Mechanical | Original | A | 2/9/2022 | DALEH | DALEH | | | Mechanical | 1634384 | Construction | Original | A | 2/8/2022 | MICHAELA | MICHAELA | | | Construction | 1633741 | Resubmittal 1 | Original | / | 2/7/2022 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1633077 | CO Springs Fire | Original | N | 1/13/2022 | CSFIRE | CSFIRE | NO FIRE FINAL | csfdit | CO Springs Fire | 1621394 | Electrical | Original | A | 12/30/2021 | SHELBY | SHELBY | | | Electrical | 1614963 | Electronic Plan | Original | / | 12/30/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1614821 | Mechanical | Original | D | 12/30/2021 | DALEH | DALEH | Provide a roof plan indicating pitch of roof and access for fan on roof How is MUA being accomplished for new fan ? All items in open plenum must be plenum rated Provide a separate demo plan and a new work plan do not combine Show point of connection from new to existing Waiting for Construction comments to get addressed Indicate how the fans will be controlled Fans must have back draft dampers that close when not in operation (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1614778 | Construction | Original | D | 12/23/2021 | MICHAELA | MICHAELA | More clarification is required as to how the walls are to be extended. Clarify what the existing rated assembly at the corridor is comprised of so as to know what to look for in the match. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1612644 | Floodplain | Original | N | 12/9/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6429316025) | | Floodplain | 1605523 |
|
| |
|