Zoning/Planning | Original | / | 9/13/2023 | SYSTEM | SYSTEM | Contact Zoning/Planning department for approval prior to permit | | Zoning/Planning | 1899358 |
Plumbing | Original | A | 8/15/2023 | TCRIPPEN | TCRIPPEN | Approved. | | Plumbing | 1885107 |
Mechanical | Original | A | 8/15/2023 | JUSTINC | JUSTINC | | | Mechanical | 1884773 |
Submittal 5 | Original | / | 8/15/2023 | SIERRAC | SIERRAC | Submittal #5 | | Submittal 5 | 1884755 |
Mechanical | Original | D | 8/3/2023 | JUSTINC | JUSTINC | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1879749 |
Electrical | Original | A | 8/3/2023 | DANIELG | DANIELG | | | Electrical | 1879706 |
Electronic Plan | Original | / | 8/3/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1879693 |
Plumbing | Original | D | 8/3/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1879562 |
Construction | Original | A | 8/2/2023 | CGIECK | CGIECK | OK | | Construction | 1879397 |
Enumeration | Original | A | 8/2/2023 | BECKYA | BECKYA | | | Enumeration | 1879168 |
Submittal 4 | Original | / | 8/2/2023 | SHELLEY | SHELLEY | Submittal #4 | | Submittal 4 | 1879123 |
Zoning/Planning | Original | / | 9/1/2022 | SYSTEM | SYSTEM | Contact Zoning/Planning department for approval prior to permit | | Zoning/Planning | 1736451 |
Electrical | Original | A | 8/29/2022 | DANIELG | DANIELG | | | Electrical | 1734650 |
Electronic Plan | Original | / | 8/29/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1734631 |
Gas/Elec. Utils | Original | A | 8/26/2022 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. ------------------------------------------------------- CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. MLW | mlwilliams | Gas/Elec. Utils | 1734371 |
Mechanical | Original | A | 8/26/2022 | JUSTINC | JUSTINC | | | Mechanical | 1734348 |
Construction | Original | A | 8/26/2022 | CGIECK | CGIECK | Please review plan. | | Construction | 1734304 |
Plumbing | Original | A | 8/26/2022 | SHANEN | SHANEN | | | Plumbing | 1734158 |
Enumeration | Original | A | 8/25/2022 | BECKYA | BECKYA | The final plat has been recorded and received by Enumerations. Thank you! | | Enumeration | 1733312 |
Electronic Plan | Original | / | 8/25/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1733305 |
Submittal 3 | Original | / | 8/24/2022 | ANDREAL | ANDREAL | Submittal #3 | | Submittal 3 | 1733268 |
Health Dept. | Original | A | 7/25/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Per Ben Hughes, project is less than 1 acre and doesn't require a construction activity permit. MT | mtemple | Health Dept. | 1718142 |
Stratmoor Hills Water | Original | A | 6/16/2022 | STRATMOORWSD | STRATMOORWSD | | nancy@stratmoorhills | Stratmoor Hills Water | 1699664 |
Plumbing | Original | A | 6/16/2022 | SHANEN | SHANEN | | | Plumbing | 1699479 |
Health Dept. | Original | D | 6/16/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1699466 |
Mechanical | Original | A | 6/15/2022 | JUSTINC | JUSTINC | | | Mechanical | 1698905 |
Electrical | Original | A | 6/15/2022 | DANIELG | DANIELG | | | Electrical | 1698754 |
Electronic Plan | Original | / | 6/15/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1698741 |
Gas/Elec. Utils | Original | D | 6/15/2022 | CSUREVIEW | CSUREVIEW | Applicant response noted. Pending approved development plan. CJS | cjsavage | Gas/Elec. Utils | 1698600 |
Construction | Original | A | 6/15/2022 | CGIECK | CGIECK | Please review plan. | | Construction | 1698507 |
Electronic Plan | Original | / | 6/15/2022 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1698501 |
Enumeration | Original | D | 6/14/2022 | BECKYA | BECKYA | The address for this project has been assigned, but the Final Plat for South Academy Highlands Filing No. 4 has not yet been recorded.The address is 4476 Venetucci Blvd and the plans will need to be updated to show the new assigned address.
Approval pending the recordation of the final plat.
Trash enclosure is under 7' in height and will not require a separate address or permit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1697803 |
Submittal 2 | Original | / | 6/14/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1697779 |
Fountain Hazmat | Original | A | 5/17/2022 | FNTNFIRE | FNTNFIRE | | mgates | Fountain Hazmat | 1683008 |
Fountain Fire | Original | A | 5/13/2022 | FNTNFIRE | FNTNFIRE | City of Fountain Fire Department requires all Fire Line & Remote FDC, Underground Piping plans to be submitted for Fire Review through the City of Fountain Website. Underground installers shall be certified through the Division of Fire Prevention and Control by the State of Colorado. | mgates | Fountain Fire | 1681952 |
Electrical | Original | D | 5/12/2022 | DANIELG | DANIELG | 1. CT cabinets must be separate from service equipment.
2. Provide SCA and SCCR for/at all cooling and refrigeration equipment.
3. Provide 2015 IECC calculation.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1681643 |
Electronic Plan | Original | / | 5/12/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1681642 |
Plumbing | Original | D | 5/11/2022 | SHANEN | SHANEN | Stratmoor Hills Water comments must be addressed. All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans and provide on the mechanical plans. Provide service, backflow preventer, meter and distribution sizing on the domestic water service entrance detail. Clarify water meter size and location. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Water service size does not match utility plan. All plumbing fixtures in a restaurant, except restroom fixtures, water entry floor drain, dishwasher, ice machine and hub drains for condensate, must discharge to the grease waste. Provide a two way clean-out at the junction of the building drain and building sewer per CO state amendment to section 708.1.3. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1680502 |
Stratmoor Hills Waste Water | Original | A | 5/10/2022 | STRATMOORWSD | STRATMOORWSD | Spoke to Matt Larson and straightened out issue resolved | nancy@stratmoorhills | Stratmoor Hills Waste Water | 1679960 |
Mechanical | Original | D | 5/10/2022 | JUSTINC | JUSTINC | Provide all gas associated work with mechanical submittal
This building has been indicated as a V-B structure, with an above ceiling open return air plenum.All construction and materials located within the plenum must comply with all compliance requirements
Typical - Provide air curtain equipment schedules. Cannot be differed or provided by others
Clarify intent? MUA and RTU supply are both shown serving the hood eyebrow. Provide section view or provide additional clarification
Clarify duct size on plan MUA
Clarify how CO2 over allowable limits will comply with 2015 IMC 502.8.1
Clarify roof access
Ventilated roof curbs only permitted when ducts are installed within a 1 hour constructed shaft
MECHANICAL REVIEW INCOMPLETE
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1679588 |
Electronic Plan | Original | / | 5/10/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1679510 |
Stratmoor Hills Water | Original | D | 5/9/2022 | STRATMOORWSD | STRATMOORWSD | 1.5 inch or 1 inch? | nancy@stratmoorhills | Stratmoor Hills Water | 1678655 |
Stratmoor Hills Waste Water | Original | D | 5/9/2022 | STRATMOORWSD | STRATMOORWSD | Need clarification as to sewer main or sewer lateral. | nancy@stratmoorhills | Stratmoor Hills Waste Water | 1678654 |
Stratmoor Hills Water | Original | D | 5/6/2022 | STRATMOORWSD | STRATMOORWSD | see notes on domestic service line size | nancy@stratmoorhills | Stratmoor Hills Water | 1678069 |
Stratmoor Hills Waste Water | Original | D | 5/6/2022 | STRATMOORWSD | STRATMOORWSD | See notes on Sewer main or service line. | nancy@stratmoorhills | Stratmoor Hills Waste Water | 1678068 |
Fountain Fire | Original | A | 5/6/2022 | FNTNFIRE | FNTNFIRE | City of Fountain Fire Department requires all Fire Line & Remote FDC, Underground Piping plans to be submitted for Fire Review through the City of Fountain Website. Underground installers shall be certified through the Division of Fire Prevention and Control by the State of Colorado. | mgates | Fountain Fire | 1677864 |
Gas/Elec. Utils | Original | D | 5/5/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | Gas/Elec. Utils | 1677595 |
Elevators | Original | N | 5/5/2022 | ERIC | ERIC | No Conveyance | | Elevators | 1677447 |
Health Dept. | Original | D | 5/5/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1677394 |
Construction | Original | D | 5/5/2022 | CGIECK | CGIECK | Soil report reference does not match soils report provided. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1677383 |
Electronic Plan | Original | / | 5/3/2022 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1675444 |
Enumeration | Original | D | 5/3/2022 | BECKYA | BECKYA | The address for this project has not yet been assigned. The Final Plat for South Academy Highlands Filing No. 4 has not been sent to Enumerations for addressing. The address for this project will change. Once the addresses have been assigned, these plans will need to be updated to show the new assigned address.
Approval will be pending the recordation of the final plat.
Trash enclosure is under 7' in height and will not require a separate address or permit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1675255 |
Electronic Plan | Original | / | 5/3/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1675241 |
Zoning/Planning | Original | / | 4/29/2022 | SYSTEM | SYSTEM | You will need to contact Zoning/Planning department for approval prior to permit. This department will not review the plan electronically. | | Zoning/Planning | 1673497 |
Traffic Engr. | Original | / | 4/29/2022 | SYSTEM | SYSTEM | You will need to contact Traffic Engr. department for approval prior to permit. This department will not review the plan electronically. | | Traffic Engr. | 1673496 |
City Engr | Original | / | 4/29/2022 | SYSTEM | SYSTEM | You will need to contact City Engr department for approval prior to permit. This department will not review the plan electronically. | | City Engr | 1673495 |
City Engr. | Original | / | 4/29/2022 | SYSTEM | SYSTEM | You will need to contact City Engr. department for approval prior to permit. This department will not review the plan electronically. | | City Engr. | 1673494 |
Floodplain | Original | N | 4/29/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6504311001) | | Floodplain | 1673493 |