Construction | Original | A | 10/9/2024 | JAY | JAY | Resubmittal forthcoming. | | Construction | 2070283 |
Triage | Original | D | 10/12/2023 | ANDREAL | ANDREAL | Waiting on Documents for the remaining Disapproved departments. | | Triage | 1912389 |
Plan Coordinator (Main) | Original | D | 10/12/2023 | ANDREAL | ANDREAL | Disapprove all remaining departments to allow plan to be resubmitted. Sending back for the appropriate documents to be uploaded. | | Plan Coordinator (Main) | 1912388 |
Resubmittal 6 | Original | / | 10/12/2023 | ANDREAL | ANDREAL | Resubmittal #6 | | Resubmittal 6 | 1912387 |
CO Springs DRE | Original | D | 10/25/2022 | RTEFERTILLER | RTEFERTILLER | Construction documents are substantially consistent with the approved development plan (AR PUD 20-00169). Previous comments regarding roof-deck have been discussed verbally and Planning Staff agrees that the construction documents can be supported even though they still show an unapproved roof-deck. Prior to CO the development plan will either need to be updated to show the deck or the construction documents must be updated to remove the deck. The only remaining comment is to collect park and school fees. Plans are approved and once fees are collected, the building permit can be approved (see full review) | | CO Springs DRE | 1761255 |
CSU Contract Admin. | Original | D | 10/25/2022 | CSUAPPSPRM | CSUAPPSPRM | Commerical Water Meter Sizing form approved, requires payment of development fees/charges. Contact our office at 719-668-8111 for additional information. AG | aguerin | CSU Contract Admin. | 1761208 |
Zoning/Planning | Original | / | 10/21/2022 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1760331 |
Plumbing | Original | A | 10/21/2022 | SHANEN | SHANEN | | | Plumbing | 1759922 |
CSU Water | Original | A | 10/21/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Water | 1759835 |
CSU Waste Water | Original | A | 10/21/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Waste Water | 1759834 |
Gas/Elec. Utils | Original | A | 10/21/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | Gas/Elec. Utils | 1759833 |
Resubmittal 5 | Original | / | 10/20/2022 | ANDREAL | ANDREAL | Resubmittal #5 | | Resubmittal 5 | 1759816 |
CO Springs Fire | Original | A | 9/21/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1744367 |
CO Springs DRE | Original | D | 9/2/2022 | RTEFERTILLER | RTEFERTILLER | Plans appear consistent with approved development plan (AR PUD 20-00169) but the only version of the DP included in the construction set is not the final / approved version. Please provide a copy of the stamped approved development plan within the construction set. PLDO fees must be paid prior to building permit. Previous comments regarding roof-deck have been discussed verbally and Planning Staff agrees that the construction documents can be supported even though they still show an unapproved roof-deck. Prior to CO the development plan will either need to be updated to show the deck or the construction documents must be updated to remove the deck. (see full review) | | CO Springs DRE | 1737662 |
Zoning/Planning | Original | / | 9/1/2022 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1736637 |
City Engr | Original | A | 9/1/2022 | PMORRIS | PMORRIS | | | City Engr | 1736589 |
CSU Contract Admin. | Original | D | 8/30/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1735383 |
Mechanical | Original | A | 8/30/2022 | JUSTINC | JUSTINC | | | Mechanical | 1735318 |
Gas/Elec. Utils | Original | D | 8/30/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 1735257 |
CSU Water | Original | D | 8/30/2022 | CSUREVIEW | CSUREVIEW | The address on the Utility Service Plan does not match the address on the permit. Correct whichever address is wrong, a revision to the construction plans may be required. On the plumbing plans: The irrigation line is shown branching off before the domestic backflow preventer, all branch lines must branch off after the BFP. Use the updated detail B1-11 from 2021 WaterLESS in lieu the schematic from the backflow preventer form. CJS | cjsavage | CSU Water | 1735256 |
CSU Waste Water | Original | D | 8/30/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan with City approval stamp must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 1735231 |
Construction | Original | A | 8/30/2022 | MICHAELA | MICHAELA | | | Construction | 1735222 |
Electrical | Original | A | 8/29/2022 | BERTHA | BERTHA | | | Electrical | 1734735 |
Electronic Plan | Original | / | 8/29/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1734717 |
Electronic Plan | Original | / | 8/29/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1734618 |
Enumeration | Original | A | 8/29/2022 | AMY | AMY | Not sure why 205 E Fountain Blvd was add to page A0.1/Other Accessibility Site Plan & Matrix sheet-again the address to this plan is 110 Writers Way. This was corrected for you. | | Enumeration | 1734577 |
Electronic Plan | Original | / | 8/29/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1734571 |
Resubmittal 4 | Original | / | 8/25/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #4 | | Resubmittal 4 | 1733819 |
CSU Contract Admin. | Original | D | 5/23/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. AG | aguerin | CSU Contract Admin. | 1686500 |
CO Springs Fire | Original | D | 5/19/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1685006 |
CO Springs DRE | Original | D | 5/12/2022 | RTEFERTILLER | RTEFERTILLER | Provide copy of stamped approved development plan within the construction set. PLDO fees must be paid prior to building permit. The 4th floor roof deck structure is not included on the approved development plan and can not be permitted without first gaining approval of a development plan amendment. Please submit a pre-application meeting request from the City Planning Department website to initiate this meeting. (see full review) | | CO Springs DRE | 1681142 |
Zoning/Planning | Original | / | 5/11/2022 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1680600 |
CSU Water | Original | D | 5/11/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1680246 |
CSU Waste Water | Original | D | 5/11/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1680245 |
Gas/Elec. Utils | Original | D | 5/11/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1680241 |
City Engr | Original | D | 5/11/2022 | PMORRIS | PMORRIS | Same comments: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (Permanent Water Quality pond) construction plan. Upload a copy of the approved Development Plan. | | City Engr | 1680166 |
Electrical | Original | A | 5/11/2022 | BERTHA | BERTHA | | | Electrical | 1680151 |
Electronic Plan | Original | / | 5/11/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1680078 |
Construction | Original | A | 5/11/2022 | MICHAELA | MICHAELA | | | Construction | 1680066 |
Enumeration | Original | A | 5/10/2022 | AMY | AMY | | | Enumeration | 1679890 |
Electronic Plan | Original | / | 5/10/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1679885 |
Resubmittal 3 | Original | / | 5/10/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #3 | | Resubmittal 3 | 1679640 |
CO Springs Fire | Original | D | 2/3/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1631736 |
City Engr | Original | D | 1/26/2022 | JDAGNILLO | JDAGNILLO | See previous comments: Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Pond) in the electronic building permit set. | | City Engr | 1627245 |
CO Springs DRE | Original | D | 1/20/2022 | MPFITZSIMMONS | MPFITZSIMMONS | Approved DP was not included. Please resubmit with Stamped plans. (see full review) | | CO Springs DRE | 1624251 |
Electrical | Original | D | 1/20/2022 | BERTHA | BERTHA | The entire electrical set must be re-submitted. Please submit all sheets of the Electrical plan set.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1623944 |
CSU Contract Admin. | Original | D | 1/20/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted. Commercial water meter sizing form was approved 07/22/2021. Requires payment of applicable development fees.
AMS | ASweet | CSU Contract Admin. | 1623903 |
Electronic Plan | Original | / | 1/20/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1623818 |
Zoning/Planning | Original | / | 1/19/2022 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1623442 |
Gas/Elec. Utils | Original | D | 1/19/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | Gas/Elec. Utils | 1623352 |
CSU Waste Water | Original | D | 1/19/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | CSU Waste Water | 1623349 |
CSU Water | Original | D | 1/19/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | CSU Water | 1623347 |
Construction | Original | D | 1/19/2022 | MICHAELA | MICHAELA | It was my understanding that the exception to 1028.1 was being used for the middle stair. If that is the case why is the corridor shown as rated?Why are walls between the Bikes and Mech room, the Mech and the Gym and the Gym toilet room and Garage E being rated? If there is no code path indicate that these ratings are for "Other Than the IBC". Rated walls between garages that are opening directly into units need only meet garage/dwelling separation. Why are 1-hr. fire barriers being shown at those locations. Garages B, D, H and K must comply with IBC sec. 406.3.4.1.Exit discharge #2 must comply with the exception to IBC sec. 1028.1. A7.1 and A7.3 - Handrail extension is still incorrect at the bottom. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1623168 |
Enumeration | Original | A | 1/18/2022 | AMY | AMY | Note: CORRECTED, Secondary address has been sent to Colorado Springs Utilities and the United States Postal Services.
The Code Study form has the incorrect address. Enumerations remove 810 E Fountain Blvd and added 110 Writers Way. The street names to the surrounding area and the north arrow were added to page A1.0, if this sheet gets changed out, add this information. | | Enumeration | 1622617 |
Electronic Plan | Original | / | 1/18/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1622559 |
Resubmittal 2 | Original | / | 1/18/2022 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1621999 |
CO Springs Fire | Original | D | 8/11/2021 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1545235 |
City Engr | Original | D | 7/29/2021 | PMORRIS | PMORRIS | Same comments: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (Permanent Water Quality pond) construction plan. Upload a copy of the approved Development Plan. | | City Engr | 1538588 |
CSU Contract Admin. | Original | D | 7/22/2021 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved 7/22/2021 - Requires payment of applicable development fees/charges. Please contact our office at cca@csu.org for additional information and to request an estimate. AG | aguerin | CSU Contract Admin. | 1534602 |
Electrical | Original | D | 7/22/2021 | BERTHA | BERTHA | Pending approval in Enumerations. Multi-meter services must include a list of secondary addresses on the one-line diagram. Secondary addressing must be approved by Enumerations.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1534579 |
Electronic Plan | Original | / | 7/22/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1534456 |
Gas/Elec. Utils | Original | D | 7/21/2021 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | Gas/Elec. Utils | 1533900 |
CSU Water | Original | D | 7/21/2021 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | CSU Water | 1533897 |
CSU Waste Water | Original | D | 7/21/2021 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | CSU Waste Water | 1533895 |
CO Springs DRE | Original | D | 7/21/2021 | MPFITZSIMMONS | MPFITZSIMMONS | Stamped DP plans were not included. FP is still not approved. (see full review) | | CO Springs DRE | 1533688 |
Mechanical | Original | A | 7/21/2021 | JUSTINC | JUSTINC | | | Mechanical | 1533671 |
Electronic Plan | Original | / | 7/21/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1533592 |
Plumbing | Original | A | 7/21/2021 | SHANEN | SHANEN | | | Plumbing | 1533558 |
Zoning/Planning | Original | / | 7/21/2021 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1533555 |
Construction | Original | D | 7/21/2021 | MICHAELA | MICHAELA | Main level has U occupancy as worst case. Allowable area is compliant using frontage increase and so is non-separated use. Sum of the ratios is not required at the main level. Garage separation is per IBC 406. U occupancy may not be 3 stories in V-B construction so there needs to be a separation somewhere. Indicate that separation will occur at the floor above the main level. Per 406.3.1 private garages need to be separated by 1-hr. horizontal assemblies. You will need to provide 1-hr. supporting construction for the floor above the garages and specify that the separation is occurring there. All floors above the main level use 7000 SF as the allowable area w/ .75 frontage increase and so are also non-separated use. Handrail extensions at the bottom are still incorrect. Structural - 1-hr. supporting construction must be under floor above exit passageways and under the floor above the U occupancy garages. Add shading to the garage areas as well for clarification. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1533539 |
Enumeration | Original | D | 7/19/2021 | AMY | AMY | Secondary unit numbers on page A0.0 are correct, unit number on page A1.2, A1.3 have incorrect unit numbers. These need to be corrected. Note: Secondary address from page A0.0 have been sent to Colorado Springs Utilities and the United States Postal Services.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1532455 |
Electronic Plan | Original | / | 7/19/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1532406 |
Resubmittal 1 | Original | / | 7/19/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1532230 |
CO Springs Hazmat | Original | N | 6/11/2021 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1515472 |
CO Springs Fire | Original | D | 6/11/2021 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1515471 |
Electrical | Original | D | 6/10/2021 | BERTHA | BERTHA | 1. Pending Enumerations approval - Multi-meter services must include a list of secondary addresses on the one-line diagram. 2. Pending Construction approval - Accessibility plan required. 3. Provide method of compliance with 240.87 - 2017 NEC 4. Provide SCA and SCCR for air conditioning and refrigeration equipment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1514814 |
CSU Contract Admin. | Original | D | 6/8/2021 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 or cca@csu.org for information on charges/fees and to request an estimate. ZS
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5 | zshearer | CSU Contract Admin. | 1512953 |
Plumbing | Original | D | 6/1/2021 | SHANEN | SHANEN | Construction reviewer comments regarding accessibility must be addressed. Provide an occupant load fixture count analysis for the B occupancy. Note: Occupant load exceeding 15 occupants will require separate toilet facilities, a high/low drinking fountain and service sink. P0.1: Water pipe sizing must reference 2015 IPC. P1.4: Provide roof plan to show sizing for roof drain conductors, downspouts and overflow scuppers. Provide roof plumbing plan to show location, piping and sizing for roof primary/overflow drains and overflow scuppers. Provide gpm and/or square footage served by components of the roof drain system. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1508993 |
Mechanical | Original | D | 5/28/2021 | JUSTINC | JUSTINC | See mechanical plans for all comments associated with this review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1508233 |
City Engr | Original | D | 5/28/2021 | PMORRIS | PMORRIS | Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (Permanent Water Quality Facility) construction plan. Upload a copy of the approved Development Plan. | | City Engr | 1508104 |
Electronic Plan | Original | / | 5/27/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1507942 |
Electronic Plan | Original | / | 5/27/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1507569 |
Health Dept. | Original | N | 5/26/2021 | HEALTHDEPT | HEALTHDEPT | Not applicable. Scope of work is less than an acre (0.680 acres). Confirmed information with Kristin Kotera. MT | mtemple | Health Dept. | 1507137 |
CO Springs DRE | Original | D | 5/26/2021 | MPFITZSIMMONS | MPFITZSIMMONS | Please replace the current development plan with the stamped/approved development plan. It looks like the unit count has been reduced from 30 to 28. That will require a minor amendment. Please request a pre-application meeting if that is true. (see full review) | | CO Springs DRE | 1506996 |
Zoning/Planning | Original | / | 5/26/2021 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1506939 |
CSU Water | Original | D | 5/26/2021 | CSUREVIEW | CSUREVIEW | Approved Development Plan, Utility Service Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. RDS | rsolberg | CSU Water | 1506898 |
CSU Waste Water | Original | D | 5/26/2021 | CSUREVIEW | CSUREVIEW | Approved Development Plan, Utility Service Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. RDS | rsolberg | CSU Waste Water | 1506897 |
Gas/Elec. Utils | Original | D | 5/26/2021 | CSUREVIEW | CSUREVIEW | Approved Development Plan, Utility Service Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. RDS | rsolberg | Gas/Elec. Utils | 1506896 |
Elevators | Original | N | 5/26/2021 | ERIC | ERIC | No conveyance | | Elevators | 1506876 |
Construction | Original | D | 5/26/2021 | MICHAELA | MICHAELA | Accessibility Plan - Specific addresses are required. AC.1 - U occupancy is worst case with allowable area of 5,500. A 13R system does not create a sprinklered structure. Structure does not work as V-B non-separated use. See plan for frontage calculation issues. 9.0/D - If you are using the exception revise the exit designation and wall types at this exit. AC.2 - Mechanical room dedicated to the unit need not be separated. Revise stair description throughout plan to Interior Exit Stair. AC.3 - Provide a code path to allow a B occupancy above the second story with only one meanness of egress. Revise occupancy classification for B occupancies. Locate attic accesses. A2.1 - Add note for required 18" platform at mechanical equipment open to garage. The plan north exterior garage wall is a bearing wall supporting the horizontal assembly separating the U occupancies. The exemption for supporting construction does not apply. Show walls as M8-1-hr. A3.1 - Toilet room sink approach must be forward. Locate turning radius inside all rooms A3.2 - See A3.1 - Vanity can only overlap at the control wall. A3.3 - Missing door and window numbers. A3.10 - Toilet room must be fully accessible. This is not a dwelling unit. Show required clear floor space at toilet. A3.11 - Toilet room must be fully accessible. This is not a dwelling unit. Show required clear floor space at toilet. A6.1 - Show proper fire barrier continuity . Verify wall types at Pod B exit. A6.2 - Indicate that sprinkler protection will extend to projections or indicate FRT or non-combustible construction. Show section with compliant vertical continuity at fire barriers. A7.1 - Show compliant handrail extensions. A7.2 - Clarify wall types per 1028.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1506874 |
Electronic Plan | Original | / | 5/25/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1506211 |
Enumeration | Original | D | 5/20/2021 | AMY | AMY | As stated to the City Planner in review comments for this project, the building address would be 110 Writers Way. Change EACH & EVERY page of the plan to this address, including the title blocks. This plan cannot be a 30 unit building due to the Gym & the office not being an apartment unit. The Gym should not have an apt number, needs to have the name of the use of the room posted on the door. The office should have a suite number 100, to separate this number from the apartment numbers. Enumerations has edited these numbers.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1503769 |
Electronic Plan | Original | / | 5/20/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1503740 |
Floodplain | Original | N | 5/19/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6419115056) | | Floodplain | 1502807 |