Required Departments: 11
|
|
|
Log Entries: 10
|
|
Fountain Water | Original | N | 4/22/2022 | FOUNTAIN | FOUNTAIN | | TMurphy | Fountain Water | 1670012 | Electrical | Original | A | 4/15/2022 | RICHG | RICHG | | | Electrical | 1666133 | Submittal 2 | Original | / | 4/15/2022 | NICKYA | NICKYA | Submittal #2 | | Submittal 2 | 1666114 | Plumbing | Original | A | 2/10/2022 | SHANEN | SHANEN | | | Plumbing | 1635505 | Electrical | Original | D | 2/10/2022 | DANIELG | DANIELG | 1. Comply 110.26 NEC. Proper working clearance.
2. Provide fault current information (SCA, AIC) at Panel "L".
3. Provide manufacturers list of series rated components for all series rated designs.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1635500 | Mechanical | Original | N | 2/10/2022 | DALEH | DALEH | | | Mechanical | 1635484 | Enumeration | Original | N | 2/10/2022 | BECKYA | BECKYA | | | Enumeration | 1635478 | Construction | Original | A | 2/10/2022 | CGIECK | CGIECK | ok---NA | | Construction | 1635462 | Out to Review | Original | / | 2/10/2022 | NELIDA | NELIDA | Kasey 719-632-3232 | | Out to Review | 1635438 | Floodplain | Original | N | 2/10/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5607100010) | | Floodplain | 1635436 |
|
| |
|