CO Springs Hazmat | Original | N | 3/8/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1646577 |
CO Springs Fire | Original | A | 3/8/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1646576 |
Plumbing | Original | A | 2/23/2022 | TCRIPPEN | TCRIPPEN | Approved. | | Plumbing | 1640518 |
Construction | Original | A | 2/23/2022 | MICHAELA | MICHAELA | | | Construction | 1640414 |
Enumeration | Original | A | 2/17/2022 | BRENT | BRENT | | | Enumeration | 1638536 |
Electronic Plan | Original | / | 2/17/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1638526 |
Resubmittal 2 | Original | / | 2/17/2022 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1638158 |
CO Springs Hazmat | Original | D | 2/9/2022 | CSFIRE | CSFIRE | disapproved per Kier K Moore of nighthawk design so changes can be made. | jt09ff | CO Springs Hazmat | 1634683 |
CO Springs Fire | Original | D | 2/9/2022 | CSFIRE | CSFIRE | disapproved per Kier K Moore of nighthawk design so changes can be made. | jt09ff | CO Springs Fire | 1634682 |
CO Springs DRE | Original | A | 1/25/2022 | AODOM | AODOM | All development standards met | | CO Springs DRE | 1626370 |
Zoning/Planning | Original | / | 1/24/2022 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1625742 |
Plumbing | Original | D | 1/21/2022 | SHANEN | SHANEN | Provide and schedule a lavatory that complies with section 419.1 Approval. and ICCA117.1-2009 section 606 Lavatories and sinks. Provide required service sink. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1624968 |
Mechanical | Original | A | 1/21/2022 | JUSTINC | JUSTINC | | | Mechanical | 1624937 |
Electronic Plan | Original | / | 1/21/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1624918 |
Construction | Original | D | 1/21/2022 | MICHAELA | MICHAELA | Missing 18" vertical grab bar. Remove non-compliant grab bar details. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1624916 |
Enumeration | Original | A | 1/21/2022 | BRENT | BRENT | | | Enumeration | 1624851 |
Electronic Plan | Original | / | 1/21/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1624845 |
Resubmittal 1 | Original | / | 1/21/2022 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1624699 |
CO Springs Hazmat | Original | D | 12/27/2021 | CSFIRE | CSFIRE | see fire comments | jt09ff | CO Springs Hazmat | 1612887 |
CO Springs Fire | Original | D | 12/27/2021 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1612886 |
Health Dept. | Original | N | 12/6/2021 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB | abrannon | Health Dept. | 1602877 |
Mechanical | Original | D | 12/2/2021 | JUSTINC | JUSTINC | Provide ventilation schedule per 2015 IMC 403.3.1.1 Clarify on plan location of CU-1?
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1602100 |
Electronic Plan | Original | / | 12/2/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1602097 |
Plumbing | Original | D | 12/2/2021 | SHANEN | SHANEN | Provide required water pipe size analysis data, see 2018 IPC appendix E. All backgrounds must match per PPRBD plan review requirements. MEP plans do not match architectural floor plans. Lavatories must comply with section 419.1 Approval. Describe how free standing laundry sink used as a lavatory meets ANSI requirements for accessibility. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1601802 |
City Engr | Original | N | 12/2/2021 | PMORRIS | PMORRIS | | | City Engr | 1601595 |
CO Springs DRE | Original | A | 12/2/2021 | AODOM | AODOM | approved new warehouse use in suite of light industrial building, no exterior work proposed at this time | | CO Springs DRE | 1601570 |
Electrical | Original | A | 12/1/2021 | SHELBY | SHELBY | | | Electrical | 1601421 |
Electronic Plan | Original | / | 12/1/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1601420 |
CSU Contract Admin. | Original | N | 12/1/2021 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved and applicable development fees/charges paid - master meter configuration. AG | aguerin | CSU Contract Admin. | 1601105 |
Zoning/Planning | Original | / | 11/30/2021 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1600386 |
Gas/Elec. Utils | Original | N | 11/30/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | Gas/Elec. Utils | 1600370 |
CSU Waste Water | Original | N | 11/30/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | CSU Waste Water | 1600368 |
CSU Water | Original | N | 11/30/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | CSU Water | 1600367 |
Elevators | Original | N | 11/30/2021 | ERIC | ERIC | No conveyance | | Elevators | 1600261 |
Construction | Original | D | 11/30/2021 | MICHAELA | MICHAELA | All architectural pages must be stamped Locate required clear floor spaces at fixtures in toilet room. Provide elevations showing grab bar locations. Indicate compliance with IBC sec. 1210 for floor and wall finishes in toilet room. Clarify why a rated door is being placed in a non-rated wall. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1600253 |
Electronic Plan | Original | / | 11/30/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1600229 |
Enumeration | Original | A | 11/17/2021 | BRENT | BRENT | | | Enumeration | 1595673 |
Electronic Plan | Original | / | 11/17/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1595661 |
Plumbing | Original | / | 11/16/2021 | ANDREAL | ANDREAL | Overtime approved for Plumbing by Rodney | | Plumbing | 1594630 |
Mechanical | Original | / | 11/16/2021 | ANDREAL | ANDREAL | Overtime approved for Mechanical by Rodney | | Mechanical | 1594629 |
Electrical | Original | / | 11/16/2021 | ANDREAL | ANDREAL | Overtime approved for Electrical by Rodney | | Electrical | 1594628 |
Construction | Original | / | 11/16/2021 | ANDREAL | ANDREAL | Overtime approved for Construction by Rodney | | Construction | 1594627 |
Floodplain | Original | N | 11/16/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6331101013) | | Floodplain | 1594625 |