6/4/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1075706 |
Mechanical | Original | D | 6/4/2018 | DALEH | DALEH | provide full size mechanical drawings no review no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1075705 |
Mechanical | Original | / | 6/4/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1075700 |
Mechanical | Original | / | 6/1/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1074982 |
Plan Coordinator | Original | / | 5/31/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1074961 |
Electrical | Original | D | 5/31/2018 | SHELBY | SHELBY | 1. Show location of Electrical meters, Service disconnects,and Electrical panels on floor plan ( Electrical panels may not be in rated walls). 2. Approval pending CRS data. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1074960 |
Electrical | Original | / | 5/31/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1074930 |
Electrical | Original | / | 5/31/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1074730 |
Plan Coordinator | Original | / | 5/31/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1074695 |
Construction | Original | D | 5/31/2018 | DANM | DANM | 'J' trusses are missing from the engineered truss package All accessibility details on Sheet A0.23 should be labeled Type B and should reflect Type B requirements Specify location of fire rating detail B - if not being used, remove from submittal Detail marker D on building sections do not seem to match the actual detail Clarify how vertical continuity is being addressed on Detail 7/A0.45 Sheet A0.50 - Clearly identify scope of work; clearly identify accessible units; provide dimensions between buildings; architectural site plan does not seem to match development plan and floor plans which show 4 uniform rectangles and only 3 buildings Detail 7/A2.01 toilet clearance should meet forward approach requirements Window type B does not seem to meet 5.7 sf clear opening requirement Provide typical stair section showing riser height, head room clearance, and handrail height 31 3/4" clear width required at powder room doors No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1074694 |
Construction | Original | / | 5/30/2018 | DANM | DANM | In Current Review by DANM | | Construction | 1073974 |
Construction | Original | / | 5/30/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1073944 |
Plan Coordinator | Original | / | 5/30/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1073878 |
Enumeration | Original | D | 5/30/2018 | AMY | AMY | Pending Final plat. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1073877 |
Enumeration | Original | / | 5/29/2018 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1073691 |
Resubmittal 1 | Original | / | 5/29/2018 | NELIDA | NELIDA | Resubmittal #1 5/29/18 | | Resubmittal 1 | 1073689 |
Out to Review | Original | / | 10/13/2017 | AMY | AMY | MIKE FENTON 247-9004 | | Out to Review | 1003829 |
Enumeration | Original | D | 10/13/2017 | AMY | AMY | TOTAL OF 3 BUILDINGS: 5512, 5518, 5524, 5530-1 BUILDING. 5542, 5548, 5554, 5560-1 BUILDING. 5572, 5578, 5584, 5590 STETTSON HILLS BLVD-1 BUILDING.
APPROVAL PENDING COPY OF THE FINAL RECORDED PLAT. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1003828 |
Out to Review | Original | / | 10/13/2017 | AMY | AMY | In Current Review by AMY | | Out to Review | 1003808 |
Health Dept. | Original | N | 10/10/2017 | HEALTHDEPT | HEALTHDEPT | Plan review is not needed - Not applicable. JZ 719-575-8966 | Jzimmerman | Health Dept. | 1002707 |
Out to Review | Original | / | 9/29/2017 | GITA | GITA | Mike picked up | | Out to Review | 1000058 |
Electrical | Original | / | 9/22/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 997769 |
Plan Coordinator | Original | / | 9/22/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 997750 |
Construction | Original | D | 9/22/2017 | DANM | DANM | All drawings are out of date by more than two years - resubmit new sheets for architectural and structural with current stamp and signature of design professionals Engineering for floor and roof trusses is out of date by more than two years - provide new truss engineering Remove architectural site plan for previous development and provide new site plan for entire new development showing C.R.S. calculations and identifying all accessible units No Accessibility Review Completed No Structural Review Completed No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 997749 |
Construction | Original | / | 9/21/2017 | DANM | DANM | In Current Review by DANM | | Construction | 997614 |
Construction | Original | / | 9/19/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 996742 |
Plan Coordinator | Original | / | 9/19/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 996724 |
Enumeration | Original | D | 9/19/2017 | BRENT | BRENT | Final plat has not yet been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. Tax schedule numbers and legal description to change after plat. On future submittals, highlight area of work on site plan and include the tax schedule number for each lot. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 996723 |
Floodplain | Original | N | 9/18/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 996453 |