CSU Water | Original | A | 5/12/2023 | CSUREVIEW | CSUREVIEW | Comments addressed. SSM | stefanm | CSU Water | 1843162 |
CSU Water | Original | / | 5/12/2023 | CSUREVIEW | CSUREVIEW | | stefanm | CSU Water | 1843161 |
CSU Water | Original | D | 5/4/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1839678 |
Electrical | Original | A | 5/4/2023 | DANIELG | DANIELG | | | Electrical | 1839671 |
Electronic Plan | Original | / | 5/4/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1839667 |
Plumbing | Original | A | 5/4/2023 | SHANEN | SHANEN | | | Plumbing | 1839615 |
Electronic Plan | Original | / | 5/4/2023 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1839599 |
Construction | Original | A | 5/4/2023 | DANM | DANM | | | Construction | 1839544 |
Electronic Plan | Original | / | 5/4/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1839515 |
Enumeration | Original | A | 5/3/2023 | BRENT | BRENT | | | Enumeration | 1839200 |
Electronic Plan | Original | / | 5/3/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1839190 |
Submittal 10 | Original | / | 5/3/2023 | SIERRAC | SIERRAC | Submittal #10 | | Submittal 10 | 1839180 |
CSU Water | Original | D | 5/1/2023 | CSUREVIEW | CSUREVIEW | Updating previous disapproval comment. Per conversation with Civil Engineer and from the information from the pool plans, there is no service line from the building to the pool and no updated USP required. Any other comments still apply. SSM | stefanm | CSU Water | 1837807 |
CSU Water | Original | / | 5/1/2023 | CSUREVIEW | CSUREVIEW | | stefanm | CSU Water | 1837804 |
Health Dept. | Original | A | 4/3/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1186 is valid from 4/1/23 - 10/1/23. To continue earthmoving activities after 10/1/23, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Water recreation plan review application received. Final approval not required for building permit or Certificate of Occupancy. A final inspection is required before the pool may be used.
For questions, contact Environmental Health at 719-578-3199 option 3.
Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. MT | mtemple | Health Dept. | 1824584 |
Health Dept. | Original | D | 3/30/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1186 is valid from 4/1/23 - 10/1/23. To continue earthmoving activities after 10/1/23, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Retail food establishment plan review is in process and not yet approved.
Water recreation plan review application received. Final approval not required for building permit or Certificate of Occupancy.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1823493 |
Plumbing | Original | D | 3/29/2023 | SHANEN | SHANEN | CSU comments must be addressed. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1822474 |
CSU Water | Original | D | 3/29/2023 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
It appears that both a water and wastewater service line are serving the pool from the pool mechanical room but the utility plans DO NOT show these lines. a revised USP is required showing the details of these lines. Additionally, pool deck drains exposed to rain water shall NOT enter Colorado Springs Utilities' wastewater system.
A variance is required for this unit as it is located too far from the existing grease interceptor. Contact CSU Industrial Pretreatment representative Bob Bowren via email at fog@csu.org to request a variance for this condition. Provide a copy of the Variance Letter in the building plan set. SSM | stefanm | CSU Water | 1822285 |
Electrical | Original | A | 3/28/2023 | DANIELG | DANIELG | | | Electrical | 1822106 |
Electronic Plan | Original | / | 3/28/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1822105 |
Elevators | Original | A | 3/28/2023 | ROBERTV | ROBERTV | RBD Notes:
1 - Otis Gen3 Belted Traction Elevator, 3500 lbs, w/ Fire Rated Suspension Means, w/o Generator Power - 2019 Code
1 - Otis Gen3 Belted Traction Elevator, 2500 lbs, w/ Fire Rated Suspension Means, w/o Generator Power - 2019 Code | | Elevators | 1821706 |
Construction | Original | A | 3/28/2023 | DANM | DANM | | | Construction | 1821639 |
Electronic Plan | Original | / | 3/28/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1821625 |
Enumeration | Original | A | 3/28/2023 | BRENT | BRENT | | | Enumeration | 1821576 |
Electronic Plan | Original | / | 3/28/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1821556 |
Submittal 9 | Original | / | 3/28/2023 | JAY | JAY | Submittal #9 | | Submittal 9 | 1821501 |
City Engr | Original | A | 3/17/2023 | PMORRIS | PMORRIS | | | City Engr | 1817494 |
Electrical | Original | D | 3/15/2023 | DANIELG | DANIELG | Pending elevator approval.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1816127 |
Electronic Plan | Original | / | 3/15/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1816123 |
Construction | Original | A | 3/13/2023 | DANM | DANM | | | Construction | 1814839 |
Elevators | Original | D | 3/10/2023 | ROBERTV | ROBERTV | See all sheet comments
1) A323 - Elevator pit dimensions do not match elevator submittals
2) E206 - Pit and top of shaft electrical requirements need to be split up into separate details. All branch circuits need to be separate as listed in NEC 620.22, 23 and 24. Lighting Fixtures need to be installed in elevator pit and top of shaft machine space. Main and Cab 110v Disconnects need to be shown as required per Otis submittals. Keynote 3 needs to be removed to eliminate lighting and receptacles at each floor in the hoistway, and 620.85 does not exist in the NEC 2020. Keynote 4 needs removed as elevator shut down (shunt trip) is not allowed in this jurisdiction, remove all notation of shunt trip in this planset.
3) E309 - Elevator controllers are located at 4th floor elevator entrance jamb, revise one line to reflect.
4) FA201 - Remove fire alarm detection in pit, this is a traction elevator and no fire sprinklers are shown in the elevator pit.
5) FA204 - Need fire alarm detection at top of shaft for elevator drive machines. Fire alarm detection must interrupt motorized damper and exhaust fan power in the event of alarm. Fire alarm detection must flash hat ion elevator car.
6) Need documentation from Otis indicating this elevator will be equipped with Fire Rated Suspension Belts.
RBD Note: Otis Gen3 Belted Traction Elevator w/o Generator Power
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Elevators | 1814674 |
Health Dept. | Original | D | 3/9/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1186 is valid from 9/23/22 - 3/23/23. To continue earthmoving activities after 3/23/23, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Retail food establishment plan review is in process and not yet approved.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Please email application and all required documents to healthinfo@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1813957 |
CO Springs DRE | Original | A | 3/9/2023 | PLANGE | PLANGE | Plan set submitted for building permit review is consistent with the approved PUD plan set (AR PUD 22-0010) which was approved by KAW on February 8, 2023. (see full review) | | CO Springs DRE | 1813890 |
Zoning/Planning | Original | A | 3/9/2023 | PLANGE | PLANGE | Plan set submitted for building permit review is consistent with the approved PUD plan set (AR PUD 22-0010) which was approved by KAW on February 8, 2023. | | Zoning/Planning | 1813818 |
Plumbing | Original | A | 3/8/2023 | SHANEN | SHANEN | | | Plumbing | 1813413 |
CSU Water | Original | D | 3/8/2023 | CSUREVIEW | CSUREVIEW | Initial comments addressed. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. mjg | mgackle | CSU Water | 1813384 |
CSU Waste Water | Original | A | 3/8/2023 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Waste Water | 1813382 |
Gas/Elec. Utils | Original | A | 3/8/2023 | CSUREVIEW | CSUREVIEW | Comments addressed. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 1813381 |
Construction | Original | A | 3/8/2023 | DANM | DANM | Elevators revisions | | Construction | 1813339 |
Electronic Plan | Original | / | 3/8/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1813338 |
Enumeration | Original | A | 3/6/2023 | BRENT | BRENT | | | Enumeration | 1810640 |
Electronic Plan | Original | / | 3/6/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1810614 |
Submittal 8 | Original | / | 3/3/2023 | KALLISTAJ | KALLISTAJ | Submittal #8 | | Submittal 8 | 1810315 |
Health Dept. | Original | D | 9/23/2022 | HEALTHDEPT | HEALTHDEPT | Payment for construction activity permit has not yet been received.
Retail food establishment plan review is in process and not yet approved.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Please email application and all required documents to healthinfo@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1745685 |
Electrical | Original | D | 9/16/2022 | SHELBY | SHELBY | See Elevator comments. Previous review comments have been addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1742583 |
Electronic Plan | Original | / | 9/16/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1742572 |
City Engr | Original | D | 9/16/2022 | PMORRIS | PMORRIS | Same comment: Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. | | City Engr | 1742003 |
CSU Water | Original | D | 9/15/2022 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1741924 |
CSU Waste Water | Original | D | 9/15/2022 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1741923 |
Gas/Elec. Utils | Original | D | 9/15/2022 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1741922 |
Elevators | Original | D | 9/15/2022 | ROBERTV | ROBERTV | Changed to Disapproved RV - TK Elevator has indicated this is not one of their jobs. Please provide submittals for elevators being installed.
These plans were approved 7/22/2022 for 2 - TK Elevator Machine Room-Less Traction Elevators w/ Fire Rated Suspension Belts w/o Generator Power, but now cannot locate Elevator Preliminary Drawings in Planset.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1741569 |
Plumbing | Original | D | 9/15/2022 | SHANEN | SHANEN | Per fixture schedule, URL-1 requires a 3/4"CW supply. Clarify supply sizing to URL-1 throughout (water supply plans, water supply riser diagrams, fixture schedule, etc.). Provide a unit plan and riser diagram for toilet 160A, guest laundry 151, emp. tlt 144, bar in restaurant area 166 and pool equipment room 188. P-401 Plumbing fixture schedule: Per manufacturer's website WCL-03 requires a 1"CW supply. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1741549 |
Elevators | Original | A | 9/15/2022 | ROBERTV | ROBERTV | These plans were approved 7/22/2022 for 2 - TK Elevator Machine Room-Less Traction Elevators w/ Fire Rated Suspension Belts w/o Generator Power. Appears no changes have been made but now cannot locate Elevator Preliminary Drawings in Planset.
Final Elevators Drawings will be required to be spliced into the planset to obtain a permit before elevator installations begin. | | Elevators | 1741525 |
CO Springs DRE | Original | D | 9/15/2022 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement. No approval stamp from City Planning is located on submitted DP. (see full review) | | CO Springs DRE | 1741508 |
Construction | Original | A | 9/15/2022 | DANM | DANM | | | Construction | 1741424 |
Electronic Plan | Original | / | 8/29/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1734799 |
Enumeration | Original | A | 8/26/2022 | BECKYA | BECKYA | | | Enumeration | 1734134 |
Submittal 7 | Original | / | 8/26/2022 | KALLISTAJ | KALLISTAJ | Submittal #7 | | Submittal 7 | 1734114 |
CSU Contract Admin. | Original | A | 8/4/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid. AMS | ASweet | CSU Contract Admin. | 1723709 |
CSU Contract Admin. | Original | / | 8/4/2022 | CSUAPPSPRM | CSUAPPSPRM | | ASweet | CSU Contract Admin. | 1723707 |
Health Dept. | Original | D | 8/1/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KM | kmaldonado | Health Dept. | 1721310 |
CSU Contract Admin. | Original | D | 7/27/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved - requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 1719665 |
City Engr | Original | D | 7/26/2022 | PMORRIS | PMORRIS | Same comment: Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. | | City Engr | 1718713 |
CO Springs Hazmat | Original | N | 7/26/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1718671 |
CO Springs Fire | Original | A | 7/26/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1718668 |
Electrical | Original | D | 7/26/2022 | BERTHA | BERTHA | 1. Comply with previous review comment - Comply with 240.87 NEC including verification that the method chosen to reduce clearing time is set to operate at less than the available arcing current. Information must be supplied and verified by the engineer at the time of plan submittal.
2. Provide service disconnect on one-line.
3. Comply with previous review comment - Comply with Colorado Springs Utilities Electric Line Extension Service Standards (ELESS) - 5.04. Information must be supplied and verified by the engineer at the time of plan submittal.
4. Provide compliance with 620.62 - Information must be supplied and verified by the engineer at the time of plan submittal.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1718609 |
Plumbing | Original | D | 7/25/2022 | SHANEN | SHANEN | P-101: Provide sizing for each section of water piping on the water heater installation detail. P-202, P-302B, P304B, P-306: All kitchen fixtures must discharge to the grease interceptor. Cocktail station and fourth floor bar fixtures may be required to discharge to the grease waste. Contact FOG program manger Robert Bowren 719-668-1735 or fog@csu.org for more information. Provide a unit plan and riser diagram for any area that contains plumbing fixtures (men's restrooms, women's restrooms, fitness area restroom,cocktail station, employee restrooms, fourth floor bar, etc.). P-306: Show FD-02 in guest laundry. P-401: PPRBD does not enforce ADA. Reference ANSI A117.1-2009 for accessibility. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1718104 |
Mechanical | Original | A | 7/25/2022 | JUSTINC | JUSTINC | | | Mechanical | 1717978 |
Electronic Plan | Original | / | 7/25/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1717972 |
Electronic Plan | Original | / | 7/25/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1717971 |
Elevators | Original | A | 7/22/2022 | ROBERTV | ROBERTV | 2 - TK Machine Room-Less Traction Elevators w/ Fire Rated Suspension Belts. No Generator Power | | Elevators | 1717753 |
CSU Water | Original | D | 7/22/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1717568 |
CO Springs DRE | Original | D | 7/22/2022 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement. No approval stamp from City Planning is located on submitted DP. (see full review) | | CO Springs DRE | 1717567 |
CSU Waste Water | Original | D | 7/22/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Waste Water | 1717566 |
Gas/Elec. Utils | Original | D | 7/22/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1717565 |
Construction | Original | D | 7/22/2022 | DANM | DANM | Sheet A-011 still shows UL L524 for the 1-hr rated steel beam UL L524 was tested as an entire floor system with steel joists - does not match wood floor trusses and I-joist shown on drawings for this project. Indicate code compliance with separation of exits on occupied roof. Stair #2 open to occupied roof does not meet requirements for a penthouse per IBC 1011.12.2. UL L524 is still shown on Sheet A-812 and was tested as an entire floor system with steel joists - does not match wood floor trusses and I-joist shown on drawings for this project. ASCE 7-16 is still being referenced on Sheet S-101 when it should be ASCE 7-10.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1717518 |
Electronic Plan | Original | / | 7/20/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1716230 |
Enumeration | Original | A | 7/19/2022 | BECKYA | BECKYA | | | Enumeration | 1715596 |
Electronic Plan | Original | / | 7/19/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1715544 |
Submittal 6 | Original | / | 7/19/2022 | KALLISTAJ | KALLISTAJ | Submittal #6 | | Submittal 6 | 1715488 |
Electrical | Original | D | 6/29/2022 | BERTHA | BERTHA | 1. Provide all conductor size, type and quantity on the one-line diagram - Panel RP
2. Comply with previous review comment 2 - All information must be supplied and verified by the engineer at the time of plan submittal - see Key Note 2 on sheet E-309
3. Comply with previous review comment 3 - Provide the required information for electrical equipment including; elevator control panel, air conditioning and refrigeration equipment.
4. Comply with previous review comment 8 - Comply with 240.87 NEC including verification that the method chosen to reduce clearing time is set to operate at less than the available arcing current.
5. Comply with previous review comment 10 - Provide compliance with 230.70(A)(1)
6. Comply with previous review comment 11 - Comply with Colorado Springs Utilities Electric Line Extension Service Standards (ELESS) - 5.04
7. Provide all feeder and Main Breaker over current device size (ampacity) on the one-line - Panel RP, Panel HLA, Dimmer Panel, etc.
8. Provide compliance with 620.62
9. Pending Elevator approval - see Elevator review comments.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1706092 |
Electrical | Original | D | 6/24/2022 | BERTHA | BERTHA | Electrical review incomplete
Please contact PPRBD for electrical consultation
Electrical reviewer - Bertha Adame - 719-327-2911- Bertha@pprbd.org (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1703685 |
CSU Contract Admin. | Original | D | 6/14/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate.
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
AMS | ASweet | CSU Contract Admin. | 1698258 |
Mechanical | Original | D | 6/14/2022 | JUSTINC | JUSTINC | Mechanical review incomplete
Please contact PPRBD for mechanical consult
Mechanical reviewer - Justin Couturier - 719-327-2899 - Justinc@pprbd.org
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1698014 |
City Engr | Original | D | 6/14/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV22-0184) | | City Engr | 1697844 |
Electronic Plan | Original | / | 6/13/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1697541 |
Plumbing | Original | D | 6/13/2022 | SHANEN | SHANEN | All gas piping and condensate piping shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. See red lines throughout. Pump schedule marks do not match . Verify that all drawings marks match throughout. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1697361 |
Electronic Plan | Original | / | 6/13/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1697019 |
CSU Water | Original | D | 6/10/2022 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | CSU Water | 1696761 |
CSU Waste Water | Original | D | 6/10/2022 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | CSU Waste Water | 1696758 |
Gas/Elec. Utils | Original | D | 6/10/2022 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | Gas/Elec. Utils | 1696755 |
Health Dept. | Original | D | 6/10/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas.
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0.
Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1696674 |
CO Springs Hazmat | Original | D | 6/10/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1696633 |
CO Springs Fire | Original | D | 6/10/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1696632 |
CO Springs DRE | Original | D | 6/10/2022 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement. No approval stamp from City Planning is located on submitted DP. (see full review) | | CO Springs DRE | 1696616 |
Elevators | Original | D | 6/10/2022 | ROBERTV | ROBERTV | Nothing in Fire Alarm Drawings were noted on how the hoistway ventilation is to operate in the event of elevator related Fire Alarm Device activation. Below listed notes are now required to be listed in the Mechanical M-205 and Electrical E-205 sheets:
- Power to Exhaust Fan and Fire / Smoke Damper must be disconnected upon elevator related Fire Alarm device activation. Fire Damper / Smoke Damper must close upon power loss.
- Thermostat mounted in Elevator Hoistway shall open the Fire / Smoke Damper and energize the Exhaust Fan upon Elevator Machine Space cooling demand, but shall not be capable of providing power to either component in the event of Fire Alarm activation. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1696610 |
Construction | Original | D | 6/10/2022 | DANM | DANM | UL L524 was tested as an entire floor system with steel joists - does not match wood floor trusses and I-joist shown on drawings for this project. UL U305 is a tested wall assembly - clarify reason it is being referenced for rated wood column. Occupied roof appears to have 163 occupants which requires 2 exits - indicate the two exits and indicate code compliance with separation of exits and doors swinging in the direction of egress. Stair #2 open to occupied roof does not meet requirements for a penthouse per IBC 1011.12.2. Specify which System (1-13) is being used for UL L556 listing. Appears that there are still some incorrect ratings on the door schedule. Also make sure to note those doors that must resist the passage of smoke due to the room's incidental use. ASCE 7-10 should be referenced on structural sheets (not ASCE 7-16) Floor framing members are indicated as I-joists on architectural drawings - structural notes indicate floor trusses.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1696440 |
Electronic Plan | Original | / | 6/10/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1696136 |
Enumeration | Original | A | 6/9/2022 | BRENT | BRENT | | | Enumeration | 1695625 |
Electronic Plan | Original | / | 6/9/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1695609 |
Submittal 5 | Original | / | 6/8/2022 | BECKYA | BECKYA | Submittal #5 | | Submittal 5 | 1695097 |
CO Springs Hazmat | Original | D | 5/2/2022 | CSFIRE | CSFIRE | pending receipt of all documents required by fire construction review, completed per instructions on those forms | dwithee | CO Springs Hazmat | 1674476 |
CO Springs Fire | Original | D | 5/2/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1674474 |
Health Dept. | Original | D | 4/29/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0. Please email applications and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1673936 |
City Engr | Original | D | 4/29/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV22-0184) | | City Engr | 1673647 |
Electrical | Original | D | 4/29/2022 | BERTHA | BERTHA | 1. For plans feeder schedules in CU and AL, the type of conductor (either CU or AL) must be specified for each conductor.
2. All information must be supplied and verified by the engineer at the time of plan submittal - see Key Note 2 on sheet E-309
3. Provide fault current information (SCA, SCCR, AIC) in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, service equipment, transfer equipment, elevator control panel, fire pump control panel, industrial control panels, air conditioning and refrigeration equipment.
4. Provide elevator horsepower on the one line.
5. Provide levator feeder size, type, and quantity on the one line.
6. Provide elevator over current device size ( Ampacity) on the one line.
7. Pending Elevator approval.
8. Comply with 240.87 NEC including verification that the method chosen to reduce clearing time is set to operate at less than the available arcing current.
9. Provide compliance with 680.14 - Panel SP
10. Provide compliance with 230.70(A)(1)
11. Comply with Colorado Springs Utilities Electric Line Extension Service Standards (ELESS) - 5.04
Review stopped. Complete re-review necessary. Please refer to the following link for Electrical Plan Review Requirements.
https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1673634 |
Electronic Plan | Original | / | 4/29/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1673446 |
CSU Water | Original | D | 4/28/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Water | 1673325 |
CSU Waste Water | Original | D | 4/28/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Waste Water | 1673324 |
Gas/Elec. Utils | Original | D | 4/28/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | Gas/Elec. Utils | 1673322 |
CSU Contract Admin. | Original | D | 4/28/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. CWMSF was received from plan set, and submitted for review.
Please contact our office at 719-668-8111 for additional information and to request an estimate.
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
AMS | ASweet | CSU Contract Admin. | 1673297 |
Plumbing | Original | D | 4/28/2022 | SHANEN | SHANEN | P003: Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Remove all references to uniform plumbing code and national plumbing code of Canada. All gas piping and condensate piping shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. P-201: Yard hydrant must comply with CSU Water Dept. standards for piping materials and burial depth.Yard hydrant must be provided with a separate backflow preventer per section 608.7 Valves and outlets prohibited below grade. Exception.HOSE THREAD VACUUM BREAKER DOES NOT MEET THIS REQUIREMENT. Show location of and piping for the required high/low drinking fountain. P-202: CSU Storm Water Enterprises approval required to discharge FD-01 to the storm sewer as there is a yard hydrant in this area and cleaning products are prohibited from discharging to the storm drain. FD-01 shall not discharge to the sanitary sewer in a dumpster area not covered by a roof. P-202, P-306: Show vent piping for the grease interceptor. P-302B: Schedule SNK-03. SNK-03 shall discharge indirectly if used for food prep or ware washing. Show compliance with section 802 where required. P-304B: Clothes washer discharge must show compliance with section 1003.6. P-306: Provide a detail to show pool deck drains are in compliance with section 802.1.4 Swimming pools. Where waste water from swimming pools, backwash from filters, and water from pool deck drains discharge to the building drainage system (as in this jurisdiction), the discharge shall be through an indirect waste pipe by means of an air gap. Discharging deck drains to the backwash pit as indicated does not meet this requirement. P-401: Schedule all kitchen plumbing fixtures. Schedule required high/low drinking fountain. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1673223 |
Mechanical | Original | D | 4/28/2022 | JUSTINC | JUSTINC | Mechanical review incomplete
See (M) sheets for all comments associated with this review
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1673200 |
CO Springs DRE | Original | D | 4/28/2022 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement. No approval stamp from City Planning is located on submitted DP. (see full review) | | CO Springs DRE | 1673148 |
Electronic Plan | Original | / | 4/28/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1672996 |
Elevators | Original | D | 4/28/2022 | ERIC | ERIC | Provide preliminary elevator submittals, 2 machineroom-less traction elevators
G003 Correct elevator code to ASME A17.1-2019
E-206 detail 3 Pit gfci's to be on individual circuits Top of hoistway gfci's to be on dedicated circuits Non-fused means of main disconnect required adjacent to drive machines Fused cab circuit disconnect required adjacent to drive machines E-309 riser diagram and E-309 E307-Key Notes, remove shunt trip
FA-102 Remove shunt trip. Only required fire alarm initiating devices required by elevator code are; approved device at top of hoistway, approved smoke detectors at all elevator lobbies, these devices will be interlocked with the hoistway ventilation system and close the damper and shut off the fan upon activation of any of these devices.
LT-201 Separate circuits required for elevator pit lighting LT-204 Dedicated circuits required for top of hoistway lighting Ensure 19 fc of lighting at each 4th floor elevator entrance to illuminate test and inspection panel .
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1672952 |
Construction | Original | D | 4/28/2022 | DANM | DANM | Provide egress width calculations for stairs showing code compliance. Include Occupied Roof in 4th Floor Occupant Load table. Meeting Room 154 should be A-3 occupancy with an occupant load factor of 1:15. Laundry 141 must resist the passage of smoke as an incidental use (IBC Table 509). Linen Storage 261 / 361 / 461 must resist the passage of smoke as an incidental use (IBC Table 509). Indicate hatch of 1-hr fire partition at wall between Unit 212 / 312 and Elevator Lobby. Shaft adjacent to Ice Room and Elevators should be rated. Clarify reason for rated wall between bedroom and living room of Unit 211 / 311 / 411 / 429. Shaft adjacent to Stair #1 should be rated. Clarify reason for 2-hr rated wall between Units 219 & 221/ 319 & 321 / 419 & 421. Only 20-min. doors are required between units in a 1-hr fire partition (typical). Provide listed assemblies for all individually encased structural members. Provide area and occupancy of occupied roof - appears to be over 2000 sf and A-2 occupancy. Clarify code compliance of means of egress for occupied roof by labeling the exits from the roof, separation of exits and doors swinging in the direction of egress. Stair #2 open to occupied roof does not seem to meet exterior stair requirements of IBC 1011.7.2 and penthouse requirements of IBC 1011.12.2. UL listings for wall Partition Types are all missing the U that should be in front of the number. UL U305 is referenced for a 2-hr rated wall but the listing is only for a 1-hr rated wall. UL L569 is tested for standard lumber wood joists not for engineered wood I-joists as shown in roof assembly. Specify which System (1-18) is being used for UL L570 listing. Specify which System (1-13) is being used for UL L556 listing. Clarify if roof and floor framing members are I-joists or pre-engineered trusses - shown both ways on drawings - if pre-engineered trusses then listed assemblies are no longer valid since they were tested for I-joists. Many, if not all, UL listing descriptions appear to be outdated - provide newest descriptions from UL website. Provide section through shafts addressing vertical continuity requirements. Provide dashed clear floor space at all accessible fixtures in Mens 158 restroom. Provide dashed clear floor space at accessible urinal in Mens 482 restroom. Show proper handrail extensions at Stair #1 and Stair #2. Clarify how reduced vertical clearance is being addressed at Stair #1 per ICC A117.1 307.4. Provide height dimension for glass parapet at Stair #2. Linen Chute fire barriers do not seem to be meeting vertical continuity requirements at roof. Indicate dashed clear floor space at all accessible bathroom fixtures as well as dashed turning space in King 01 and ADA-1BR. Various doors on Door Schedule showing incorrect ratings. Provide horizontal assembly tags on Wall Section 3 / A-700. UL X526 was tested for steel columns not beams. ASCE 7-10 should be referenced on structural sheets. Clarify if roof and floor framing members are I-joists or pre-engineered trusses - shown both ways on drawings.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1672900 |
Electronic Plan | Original | / | 4/22/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1669829 |
Enumeration | Original | A | 4/21/2022 | BRENT | BRENT | | | Enumeration | 1668839 |
Electronic Plan | Original | / | 4/21/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1668834 |
Submittal 4 | Original | / | 4/20/2022 | JAY | JAY | Submittal #4 | | Submittal 4 | 1668502 |
Plan Coordinator | Original | D | 4/7/2022 | DANM | DANM | Building has not been proven to be code compliant.
Disapprove all remaining departments to allow plan to be resubmitted | | Plan Coordinator | 1662030 |
Construction | Original | D | 4/7/2022 | DANM | DANM | PRELIMINARY REVIEW ONLY The area of the occupied roof under the roof projection must be included in the building area and therefore results in an A-2 occupancy on the 4th floor which is not code compliant. Appears that nonseparated mixed use occupancies will work for the main level which would eliminate the fire barriers.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1662029 |
Electronic Plan | Original | / | 4/5/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1660901 |
Enumeration | Original | A | 4/5/2022 | BRENT | BRENT | | | Enumeration | 1660660 |
Electronic Plan | Original | / | 4/5/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1660654 |
Submittal 3 | Original | / | 4/5/2022 | BPHILLIPS | BPHILLIPS | Submittal #3 | | Submittal 3 | 1660631 |
Plan Coordinator | Original | D | 3/25/2022 | DANM | DANM | Building has not been proven to be code compliant.
Disapprove all remaining departments to allow plan to be resubmitted | | Plan Coordinator | 1655824 |
Construction | Original | D | 3/25/2022 | DANM | DANM | PRELIMINARY REVIEW ONLY A-2 occupancy shown on 4th floor is not allowed per IBC Table 504.4. All responses on letter from architect regarding initial disapproval comments should be integrated into the drawings. Response letters are not considered part of the approved documents. Clarify if there is an occupancy separation between the main level and the second floor - if so, indicate hour rating. Replace "ADA with "Accessible" for all units highlighted orange on the accessibility sheet and all floor plan drawings. Occupant load factor for kitchen can be 1:200. Clarify reason for fire partitions at Kitchen, Fitness and restrooms on first floor. Clarify reason for fire partitions at Business Office on first floor. Clarify reason for fire barrier / occupancy separation at Storage room on first floor. Clarify reason for fire barrier / occupancy separation at corridor on first floor. Occupied rooftop used for food and drink consumption must be considered an A-2 occupancy - the part of the rooftop under the roof overhang cannot be considered a B occupancy - use occupant load factor of 1:15 for main seating area, the actual number of seats at the bar area, and 1:200 for behind the bar - indicate occupant load in uncovered area and covered area separately. Areas designated A-2 Assembly w/o Kitchen on 4th floor do not need to be considered A-2. Storage can be S-1 with occupant load factor of 1:300. The restrooms and corridor can be considered part of the R-1 occupancy with an occupant load factor of 1:200. Sheet A-603 missing from submittal. Sum of the ratios calculations should only be provided on the drawings for floors where there are mixed occupancies and those occupancies are separated by fire barriers. For each floor that has mixed occupancies that are not separated by fire barriers indicate on the drawings the most restrictive occupancy. Clearly indicate all primary structural members requiring individual encasement per IBC 704.2 & 704.3.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1655820 |
Electronic Plan | Original | / | 3/24/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1655330 |
Enumeration | Original | A | 3/24/2022 | BRENT | BRENT | | | Enumeration | 1655144 |
Electronic Plan | Original | / | 3/24/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1655135 |
Submittal 2 | Original | / | 3/24/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1654674 |
Plan Coordinator | Original | D | 3/2/2022 | DANM | DANM | Building has not been proven to be code compliant.
Disapprove all remaining departments to allow plan to be resubmitted | | Plan Coordinator | 1644008 |
Construction | Original | D | 3/2/2022 | DANM | DANM | PRELIMINARY REVIEW ONLY 4th floor area should include covered portion of rooftop bar. Total of occupancy areas on Page 2 of Code Study Form should equal total building area on Page 1 (73,334 sf vs 69,226 sf). Any occupancies with area < 10% of total floor area should be noted as accessory on Page 2 of the Code Study Form. Title block shows "Issued for 60% Franchise Review" - drawings do not appear to be final set. Provide Accessibility Plan per PPRBD requirements. How is allowable height and area being addressed for the occupancies other than R-1 (A-2 / A-3 / B / S-1). Indicate where occupancy separations occur and the hour rating. Note most restrictive occupancy on any level where nonseparated mixed uses exist and provide sum of the ratios for any level where separated mixed uses exist. How is allowable height and area being addressed for the occupancies other than R-1 (A-2 / A-3 / B / S-1). Indicate where occupancy separations occur and the hour rating. Note most restrictive occupancy on any level where nonseparated mixed uses exist and provide sum of the ratios for any level where separated mixed uses exist. Note type of automatic sprinkler system for the building on the drawings (NFPA 13R per Code Study Form). Provide dimensions from exterior of building to center of any surrounding roads to accurately represent fire separation distance for those sides. Per IBC Table 705.8 the maximum area of exterior wall openings based on fire separation distance at each story is 10% for unprotected, nonsprinklered openings - provide calculations on elevations showing compliance.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1644007 |
Electronic Plan | Original | / | 3/1/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1643087 |
Enumeration | Original | A | 2/25/2022 | BRENT | BRENT | | | Enumeration | 1642120 |
Electronic Plan | Original | / | 2/25/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1641709 |
Floodplain | Original | N | 2/24/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220401003) | | Floodplain | 1640916 |