Mechanical | Original | A | 5/18/2022 | DALEH | DALEH | | | Mechanical | 1684311 |
Plumbing | Original | A | 5/18/2022 | SHANEN | SHANEN | | | Plumbing | 1684048 |
Electrical | Original | A | 5/18/2022 | DANIELG | DANIELG | | | Electrical | 1683921 |
Electronic Plan | Original | / | 5/18/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1683918 |
Construction | Original | A | 5/18/2022 | MICHAELA | MICHAELA | | | Construction | 1683803 |
Enumeration | Original | A | 5/17/2022 | AMY | AMY | SEE ADDRESS CHANGES | | Enumeration | 1683633 |
Electronic Plan | Original | / | 5/17/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1683608 |
Resubmittal 4 | Original | / | 5/17/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #4 | | Resubmittal 4 | 1683058 |
Electrical | Original | D | 4/22/2022 | DANIELG | DANIELG | 1. Provide conductor size, type, and quantity from utility transformer to the scope of work.
2. Show OCPD's on the one-line.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1669985 |
Mechanical | Original | D | 4/15/2022 | DALEH | DALEH | These are not the same plans that were submitted last time (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1665842 |
Enumeration | Original | D | 4/14/2022 | AMY | AMY | After further review it seems as though all spaces throughout this business has a different address. 34, 36, 38, & now 40. What address is your license under? This should be the only address in use on site. Please contact me Amy@pprbd.org to clarify. Once clarified, I can edit the addresses throughout this plan for you.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1665737 |
Plumbing | Original | D | 4/14/2022 | SHANEN | SHANEN | All backgrounds must match per PPRBD plan review requirements. P1.1 plumbing plan does not match the architectural floor plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1665366 |
Construction | Original | A | 4/14/2022 | MICHAELA | MICHAELA | | | Construction | 1665117 |
Resubmittal 3 | Original | / | 4/13/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #3 | | Resubmittal 3 | 1664954 |
Mechanical | Original | D | 1/3/2022 | DALEH | DALEH | Waiting on Construction comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1615313 |
Electrical | Original | D | 12/30/2021 | SHELBY | SHELBY | No electrical plans submitted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1615047 |
Plumbing | Original | D | 12/30/2021 | SHANEN | SHANEN | No plumbing plans provided with this re-submittal. Previous comments still apply. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1614544 |
Construction | Original | D | 12/30/2021 | MICHAELA | MICHAELA | Provide the information requested on the previous two plan reviews. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1614537 |
Resubmittal 2 | Original | / | 12/29/2021 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1614502 |
Electrical | Original | D | 11/24/2021 | DANIELG | DANIELG | 1. Show size of service disconnect on one-line.
2. Pending construction review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1598601 |
Plumbing | Original | D | 11/24/2021 | SHANEN | SHANEN | Construction reviewer comments must first be addressed to verify compliance with section 403.1 Minimum number of fixtures. All backgrounds must match per PPRBD plan review requirements, see construction comments. Reference 2018 IPC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1598593 |
Electronic Plan | Original | / | 11/24/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1598589 |
Mechanical | Original | D | 11/23/2021 | JUSTINC | JUSTINC | Mechanical approval pending construction comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1598527 |
Construction | Original | D | 11/23/2021 | MICHAELA | MICHAELA | The plan must include Code Data; Type of Construction Occupancy classification Occupant load Codes being complied with Height and area calculations Exit access travel distance What is the scope of work? Are the interior walls new and if so how are they being constructed? Show fixtures in toilet room and show required clear floor spaces. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1598519 |
Resubmittal 1 | Original | / | 11/23/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1598492 |
CO Springs Hazmat | Original | N | 9/23/2021 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1567362 |
CO Springs Fire | Original | N | 9/23/2021 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles | csfdit | CO Springs Fire | 1567359 |
Electrical | Original | D | 8/27/2021 | DANIELG | DANIELG | Pending construction review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1554374 |
Electronic Plan | Original | / | 8/27/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1554046 |
Mechanical | Original | D | 8/26/2021 | JUSTINC | JUSTINC | Change of occupancy requires all mechanical scope to be indicated on plan, provide ventilation schedule
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1553585 |
Electronic Plan | Original | / | 8/26/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1553571 |
CO Springs DRE | Original | N | 8/26/2021 | PDOSCH | PDOSCH | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy | | CO Springs DRE | 1553438 |
Zoning/Planning | Original | / | 8/26/2021 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1553437 |
CSU Water | Original | N | 8/26/2021 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1553399 |
CSU Waste Water | Original | N | 8/26/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1553397 |
Plumbing | Original | D | 8/26/2021 | SHANEN | SHANEN | Construction reviewer comments must first be addressed to verify compliance with section 403.1 Minimum number of fixtures. All backgrounds must match per PPRBD plan review requirements. MEP plans do not match the architectural floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1553320 |
Construction | Original | D | 8/26/2021 | MICHAELA | MICHAELA | Correct and complete Code Study form. The plan must include Code Data; Type of Construction Occupancy classification Occupant load Codes being complied with Height and area calculations Exit access travel distance What is the scope of work? Are the interior walls new and if so how are they being constructed? Show fixtures in toilet room and show required clear floor spaces. See plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1553180 |
Electronic Plan | Original | / | 8/25/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1552830 |
Enumeration | Original | N | 8/17/2021 | AMY | AMY | | | Enumeration | 1548169 |
Floodplain | Original | N | 8/16/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6331208021) | | Floodplain | 1547851 |