- Not Set - | Splice 11/21/18 | / | 10/3/2019 | JLANE | JLANE | EXPIRED PLAN - Plan has been Disposed of. Plan is over 180 days old. This SPLICE plan has been scanned into the Plan Images | | - Not Set - | 1242196 |
- Not Set - | Original | / | 7/12/2019 | | JLANE | Location = EXPIRED PLANS BIN by JLANE - Plans are over 180 Days old. Email Communication Sent to email on file for plans. Will dispose of 7/19/19 Friday if not picked up. | | - Not Set - | 1212226 |
To Be Scanned Bin | Splice 11/21/18 | / | 11/26/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1133674 |
Plan Coordinator | Splice 11/21/18 | / | 11/26/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1133610 |
Mechanical | Splice 11/21/18 | A | 11/26/2018 | JUSTINC | JUSTINC | Revised design and calculations for basement in lieu of crawlspace | | Mechanical | 1133609 |
Mechanical | Splice 11/21/18 | / | 11/26/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1133551 |
Mechanical | Splice 11/21/18 | / | 11/21/2018 | | NELIDA | Location = Mechanical by NELIDA | | Mechanical | 1133024 |
Construction | Splice 8/24/18 | A | 8/24/2018 | BPHILLIPS | BPHILLIPS | Revised header support. | | Construction | 1103379 |
Out to Review | Splice 8/24/18 | / | 8/24/2018 | BECKYA | BECKYA | | | Out to Review | 1103364 |
Construction | Splice 6/28/18 | A | 6/28/2018 | MICHAELA | MICHAELA | modified foundation plan | | Construction | 1084569 |
Out to Review | Splice 6/28/18 | / | 6/28/2018 | BECKYA | BECKYA | | | Out to Review | 1084561 |
Scanned/Finished Bin | Original | / | 6/6/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1076993 |
DRE Large Bin | Original | / | 3/1/2018 | | KHYLLESTED | Location = DRE Large Bin by KHYLLESTED | | DRE Large Bin | 1042305 |
CO Springs DRE | Original | A | 3/1/2018 | KHYLLESTED | KHYLLESTED | 750 sf addition to SFR. Max height is 30'. (see full review) | | CO Springs DRE | 1042304 |
Zoning/Planning | Original | / | 2/27/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1041209 |
Zoning/Planning | Original | / | 2/26/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1040839 |
Plan Coordinator | Original | / | 2/26/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1040820 |
Mechanical | Original | A | 2/26/2018 | DALEH | DALEH | | | Mechanical | 1040819 |
Mechanical | Original | / | 2/23/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1040477 |
Mechanical | Original | / | 2/23/2018 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 1040467 |
Resubmittal 2 | Original | / | 2/23/2018 | MINDY | MINDY | Resubmittal #2 | | Resubmittal 2 | 1040466 |
Out to Review | Original | / | 2/23/2018 | MINDY | MINDY | Jim 650 9978 | | Out to Review | 1040454 |
Finished Bin | Original | / | 2/7/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1035675 |
Plan Coordinator | Original | / | 2/7/2018 | | KHYLLESTED | Location = Plan Coordinator by KHYLLESTED | | Plan Coordinator | 1035657 |
Out to Review | Original | / | 2/1/2018 | GITA | GITA | Jim 7196509978 | | Out to Review | 1033889 |
Finished Bin | Original | / | 1/31/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1033273 |
Plan Coordinator | Original | / | 1/30/2018 | | KHYLLESTED | Location = Plan Coordinator by KHYLLESTED | | Plan Coordinator | 1033171 |
CO Springs DRE | Original | D | 1/30/2018 | KHYLLESTED | KHYLLESTED | Max building height for R zone is 30 feet. Site plan needs to specify and label building height prior to approval. Using the numeric scale provided, the elevations are more than 30'. Please revise the site plan before resubmitting. (see full review) | | CO Springs DRE | 1033170 |
Zoning/Planning | Original | / | 1/29/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1032666 |
Zoning/Planning | Original | / | 1/26/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1032301 |
Plan Coordinator | Original | / | 1/26/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1032288 |
Mechanical | Original | D | 1/26/2018 | DALEH | DALEH | friction loss work sheet needs to show .7 duct system summary needs to show .7 performance data sheet is correct it shows .7
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1032287 |
Mechanical | Original | / | 1/26/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1032273 |
Mechanical | Original | / | 1/26/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1032242 |
Plan Coordinator | Original | / | 1/26/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1032227 |
Construction | Original | A | 1/26/2018 | SHELLEY | SHELLEY | | | Construction | 1032226 |
Construction | Original | / | 1/26/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1032221 |
Construction | Original | / | 1/26/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1032198 |
Resubmittal 1 | Original | / | 1/26/2018 | SCANNING | SCANNING | Resubmittal #1 | | Resubmittal 1 | 1032197 |
Out to Review | Original | / | 1/2/2018 | RDCUSER | RDCUSER | applicant picked up plans from DRE flat bin | | Out to Review | 1025223 |
Zoning/Planning | Original | / | 12/27/2017 | | KHYLLESTED | Location = Zoning/Planning by KHYLLESTED | | Zoning/Planning | 1024380 |
CO Springs DRE | Original | D | 12/27/2017 | KHYLLESTED | KHYLLESTED | Max building height for R zone is 30 feet. Site plan needs to specify and label building height prior to approval. (see full review) | | CO Springs DRE | 1024379 |
Zoning/Planning | Original | / | 12/19/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1022615 |
Plan Coordinator | Original | / | 12/19/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1022597 |
Mechanical | Original | D | 12/19/2017 | DALEH | DALEH | see duct design and equipment spec sheets for red lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1022595 |
Mechanical | Original | / | 12/19/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1022573 |
Mechanical | Original | / | 12/19/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1022479 |
Plan Coordinator | Original | / | 12/19/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1022462 |
Construction | Original | D | 12/19/2017 | SHELLEY | SHELLEY | Specify functions of all new windows; see notes on roof framing; see plans; walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1022461 |
Construction | Original | / | 12/19/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1022449 |
Floodplain | Original | N | 12/14/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7436210009) | | Floodplain | 1021555 |