Mechanical | Splice 12/10/18 | A | 12/28/2018 | DALEH | DALEH | revised lower level from forced air to electric heat | | Mechanical | 1145554 |
Resubmittal 1 | Splice 12/10/18 | / | 12/28/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1145521 |
Out to Review | Splice 12/10/18 | / | 12/18/2018 | BECKYA | BECKYA | caleb has splice 814-280-8008 | | Out to Review | 1142505 |
Finished Bin | Splice 12/10/18 | / | 12/12/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1140556 |
Plan Coordinator | Splice 12/10/18 | / | 12/12/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1140538 |
Mechanical | Splice 12/10/18 | D | 12/12/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
It appears intent of this splice is to not use the Furnace HVAC system to heat the basements, and in lieu use electric heat at basement levels. Will need to revise each calculation to indicate the basement as a separate zone associated with its own equipment and not part of the furnace systems. Will also need to revise both HVAC equipment certificates to only indicate the losses and equipment associated with the furnace system. Will need to provide new HVAC equipment certificates for the basement levels with electric heat.
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1140537 |
Construction | Splice 12/10/18 | A | 12/12/2018 | DANM | DANM | New IECC Certificates for each unit - no change from approved | | Construction | 1140518 |
Mechanical | Splice 12/10/18 | / | 12/12/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1140515 |
Construction | Splice 12/10/18 | / | 12/11/2018 | | BECKYA | Location = Construction by BECKYA | | Construction | 1140437 |
Electrical | Original | A | 7/16/2018 | DEAN | DEAN | Meters/disconnects/panel locations on plan. | | Electrical | 1089822 |
Mechanical | Original | A | 7/13/2018 | DALEH | DALEH | | | Mechanical | 1089303 |
Construction | Original | A | 7/12/2018 | SHELLEY | SHELLEY | | | Construction | 1088822 |
Resubmittal 5 | Original | / | 7/11/2018 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1088473 |
Electrical | Original | D | 7/11/2018 | SHELBY | SHELBY | Show on floor plan two electrical meters, two service disconnects, and all panels being installed on floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1088271 |
Mechanical | Original | D | 7/11/2018 | DALEH | DALEH | multiple up loads of both unit a and b with different losses ....decide on which heat calc will be used and remove other heat calc (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1088137 |
CO Springs DRE | Original | A | 7/10/2018 | KHYLLESTED | KHYLLESTED | New duplex - all development standards met. (see full review) | | CO Springs DRE | 1087974 |
Zoning/Planning | Original | / | 7/9/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1087218 |
Construction | Original | A | 7/6/2018 | SHELLEY | SHELLEY | | | Construction | 1086911 |
Enumeration | Original | A | 7/6/2018 | BRENT | BRENT | | | Enumeration | 1086885 |
Resubmittal 4 | Original | / | 7/5/2018 | BPHILLIPS | BPHILLIPS | Resubmittal #4 | | Resubmittal 4 | 1086674 |
Plan Coordinator | Original | D | 7/3/2018 | BECKYA | BECKYA | Disapprove all remaining departments to allow plan to be resubmitted (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1086101 |
Mechanical | Original | D | 7/3/2018 | DALEH | DALEH | no revisions to previous comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1086078 |
Electronic Plan | Original | / | 7/3/2018 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1086075 |
Electrical | Original | A | 6/28/2018 | SHELBY | SHELBY | | | Electrical | 1084850 |
Zoning/Planning | Original | / | 6/28/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1084770 |
Construction | Original | D | 6/28/2018 | SHELLEY | SHELLEY | HVAC equipment cert belongs in mechanical submittal - remove from IECC submittal; provide structural plans - have been completely removed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1084667 |
Enumeration | Original | A | 6/27/2018 | BRENT | BRENT | | | Enumeration | 1084085 |
Resubmittal 3 | Original | / | 6/27/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1084083 |
CO Springs DRE | Original | D | 5/22/2018 | KHYLLESTED | KHYLLESTED | Address previous review comments. (see full review) | | CO Springs DRE | 1071588 |
Electrical | Original | D | 5/21/2018 | SHELBY | SHELBY | Please address previous review comments. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1070627 |
Zoning/Planning | Original | / | 5/21/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1070483 |
Mechanical | Original | D | 5/18/2018 | DALEH | DALEH | two of the same duct designs need to provide two separate duct designs with two different AED'S no review no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1070313 |
Construction | Original | D | 5/17/2018 | SHELLEY | SHELLEY | COOKING APPLIANCES REMOVED FROM BASEMENTS - MEETS DUPLEX REQUIREMENTS
PLEASE provide a valid assembly from the 18th or newer edition of the GA manual. PLEASE copy all plan review notes from previous reviews to resubmittal. Please review and address ALL comments on plan prior to resubmittal.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1069997 |
Enumeration | Original | D | 5/17/2018 | BRENT | BRENT | See comments from 02/02/18 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1069967 |
Resubmittal 2 | Original | / | 5/17/2018 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1069950 |
CO Springs DRE | Original | D | 5/14/2018 | KHYLLESTED | KHYLLESTED | Site plan is showing a garage. Please remove this from the plans - proposed garage is not within property boundaries and cannot be approved. Indicate off street parking spaces - 1 space is required for each unit. Show driveway location. Indicate building height and include a building elevation schematic with the average finished grade line and height on the site plan. (see full review) | | CO Springs DRE | 1068386 |
Mechanical | Original | D | 5/14/2018 | DALEH | DALEH | need clarification on 4 unit commercial building no review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1067927 |
Electronic Plan | Original | / | 5/10/2018 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1067228 |
Zoning/Planning | Original | / | 5/9/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1066560 |
Electrical | Original | D | 5/9/2018 | SHELBY | SHELBY | Identify Electrical meters, Service disconnect(s), and areas with panels on floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1066503 |
Construction | Original | D | 5/9/2018 | SHELLEY | SHELLEY | UPON FURTHER REVIEW, THIS IS NOT A DUPLEX. BASEMENT UNITS HAVE KITCHENS WITH PERMANENT COOKING APPLIANCES, THEREFORE THIS IS A 4 UNIT BUILDING, AND WOULD BE CONSIDERED A COMMERCIAL R-2. PLEASE SUBMIT ACCORDINGLY. OR REMOVE BASEMENT COOKING APPLIANCES. GARAGE REMOVED; OTHER COMMENTS NOT ADDRESSED.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1066454 |
Enumeration | Original | D | 5/8/2018 | BRENT | BRENT | See comments from 02/02/18 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1066268 |
Resubmittal 1 | Original | / | 5/8/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1066250 |
Electrical | Original | D | 2/16/2018 | SHELBY | SHELBY | Show location of building service and branch panels on floor plan. Note: One structure is permitted to have one service. Electrical panels may not be located in rated walls. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1038417 |
CO Springs DRE | Original | D | 2/14/2018 | KHYLLESTED | KHYLLESTED | Show garage on site plan or remove all garage components from plan. Covered porch square footage needs to be indicated and included in the lot coverage calc. Garage square footage will also need to be indicated and included in lot coverage calc (if included on site plan). Indicate drainage pattern locations. Building height needs to be included on site plan along with the average finished grade. This parcel is located west of I-25, and a geologic hazard report or geologic hazard waiver is required. You may qualify for a geologic hazard waiver if this parcel does not lie within the landslide susceptibility area and does not exhibit any of the following characteristics: 1. Slopes greater than 33% percent 2. Underground mining or subsidence activity 3. A history of landfill or uncontrolled or undocumented fill activity IF the criteria outlined above is met, the site is eligible for a geologic hazard waiver application. The application needs to be signed by a professional geologist or geotechnical engineer AND it must be accompanied by a letter that states this site does not exhibit any of the characteristics noted above (also outlined on the application). There is not a review fee for geohazard waiver applications. Once you have the letter from a geotechnical engineer or geologist, please email the following to me: 1. The letter 2. The signed application 3. Your site plan As long as your property meets the three criteria above, city engineering and city planning will be able to sign off on the application and then you’ll be able to submit your site plan and waiver to regional building. Wait until you have all three signatures on the geologic hazard waiver application before you submit your site plan for a building permit. Site plans that do not have a signed copy of the application will be denied. Please contact Katelyn Hyllested with questions at khyllested@springsgov.com (see full review) | | CO Springs DRE | 1037594 |
Zoning/Planning | Original | / | 2/12/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1036926 |
Mechanical | Original | D | 2/12/2018 | DALEH | DALEH | need to provide two different calcs and two different performance test drawings showing two different addresses...site specific requires a calc for each ..AED will be different for both. no review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1036601 |
Electronic Plan | Original | / | 2/12/2018 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1036597 |
Construction | Original | D | 2/12/2018 | SHELLEY | SHELLEY | Show garage on site plan or remove all garage components from plan; Minimum of 18th edition of GA manual required - assemblies 1001 and 1005 are no longer valid; see plans; (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1036578 |
Electronic Plan | Original | / | 2/12/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1036548 |
Enumeration | Original | D | 2/2/2018 | BRENT | BRENT | Clearly show secondary addressing for all units on architectural pages. Secondary addressing guide available on our website www.pprbd.org ->addressing->secondary addressing guide. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1034304 |
Floodplain | Original | N | 2/1/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7413212007) | | Floodplain | 1033959 |