Construction | Splice 03/10/21 | A | 3/11/2021 | SHELLEY | SHELLEY | Structural revisions - columns and beams | | Construction | 1469057 |
Construction | Splice 01/05/21 | A | 1/26/2021 | SHELLEY | SHELLEY | Architectural and structural details/revisions. | | Construction | 1445547 |
Resubmittal 1 | Splice 01/05/21 | / | 1/25/2021 | JAY | JAY | Resubmittal #1 | | Resubmittal 1 | 1445404 |
Construction | Splice 01/05/21 | D | 1/5/2021 | SHELLEY | SHELLEY | S2.2 missing stamp. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1434985 |
Construction | Splice 11/19/20 | A | 11/23/2020 | SHELLEY | SHELLEY | Revised accessibility matrix, garage and exterior cladding. | | Construction | 1417188 |
Construction | Splice 11/19/20 | D | 11/20/2020 | SHELLEY | SHELLEY | Remove old clouds and cloud changes only for this splice, Cloud changes on all pages. If a sheet doesn't have changes, remove it. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1416061 |
Floodplain | Original | A | 10/30/2020 | KEITH | KEITH | | | Floodplain | 1405705 |
Floodplain | Original | A | 10/30/2020 | KEITH | KEITH | | | Floodplain | 1405694 |
CO Springs DRE | Original | A | 8/27/2020 | MPFITZSIMMONS | MPFITZSIMMONS | DRE has already stamped this document. This is for Enumerations (see full review) | | CO Springs DRE | 1373629 |
Zoning/Planning | Original | / | 8/26/2020 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1373138 |
Floodplain | Original | D | 8/26/2020 | KEITH | KEITH | We need preliminary Elevation Certificates based on construction drawing for each individual building except 7. The following base Flood elevations (Box B9) established by CWCB should be used for each EC: Bldgs 1&4 5945.0, Bldgs 2&3 5946.7 Bldg 5 5946.0 Bldg 6 5943.8 Bldg 7 5942.0 Lowest Finished floor (box C2a) should be a minimum of 1 foot higher than BFE for each building. If Garage top of slab (box C2d) is less than one foot higher than BFE then flood vents must be specified and shown on the plans.
Street address (box A2) on each elevation certificate should be formatted as follows : (Building 1) 1776, 1770 Creek Edge View, (Building 2) 4,6,8,10 E St Elmo Ave, …Ect..
A total of 6 elevation certificates are required.
Also required is a water surface elevation comparison table pre vs post project to confirm that water surface elevations are not changing up or down more than 0.3 ft, if there are changes in excess of 0.3ft a LOMR will be required post project
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Floodplain | 1372924 |
Resubmittal 4 | Original | / | 8/25/2020 | JAY | JAY | Resubmittal #4 | | Resubmittal 4 | 1372652 |
CO Springs DRE | Original | A | 7/30/2020 | MPFITZSIMMONS | MPFITZSIMMONS | Approved Site plan included. (see full review) | | CO Springs DRE | 1357945 |
Zoning/Planning | Original | / | 7/28/2020 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1356667 |
Elevators | Original | A | 7/28/2020 | ERIC | ERIC | 2 In-line geared elevators by Morningstar | | Elevators | 1356054 |
Construction | Original | A | 7/28/2020 | SHELLEY | SHELLEY | | | Construction | 1355981 |
Enumeration | Original | A | 7/27/2020 | AMY | AMY | Building #5 addresses are incorrect 1771. 1765, 1759, & 1753 Creek Edge View | | Enumeration | 1355547 |
Electronic Plan | Original | / | 7/27/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1355542 |
Floodplain | Original | D | 7/24/2020 | KEITH | KEITH | we need preliminary Elevation Certificates based on construction drawing for all the buildings except 7.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Floodplain | 1355185 |
Resubmittal 3 | Original | / | 7/24/2020 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1354919 |
CO Springs DRE | Original | A | 7/22/2020 | MPFITZSIMMONS | MPFITZSIMMONS | Stamped planned attached (see full review) | | CO Springs DRE | 1353724 |
Zoning/Planning | Original | / | 7/20/2020 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1352625 |
Mechanical | Original | A | 7/20/2020 | JUSTINC | JUSTINC | | | Mechanical | 1352430 |
Electronic Plan | Original | / | 7/20/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1352398 |
Construction | Original | A | 7/20/2020 | SHELLEY | SHELLEY | | | Construction | 1352354 |
Floodplain | Original | D | 7/20/2020 | AMY | AMY | A copy of the final recorded plat is required. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Floodplain | 1352345 |
Enumeration | Original | D | 7/20/2020 | AMY | AMY | All of the pages that have the Cascade AVE address needs to be removed. The site plan file should have the site plan-not the development plan. On the site plan A1.1 label all of the surrounding sheets, include all the building addresses on the site plan and cloud area of work. Enumerations has not received a copy of the Final Recorded Plat. this is required prior to approval in Enumerations. The Mech.Duct and the IECC have the incorrect address.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1352344 |
Elevators | Original | D | 7/20/2020 | ERIC | ERIC | Provide elevator submittals (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1352338 |
Electronic Plan | Original | / | 7/20/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1352335 |
Resubmittal 2 | Original | / | 7/20/2020 | JAY | JAY | Resubmittal #2 | | Resubmittal 2 | 1352315 |
Construction | Original | A | 2/27/2019 | SHELLEY | SHELLEY | | | Construction | 1163352 |
Out to Review | Original | / | 2/27/2019 | NELIDA | NELIDA | Ryan 7193877836 | | Out to Review | 1163002 |
Finished Bin | Original | / | 10/12/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1119515 |
Plan Coordinator | Original | / | 10/12/2018 | | MPFITZSIMMONS | Location = Plan Coordinator by MPFITZSIMMONS | | Plan Coordinator | 1119484 |
CO Springs DRE | Original | D | 10/12/2018 | MPFITZSIMMONS | MPFITZSIMMONS | DP and FP have not been approved by zoning yet. Resubmit the plans once the DP and FP are stamped by the planner. (see full review) | | CO Springs DRE | 1119483 |
Zoning/Planning | Original | / | 10/9/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1118009 |
Plan Coordinator | Original | / | 10/9/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1117967 |
Mechanical | Original | D | 10/9/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Verify orientation indicated in heatloss calculation. Calculations indicate front door as facing south. The (A) sheets indicate the front door facing north. Revise orientation to match (A) sheets. and revise for any loads changes
Will require full mechanical review with next submittal
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1117965 |
Mechanical | Original | / | 10/9/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1117784 |
Mechanical | Original | / | 10/8/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1117736 |
Plan Coordinator | Original | / | 10/8/2018 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1117720 |
Elevators | Original | D | 10/8/2018 | ERIC | ERIC | Please provide elevator specifications (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1117719 |
Elevators | Original | / | 10/8/2018 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1117485 |
Plan Coordinator | Original | / | 10/8/2018 | AMY | AMY | In Current Review by AMY | | Plan Coordinator | 1117482 |
Plan Coordinator | Original | / | 10/8/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1117429 |
Construction | Original | D | 10/8/2018 | SHELLEY | SHELLEY | Missing S2.2. All else ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1117428 |
Construction | Original | / | 10/8/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1117398 |
Construction | Original | / | 10/8/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1117358 |
Plan Coordinator | Original | / | 10/8/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1117321 |
Floodplain | Original | D | 10/8/2018 | AMY | AMY | PROVIDE A COPY OF THE LOMA TO THIS DEPARTMENT PRIOR TO APPROVAL OF THE PLAN. IF 100 YEAR FLOODPLAIN IS NOT REMOVED PER THE LOMA A FLOODPLAIN DEVELOPMENT PERMIT MAY STILL BE REQUIRED ALONG WITH OTHER REQUIREMENTS. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Floodplain | 1117320 |
Floodplain | Original | / | 10/8/2018 | | AMY | Location = Floodplain by AMY | | Floodplain | 1117303 |
Enumeration | Original | D | 10/8/2018 | AMY | AMY | FOLLOWINGT COMMENTS ARE FROM ENUMERATIONS TO THE CITY PLANNER 7-23-18-THESE COMMENTS HAVE NOT BEEN MET: 1. Buildings 2 & 3 will be addressed from St. Elmo Ave, Buildings 1, 4, 5 & 6 from interior street name “CREEK EDGE VIEW”, Building 7 from E. Ramona Ave. 2. At building final inspection with RBD, inspectors will be looking for addressing to be posted: buildings 2, 3, 7 will need to be posted on the front doors only, buildings 1, 4, 5 & 6 addressing posted on the front and the rear of the structures. 3. When building plans are submitted for review for permit; a similar note (from Enumerations comment 2) should be on the site plans. final plat comments to the planner: 1.Approved private street name needs to be added to the plat in the road location. 2.Addressing should be shown on the plat in the locations of the proposed buildings. Utilizing a range for each building would be okay. 3.Note on plat has been added, note 10; where addressing is to be posted on the buildings.
CONTACT THIS DEPT. FOR ALL ADDRESSES TO BE ADDED TO PAGE A1.1. ADDRESSES SHOULD BE PLACED AT FRONT DOOR. ADD THE APPROVED PRIVATE STREET NAME TO THE ADDRESSING PLAN. ALONG WITH ALL SURROUNDING STREET NAMES THAT APPLY TO THIS PLAN- ST. ELMO, E. RAMONA. DEMO PERMITS SHOULD BE IN PLACE PRIOR TO APPROVAL FOR THIS PERMIT.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1117302 |
Enumeration | Original | / | 10/8/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1117270 |
Enumeration | Original | / | 10/4/2018 | | RITA | Location = Enumeration by RITA | | Enumeration | 1116587 |
Resubmittal 1 | Original | / | 10/4/2018 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1116585 |
Out to Review | Original | / | 10/20/2017 | GITA | GITA | 7193221022 lloyd | | Out to Review | 1005841 |
Finished Bin | Original | / | 10/19/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1005431 |
Plan Coordinator | Original | / | 10/18/2017 | | RDCUSER | Location = Plan Coordinator by RDCUSER | | Plan Coordinator | 1005391 |
CO Springs DRE | Original | D | 10/18/2017 | RDCUSER | RDCUSER | Please include approved Development Plan with plan set (see full review) | | CO Springs DRE | 1005390 |
Zoning/Planning | Original | / | 10/18/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1005179 |
Plan Coordinator | Original | / | 10/18/2017 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1005162 |
Elevators | Original | D | 10/18/2017 | ERIC | ERIC | Please provide specifications for elevators (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1005161 |
Elevators | Original | / | 10/18/2017 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1005146 |
Plan Coordinator | Original | / | 10/18/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1005030 |
Mechanical | Original | D | 10/18/2017 | JUSTINC | JUSTINC | Mechanical review incomplete
Duct design background do not appear to match backgrounds indicated on sheet A2.1
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1005029 |
Mechanical | Original | / | 10/17/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1004895 |
Mechanical | Original | / | 10/17/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1004797 |
Plan Coordinator | Original | / | 10/17/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1004755 |
Construction | Original | D | 10/17/2017 | DANM | DANM | Sheet A1.1 - Provide CRS accessibility requirements including calculations and identification of all units contributing to total; current project is a two-family dwelling and does not qualify toward meeting CRS accessibility requirements Locate floor truss FA203A and clarify one header size on third floor framing Specify post size on roof framing plan No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1004754 |
Construction | Original | / | 10/17/2017 | DANM | DANM | In Current Review by DANM | | Construction | 1004586 |
Construction | Original | / | 10/12/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1003571 |
Plan Coordinator | Original | / | 10/12/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1003544 |
Floodplain | Original | D | 10/12/2017 | AMY | AMY | Contact Keith Curtis for further review and discussions regarding the current floodplain in the lots. Keith 327-2898 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Floodplain | 1003543 |
Floodplain | Original | / | 10/12/2017 | | AMY | Location = Floodplain by AMY | | Floodplain | 1003525 |
Enumeration | Original | D | 10/12/2017 | AMY | AMY | -This area has not been addressed and South Cascade address will not be used for this project. ADDRESSING WILL NOT START UNTIL THE RESPONCES FROM THE DP PLAN APPLICATION TO CITY PLANNER ARE RECEIVED.
-In my comments to City planning i stated that an interior street name needed to be added. After further review i believe this are all rear loaded. We my need to have a meeting prior to addressing, Contact Amy to setup at time to discuss. Amy 327-2930
-7, 11, 15, & 19 E Ramona Ave homes, garages & sheds will be removed from the area. On either side of this area remains 3 E Ramona Ave (office/Res.) & 23-25 E Ramona Ave (duplex 25 basement), is the garage on this lot being removed? If this is not correct please clarify so that the correct addressing can be removed and the plat does not get held up.
-Which are the 2 buildings for this plan submittal? CLOUD THE BUILDINGS.
-Enumerations/Floodplain will review the mylar prior to plat of address placement, street naming, title block & floodplain statement. $10.00 per lot & tract will be due at the time of the review of the mylar. A copy of the final recorded plat is required prior to approval in this department.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1003524 |
Enumeration | Original | / | 10/12/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 1003488 |
Floodplain | Original | / | 10/11/2017 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6430209014) | | Floodplain | 1003123 |