Electrical | Original | A | 8/31/2022 | DANIELG | DANIELG | | | Electrical | 1736056 |
Electronic Plan | Original | / | 8/31/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1736039 |
Submittal 4 | Original | / | 8/31/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1735917 |
CO Springs Hazmat | Original | N | 8/30/2022 | CSFIRE | CSFIRE | HazMat N/A DCT | DTillery94 | CO Springs Hazmat | 1735488 |
CO Springs Fire | Original | A | 8/24/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1732751 |
Electrical | Original | D | 8/5/2022 | DANIELG | DANIELG | Homogenize information from sheet E2.0 and E2.2 into one document/one-line diagram.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1724067 |
Electronic Plan | Original | / | 8/5/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1724045 |
Construction | Original | A | 8/4/2022 | MICHAELA | MICHAELA | | | Construction | 1723268 |
Enumeration | Original | A | 8/3/2022 | BRENT | BRENT | | | Enumeration | 1723052 |
Electronic Plan | Original | / | 8/3/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1723041 |
Submittal 3 | Original | / | 8/3/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1722911 |
CO Springs Hazmat | Original | D | 7/5/2022 | CSFIRE | CSFIRE | FIRE COMMENTS NOT ADDRESSED | jt09ff | CO Springs Hazmat | 1708399 |
CO Springs Fire | Original | D | 7/5/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1708398 |
Plumbing | Original | A | 6/23/2022 | SHANEN | SHANEN | | | Plumbing | 1702862 |
Mechanical | Original | A | 6/22/2022 | JUSTINC | JUSTINC | | | Mechanical | 1702698 |
Electronic Plan | Original | / | 6/22/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1702622 |
Electrical | Original | D | 6/22/2022 | DANIELG | DANIELG | 1. Comply with previous review comment.
2. Provide 2015 IECC calculation.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1702447 |
Electronic Plan | Original | / | 6/22/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1702424 |
Construction | Original | A | 6/21/2022 | MICHAELA | MICHAELA | | | Construction | 1701845 |
Enumeration | Original | D | 6/21/2022 | BRENT | BRENT | See comment from 4/28/22 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1701726 |
Electronic Plan | Original | / | 6/21/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1701692 |
Submittal 2 | Original | / | 6/21/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1701634 |
CO Springs Fire | Original | D | 5/18/2022 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1684478 |
CO Springs Hazmat | Original | D | 5/18/2022 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1684475 |
CO Springs DRE | Original | N | 5/17/2022 | ESHAFER | ESHAFER | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. | | CO Springs DRE | 1683517 |
Electrical | Original | D | 5/11/2022 | DANIELG | DANIELG | Provide complete one-line. Please see link: https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1680599 |
Electronic Plan | Original | / | 5/11/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1680547 |
Plumbing | Original | A | 5/11/2022 | SHANEN | SHANEN | | | Plumbing | 1680239 |
Zoning/Planning | Original | / | 5/9/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1679290 |
Mechanical | Original | A | 5/9/2022 | JUSTINC | JUSTINC | | | Mechanical | 1678840 |
Electronic Plan | Original | / | 5/9/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1678828 |
CSU Waste Water | Original | N | 5/9/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | CSU Waste Water | 1678755 |
CSU Water | Original | N | 5/9/2022 | CSUREVIEW | CSUREVIEW | Backflow okay. No apparent conflicts. CM | CoreyM | CSU Water | 1678750 |
Construction | Original | D | 5/9/2022 | MICHAELA | MICHAELA | Correct the Code Study of this building. There are two "buildings" separated by a Fire Wall. Neither "building is separated use. Revise Codes to those currently adopted in this jurisdiction. Are you intending to use the IEBC? If so, what level of alteration is this? Otherwise remove the IEBC reference. Remove all but one structure from the plan. A separate submittal is required for each building. For permitting purposes work on both sides of the Fire Wall can be done with one permit.. The building is still one address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1678690 |
Electronic Plan | Original | / | 5/9/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1678646 |
Enumeration | Original | D | 4/28/2022 | BRENT | BRENT | There are multiple buildings on this parcel. Include a site plan showing all buildings with addressing and the area of work highlighted in the architectural pages. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1672844 |
Electronic Plan | Original | / | 4/28/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1672822 |
Floodplain | Original | N | 4/26/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5330202009) | | Floodplain | 1671687 |