CO Springs Hazmat | Original | D | 6/1/2022 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1690877 |
CO Springs Hazmat | Original | D | 6/1/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1690876 |
CO Springs Fire | Original | D | 6/1/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1690874 |
CO Springs DRE | Original | D | 5/31/2022 | ESHAFER | ESHAFER | Please provide approval from City Clerk's office for change of floor plan. | | CO Springs DRE | 1690091 |
Zoning/Planning | Original | / | 5/23/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1686848 |
Electrical | Original | D | 5/23/2022 | BERTHA | BERTHA | Provide revised electrical for added heat pumps.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1686792 |
Electronic Plan | Original | / | 5/23/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1686742 |
Mechanical | Original | D | 5/23/2022 | DALEH | DALEH | How is ventilation being accomplished for this room? Indicated in ventilation schedule as having O.S.A., but no way of providing it Still need to show complete condensate routing, material and size See air handling schedule (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1686414 |
Plumbing | Original | D | 5/23/2022 | SHANEN | SHANEN | Provide an occupant load to fixture count analysis to verify compliance with section 403.1 Minimum number of fixtures. Door swing on existing restroom does not match the architectural plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1686384 |
CSU Water | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. It appears that the form has either not been submitted or has not been approved yet.
***Form must be submitted to crossconnection@csu.org. Contact Chelsa Shull at 719-668-8755 with any questions.*** SSM | stefanm | CSU Water | 1686315 |
Construction | Original | D | 5/23/2022 | MICHAELA | MICHAELA | Show worst case common path of travel. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1686238 |
Submittal 2 | Original | / | 5/23/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1686194 |
CO Springs Hazmat | Original | D | 2/11/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1635851 |
CO Springs Fire | Original | D | 2/11/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1635847 |
Plumbing | Original | D | 2/3/2022 | SHANEN | SHANEN | Provide an occupancy classification to occupant load fixture count analysis to verify compliance with section 403.1 Minimum number of fixtures. Show door to existing restroom. Architectural floor plans must show drinking fountain location. Reference 2018 IPC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1631869 |
Electrical | Original | D | 2/3/2022 | BERTHA | BERTHA | 1. Provide compliance with 210.8(B)(6) 2. Pending Construction approval - see Construction review comments.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1631796 |
Electronic Plan | Original | / | 1/31/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1630490 |
Mechanical | Original | D | 1/25/2022 | DALEH | DALEH | How are rooms being heated ? Show complete condensate routing and sizes (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1626671 |
CO Springs DRE | Original | D | 1/25/2022 | AODOM | AODOM | Please upload the approved Modification to Premises from the City Clerk's office | | CO Springs DRE | 1626525 |
CSU Water | Original | D | 1/25/2022 | CSUREVIEW | CSUREVIEW | Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form attached to plan has not been submitted to CSU for review yet.
***Form must be submitted to crossconnection@csu.org. Contact Chelsa Shull at 719-668-8755 with any questions.*** SSM | stefanm | CSU Water | 1626428 |
CSU Waste Water | Original | N | 1/25/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSM | stefanm | CSU Waste Water | 1626426 |
Zoning/Planning | Original | / | 1/24/2022 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1625727 |
Construction | Original | D | 1/22/2022 | MICHAELA | MICHAELA | Type of construction is V-A per RBD records. Provide a number for travel distance. Add common path of Egress travel. Show a code compliant path of egress travel. Distance stops at the door. What is the washable material on toilet room walls? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1625208 |
Enumeration | Original | N | 1/11/2022 | BRENT | BRENT | | | Enumeration | 1619949 |
Electronic Plan | Original | / | 1/11/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1619941 |
Floodplain | Original | N | 1/10/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6330404006) | | Floodplain | 1618702 |