Construction | Splice 03/16/23 | A | 3/16/2023 | DANM | DANM | Structural revisions, structural detail, missing truss | | Construction | 1817143 |
Electronic Plan | Splice 03/16/23 | / | 3/16/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1817094 |
Construction | Splice 03/07/23 | A | 3/8/2023 | DANM | DANM | Structural framing revisions | | Construction | 1813374 |
Electronic Plan | Splice 03/07/23 | / | 3/8/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1813357 |
Construction | Original | A | 5/25/2018 | DANM | DANM | Engineered foundation plan added to submittal | | Construction | 1072896 |
CO Springs Fire | Original | A | 12/11/2017 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1020348 |
Construction | Original | A | 8/14/2017 | DANM | DANM | Structural revisions by engineer | | Construction | 986486 |
Out to Review | Original | / | 6/21/2017 | RITA | RITA | ANDREW 650-814-8172 | | Out to Review | 971154 |
Finished Bin | Original | / | 6/21/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 971103 |
CO Springs Fire | Original | D | 6/20/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 970956 |
Fire | Original | / | 6/16/2017 | | MBINGMAN | Location = Fire by MBINGMAN | | Fire | 969916 |
CO Springs DRE | Original | A | 6/16/2017 | MBINGMAN | MBINGMAN | New SFR. Significant Geological Hazards Concerns. See attached documentation for authority to release plan. All HS requirements met. All DP requirements addressed. Subject to disclosure statement. See CPC DP 91-154-A2(05) in the development review enterprise for additional documentation on the review. ILC required prior to CO release. (see full review) | | CO Springs DRE | 969915 |
Zoning/Planning | Original | / | 6/13/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 968888 |
Plan Coordinator | Original | / | 6/13/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 968878 |
Mechanical | Original | A | 6/13/2017 | JUSTINC | JUSTINC | | | Mechanical | 968876 |
Mechanical | Original | / | 6/13/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 968820 |
Mechanical | Original | / | 6/12/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 968316 |
Plan Coordinator | Original | / | 6/12/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 968249 |
Construction | Original | A | 6/12/2017 | SHELLEY | SHELLEY | | | Construction | 968248 |
Construction | Original | / | 6/12/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 968224 |
Construction | Original | / | 6/12/2017 | | GITA | Location = Construction by GITA | | Construction | 968208 |
Resubmittal 2 | Original | / | 6/12/2017 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 968205 |
Fire | Original | / | 6/6/2017 | | MBINGMAN | Location = Fire by MBINGMAN | | Fire | 966178 |
CO Springs DRE | Original | D | 6/6/2017 | MBINGMAN | MBINGMAN | Per emailed review comments. Please submit new site plan in roll set for a final review once comments have been addressed. (see full review) | | CO Springs DRE | 966177 |
Zoning/Planning | Original | / | 6/1/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 965084 |
Plan Coordinator | Original | / | 5/31/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 964895 |
Mechanical | Original | D | 5/31/2017 | JUSTINC | JUSTINC | Mechanical review incomplete pending construction reviewer comments. Missing IECC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 964894 |
Mechanical | Original | / | 5/31/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 964891 |
Mechanical | Original | / | 5/31/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 964876 |
Plan Coordinator | Original | / | 5/31/2017 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 964855 |
Construction | Original | D | 5/31/2017 | BPHILLIPS | BPHILLIPS | Elevations page missing several items. Refer to residential construction plans handout for complete list of requirements. Still need completed IECC form. Changes to stamped sheets need to be initialed and dated by engineer of record. See plans for all comments. No walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 964853 |
Construction | Original | / | 5/31/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 964779 |
Construction | Original | / | 5/30/2017 | | MINDY | Location = Construction by MINDY | | Construction | 964322 |
Resubmittal 1 | Original | / | 5/30/2017 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 964321 |
Out to Review | Original | / | 4/26/2017 | RITA | RITA | Andrew 650-814-8172 | | Out to Review | 955281 |
Finished Bin | Original | / | 4/25/2017 | | JESSICAM | Location = Finished Bin by JESSICAM | | Finished Bin | 955114 |
CO Springs Fire | Original | D | 4/25/2017 | CSFIRE | CSFIRE | | dwithee | CO Springs Fire | 954917 |
Fire | Original | / | 4/13/2017 | | MBINGMAN | Location = Fire by MBINGMAN | | Fire | 952074 |
CO Springs DRE | Original | D | 4/13/2017 | MBINGMAN | MBINGMAN | See attached dissaproval comments per hillside checklist, engineering comments and other notes. No fire system requirements found. ILC required before release of CO. Must attach a copy of the disclosure statement to building permit set. (see full review) | | CO Springs DRE | 952073 |
Zoning/Planning | Original | / | 3/30/2017 | | JLANE | Location = Zoning/Planning by JLANE | | Zoning/Planning | 948378 |
Plan Coordinator | Original | / | 3/30/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 948291 |
Mechanical | Original | D | 3/30/2017 | JUSTINC | JUSTINC | Missing performance test duct design? If mechanical engineer wishes to use PPRBD heat loss calculator all mechanical sheets must have P.E stamp
SEE PLAN FOR ALL ADDITIONAL COMMENTS
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 948290 |
Mechanical | Original | / | 3/30/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 948169 |
Mechanical | Original | / | 3/29/2017 | | JLANE | Location = Mechanical by JLANE | | Mechanical | 947915 |
Plan Coordinator | Original | / | 3/29/2017 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 947892 |
Construction | Original | D | 3/29/2017 | BPHILLIPS | BPHILLIPS | Provide elevation drawings. Provide IECC. Clarify egress window sizes. Need clarification on some structural issues. Porch structural details not legible. See plans. No walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 947891 |
CO Springs DRE | Original | / | 3/29/2017 | MBINGMAN | MBINGMAN | Significant Geological Hazards on site. | | CO Springs DRE | 947683 |
Construction | Original | / | 3/28/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 947533 |
Construction | Original | / | 3/28/2017 | | MINDY | Location = Construction by MINDY | | Construction | 947308 |
Plan Coordinator | Original | / | 3/28/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 947195 |
Enumeration | Original | A | 3/28/2017 | AMY | AMY | | | Enumeration | 947194 |
Enumeration | Original | / | 3/28/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 947187 |
Floodplain | Original | N | 3/27/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 946876 |