Health Dept. | Original | D | 3/15/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1975313 |
CSU Contract Admin. | Original | D | 3/12/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) approved. Requires payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 1974245 |
Construction | Original | D | 3/11/2024 | JUSTINL | JUSTINL | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1973488 |
Plumbing | Original | A | 3/6/2024 | SHANEN | SHANEN | | | Plumbing | 1971839 |
Electronic Plan | Original | / | 3/5/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1971113 |
Enumeration | Original | A | 3/5/2024 | BECKYA | BECKYA | | | Enumeration | 1971096 |
Submittal 7 | Original | / | 3/5/2024 | BRIANNAM | BRIANNAM | Submittal #7 | | Submittal 7 | 1971081 |
CSU Contract Admin. | Original | D | 10/2/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
AMS | ASweet | CSU Contract Admin. | 1906994 |
Health Dept. | Original | D | 9/22/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1903394 |
City Engr | Original | A | 9/21/2023 | JDAGNILLO | JDAGNILLO | | | City Engr | 1902856 |
Electrical | Original | A | 9/21/2023 | DANIELG | DANIELG | | | Electrical | 1902562 |
Plumbing | Original | D | 9/21/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1902557 |
CSU Water | Original | A | 9/21/2023 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | CSU Water | 1902499 |
CSU Waste Water | Original | A | 9/21/2023 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | CSU Waste Water | 1902498 |
Electronic Plan | Original | / | 9/21/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1902471 |
Submittal 6 | Original | / | 9/21/2023 | QUINTONW | QUINTONW | Submittal #6 | | Submittal 6 | 1902459 |
Electrical | Original | D | 3/28/2023 | DANIELG | DANIELG | Upon further review. Provide the 2015 IECC ComCheck calculation.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1822114 |
Electronic Plan | Original | / | 3/28/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1822113 |
City Engr | Original | D | 3/27/2023 | PMORRIS | PMORRIS | same comment: Upload a copy of the Stormwater Enterprise approved Permanent Control Measure (permanent Water Quality Facility) Plan into the electronic building permit set. (ProjectDox# STM-REV22-0399) | | City Engr | 1821161 |
CSU Contract Admin. | Original | D | 3/27/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form attached; however, it needs to be completed in full and resubmitted. Also requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG | aguerin | CSU Contract Admin. | 1821136 |
Plumbing | Original | D | 3/27/2023 | SHANEN | SHANEN | BD is not in plumbing legend, clarify. CSU approved utility service plans required to verify water service/fire service sizing/entry locations and building drain to sewer junctions. Plumbing plans must correspond with approved utility service plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1821126 |
Elevators | Original | A | 3/27/2023 | ROBERTV | ROBERTV | 2 - 3500 lb Otis Gen3 Edge Machine Room-Less Traction Elevators w/o Generator Power (One Elevator per Type of Building) - 2019 Code
Ensure elevators are installed with Fire Rated Suspension Means
Ensure Fire Alarm Detection is installed at the top of shaft Machinery Spaces to flash hat in elevator cars and interrupt power to exhaust fans an motorized dampers if initiated | | Elevators | 1821044 |
CSU Water | Original | D | 3/24/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. Call UDS at 719-668-8259 with questions. CJS | cjsavage | CSU Water | 1820562 |
CSU Waste Water | Original | D | 3/24/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. CJS | cjsavage | CSU Waste Water | 1820559 |
Gas/Elec. Utils | Original | A | 3/24/2023 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. CJS | cjsavage | Gas/Elec. Utils | 1820555 |
Health Dept. | Original | D | 3/24/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1820533 |
Submittal 5 | Original | / | 3/24/2023 | KALLISTAJ | KALLISTAJ | Submittal #5 | | Submittal 5 | 1820511 |
CO Springs DRE | Original | A | 1/6/2023 | MALCURAN | MALCURAN | Approved per plans date stamped 3/17/2022 under CPC CU 21-00097. Please email direct to matthew.alcuran@coloradosprings.gov when the final Zoning inspection is ready. | | CO Springs DRE | 1788501 |
City Engr | Original | D | 11/14/2022 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the Stormwater Enterprise approved Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV22-0399) | | City Engr | 1770449 |
CSU Contract Admin. | Original | D | 11/10/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form attached; however, it needs to be completed in full and resubmitted. Also requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG | aguerin | CSU Contract Admin. | 1769139 |
Health Dept. | Original | D | 11/10/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KM | kmaldonado | Health Dept. | 1769003 |
Plumbing | Original | D | 11/10/2022 | SHANEN | SHANEN | CSU comments must be addressed. P3-101: Five building drain/sewer junctions do not match preliminary utility plan sheet 6 of 17. Unable to verify water service/fire service sizing/entry locations and building drain to sewer junctions without CSU approved utility service plans. Plumbing plans must correspond with approved utility service plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1768849 |
Zoning/Planning | Original | / | 11/9/2022 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1768706 |
Electrical | Original | D | 11/9/2022 | DANIELG | DANIELG | Pending elevator approval.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1768460 |
Electronic Plan | Original | / | 11/9/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1768452 |
Mechanical | Original | A | 11/9/2022 | JUSTINC | JUSTINC | As noted on (M) sheets | | Mechanical | 1768405 |
Electronic Plan | Original | / | 11/9/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1768351 |
Elevators | Original | D | 11/9/2022 | ROBERTV | ROBERTV | -Otis GEN3 Machine Room-Less Traction Elevator w/ Fire Rated Belts and no Generator Power-
Previous comments still not addressed:
1) E2-141, E2-111, E3-141, E3-111 - Machine Space and Pit lighting and GFCI's need to each be on an independent circuit and breaker, 4 independent circuits and breakers required. (NEC 620.23,24)
The elevator driving machine is located at the top of the shaft classifying this space in the overhead as "Machinery Space". The driving machine is stationery and is impossible to move from its final installation. (see NEC 620.2 Definitions). The elevator controller is also located in the elevator shaft when the elevator is in normal operation classifying this space as a "Control Space" (see NEC 620.2 Definitions). Also, when the elevator controller is slid out of the door jamb, this is only when the elevator is receiving service or inspections, not during normal service. Once the elevator controller is slid back into it normal position behind the fire rated door jamb, its returns to the shaft surrounded by fire rated materials. If there is more clarification needed for this code requirement, please feel free to contact me at 719-799-2861.
Notes: Fire Alarm detection required at top of shaft elevator machine space Fire Alarm devices required at each elevator lobby No Fire Sprinkler required in elevator pit or hoistway No Fire Alarm detection required in elevator pit
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Elevators | 1768294 |
CSU Water | Original | D | 11/9/2022 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1768273 |
CSU Waste Water | Original | D | 11/9/2022 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1768270 |
Gas/Elec. Utils | Original | D | 11/9/2022 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1768268 |
Construction | Original | A | 11/9/2022 | MICHAELA | MICHAELA | | | Construction | 1768119 |
Enumeration | Original | A | 11/8/2022 | BECKYA | BECKYA | | | Enumeration | 1767977 |
Submittal 4 | Original | / | 11/8/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1767785 |
CO Springs DRE | Original | D | 9/29/2022 | KDODGE | KDODGE | see TBrackin comments on 5/23/22. New planner M Alcuran | | CO Springs DRE | 1748562 |
CO Springs Fire | Original | A | 9/21/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1744222 |
Plumbing | Original | D | 8/31/2022 | SHANEN | SHANEN | CSU, construction and elevator review comments must be addressed. P0-201: Water service is 2" per preliminary utility plan and P3-101, 3" noted. Clarify. P3-101: 5 building drain/sewer junctions do not match preliminary utility plan sheet 6 of 17. P3-141: Provide a floor plan for unit 408. P3-151: Provide dimensions for the roof drain conductor openings through the parapet. Provide roof drain conductor head dimensions and overflow dimensions (downspout sizing is 4"x4" per sheet A2-511). Provide gpm and/or square footage served by the components of the roof drainage system. Note: All required roof drainage information is not provided on the architectural sheets A2-511 and A7-800. All roof areas to drain into gutters and downspouts per sheet A2-511, clarify how a roof sloped toward parapet walls will utilize gutters for roof drainage. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1735957 |
Mechanical | Original | D | 8/30/2022 | JUSTINC | JUSTINC | See elevator reviewer comment on (M) sheet (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1735430 |
Electrical | Original | D | 8/30/2022 | DANIELG | DANIELG | 1. Elevator conductors supplying the 25 hp motor must comply with 430.22 NEC.
2. Provide 2015 IECC calculation.
3. Pending elevator approval. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1735363 |
Electronic Plan | Original | / | 8/30/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1735335 |
Elevators | Original | D | 8/30/2022 | ROBERTV | ROBERTV | -Otis GEN3 Machine Room-Less Traction Elevator w/ Fire Rated Belts and no Generator Power-
Previous comments still not addressed:
1) A0-401 - Currently adopted elevator code is ASME A17.1 - 2019
2) A2-101 - Need to provide elevator sump pit detail and location on A Sheets
3) E2-141, E2-111, E3-141, E3-111 - Machine Space and Pit lighting and GFCI's need to each be on an independent circuit and breaker
4) E2-141 -See sheet comments, No electrical means are shown for hoistway temperature control requirements.
5) M3-141 - Elevator equipment is located in Top of Hoistway Elevator Machine Space. How is hoistway temperature and humidity going to be maintained per elevator manufacturer requirements and ASME A17.1 (2.7.9.2) ? If supplemental HVAC equipment is required to keep hoistway at required temperature and humidity, HVAC equipment cannot be located in hoistway per IBC 2015 (3002.9). See Sheet notes for required operation
Notes: Fire Alarm detection required at top of shaft elevator machine space Fire Alarm devices required at each elevator lobby No Fire Sprinkler required in elevator pit or hoistway No Fire Alarm detection required in elevator pit
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1735224 |
Health Dept. | Original | D | 8/29/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1735092 |
CSU Contract Admin. | Original | D | 8/26/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted - Requires approval of commercial water meter sizing form, and payment of applicable fees.
AMS | ASweet | CSU Contract Admin. | 1734292 |
City Engr | Original | D | 8/26/2022 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Permanent Control Measure (permanent water quality facility) construction plan into the building permit. | | City Engr | 1733991 |
Zoning/Planning | Original | / | 8/25/2022 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1733832 |
CSU Water | Original | D | 8/25/2022 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | CSU Water | 1733799 |
CSU Waste Water | Original | D | 8/25/2022 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | CSU Waste Water | 1733798 |
Gas/Elec. Utils | Original | D | 8/25/2022 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | Gas/Elec. Utils | 1733797 |
Construction | Original | D | 8/25/2022 | MICHAELA | MICHAELA | AO-601 - W107 - Based on the ICC interpretation pasted on the plan we reached out to UL regarding their area separation walls where a shaft wall assembly creates the separation and where the wood framed walls were bearing walls requiring a rating. UL engineers indicated that the wood framed walls were not rated per those assemblies and in order to afford them the 1-hr. protection they required a second layer of 5/8" type X sheetrock applied to the outside of the assembly was required. While not identical, there is enough similarity here to use the same solution. Indicate 2 layers of sheetrock on the unit side of the wall. A7-311 - This would be a similar situation to the one addressed in the wall types. The bearing wall cannot use the masonry wall to complete the required 1-hr. assembly. Add one layer of the same 5/8" type X sheetrock to the unit side of the bearing walls. A7-321 - This would be compliant. A second choice would be to add one layer of the same 5/8" type X sheetrock to the corridor/ unit/ lobby side of the bearing walls instead of between the wood wall and the masonry wall. Submit only 1 IECC certificate but also include the summary of compliance that was provided in the first review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1733562 |
Enumeration | Original | A | 8/24/2022 | BECKYA | BECKYA | | | Enumeration | 1733075 |
Submittal 3 | Original | / | 8/24/2022 | ANDREAL | ANDREAL | Submittal #3 | | Submittal 3 | 1732918 |
Plan Coordinator | Original | D | 8/19/2022 | MICHAELA | MICHAELA | Disapprove all remaining departments to allow plan to be resubmitted Per the architect the incorrect set was submitted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1730395 |
Plumbing | Original | D | 8/18/2022 | SHANEN | SHANEN | CSU, construction and elevator review comments must be addressed. P0-201: Water service is 2" per preliminary utility plan, 3" noted. Clarify. P3-101: Building drain (5) to sewer point of connection does not match preliminary utility plan sheet 6 of 17. P3-141: Provide a floor plan for unit 408. P3-151: Provide dimensions for the roof drain conductor openings through the parapet. Provide roof drain conductor head dimensions and overflow dimensions (downspout sizing is 4"x4" per sheet A2-511). Provide gpm and/or square footage served by the components of the roof drainage system. Note: All required roof drainage information is not provided on the architectural sheets A2-511 and A7-800. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1730388 |
Elevators | Original | D | 8/18/2022 | ROBERTV | ROBERTV | -Otis GEN3 Machine Room-Less Traction Elevator w/ Fire Rated Belts and no Generator Power-
Previous comments not addressed:
1) A)-401 - Currently adopted elevator code is ASME A17.1 - 2019
2) A2-101 - Need to provide elevator sump pit detail and location on A Sheets
3) E2-111, E3-111 - See sheet comments regarding separate elevator pit and hoistway circuits required
4) E2-141 -See sheet comments, No electrical means are shown for hoistway temperature control requirements.
5) M3-141 - See sheet comments regarding requirement for hoistway temperature control and operations
Notes: Fire Alarm detection required at top of shaft elevator machine space Fire Alarm devices required at each elevator lobby No Fire Sprinkler required in elevator pit or hoistway No Fire Alarm detection required in elevator pit
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1730325 |
Zoning/Planning | Original | / | 8/18/2022 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1730176 |
Health Dept. | Original | D | 8/18/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1730041 |
CSU Water | Original | D | 8/18/2022 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. MLW | mlwilliams | CSU Water | 1729908 |
CSU Waste Water | Original | D | 8/18/2022 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. MLW | mlwilliams | CSU Waste Water | 1729907 |
Gas/Elec. Utils | Original | D | 8/18/2022 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. MLW | mlwilliams | Gas/Elec. Utils | 1729905 |
Electronic Plan | Original | / | 8/18/2022 | ROBERTV | ROBERTV | In Current Review by ROBERTV | | Electronic Plan | 1729824 |
Construction | Original | D | 8/18/2022 | MICHAELA | MICHAELA | Review stopped. Most previous comments have not been addresses. Previous comments have been copied to this submittal. Ignore those that have been corrected and address those remaining that have not been addressed. Revise the imaginary lot line between buildings #3 and #4 and address opening protectives based on the new location. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1729734 |
Enumeration | Original | A | 8/17/2022 | BECKYA | BECKYA | 1 Plan, 2 Permits - approved addressing plan on page A0-300 and the Approved Secondary Addressing plans on pages A2-111, A2-211, A2-311 and A2-411. | | Enumeration | 1729519 |
Submittal 2 | Original | / | 8/17/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1729489 |
CO Springs Hazmat | Original | N | 6/1/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1690773 |
CO Springs Fire | Original | D | 6/1/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1690772 |
Plumbing | Original | D | 5/27/2022 | SHANEN | SHANEN | Provide water pipe size analysis data, see 2018 IPC appendix E. Provide a piping materials schedule. All gas piping and gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans. Provide DFU served by the building drain, each combined section of the building drain and each branch of the building drain. Provide dimensions for the roof drain conductor openings through the parapet. Provide roof drain conductor head dimensions, overflow dimensions and downspout sizing. Provide gpm and/or square footage served by the components of the roof drainage system.Note: All required roof drainage information is not provided on the architectural plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1689541 |
Health Dept. | Original | D | 5/24/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1687093 |
City Engr | Original | D | 5/24/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV22-0399) | | City Engr | 1687068 |
CO Springs DRE | Original | D | 5/23/2022 | TBRACKIN | TBRACKIN | Development Plan must have approval stamp from Planning / Land Use Review indicating Planning Commission approval.
PLDO fees must be paid prior to permit for any residential unit - School district and parkland dedication fees are due per the City PLDO along with police and fire fees for a per unit fee of 1,587.55 for this site. The fee is determined as of the date of approval of this plan and is subject to increase. These fees are due to be paid prior to building permit approval. To pay the fees please bring a check to 2880 International Circle Suite 200-7 or to pay by credit card call 719-385-5982. | | CO Springs DRE | 1686785 |
CSU Contract Admin. | Original | D | 5/23/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5 | aguerin | CSU Contract Admin. | 1686621 |
CSU Water | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1686338 |
CSU Waste Water | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1686337 |
Gas/Elec. Utils | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1686335 |
Electrical | Original | D | 5/23/2022 | DANIELG | DANIELG | 1. Fault current information (SCA, SCCR, AIC) must be included, in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, service equipment, transfer equipment, elevator control panel, fire pump control panel, industrial control panels, air conditioning and refrigeration equipment.
2. Provide elevator horsepower on the one line, SCCR and SCA at/for the Elevator controller, elevator feeder size, type, and quantity on the one line, and elevator over current device size ( Ampacity) on the one line.
3. Provide 2015 IECC calculation.
4. Pending elevator approval.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1686243 |
Electronic Plan | Original | / | 5/23/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1686206 |
Mechanical | Original | D | 5/23/2022 | JUSTINC | JUSTINC | See (M) sheets for comments associated with this mechanical review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1686197 |
Zoning/Planning | Original | / | 5/23/2022 | TBRACKIN | TBRACKIN | In Current Review by TBRACKIN | | Zoning/Planning | 1686096 |
Electronic Plan | Original | / | 5/23/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1686025 |
Elevators | Original | D | 5/23/2022 | ERIC | ERIC | Basis of design-Otis Gen3 machineroom-less traction elevator with fire rated suspension, no generator Provide preliminary elevator submittals
A0-401 Codes- The currently adopted elevator code is ASME A17.1-2019
S1-300 Detail elevator pit and sump pit
Mechanical Hoistway ventilation is required for this type of elevator, ventilation means will be provided with an approved motorized damper, controlled by a thermostat at top of hoistway and be interlocked with top of hoistway heat detector and elevator lobby smoke detectors and shall close the damper upon activation of any of these devices, mechanical equipment shall not be located inside hoistway.
P0-301 detail 7, sump controller is to be located in hoistway.
Pit lighting and gfci outlets are to be on separate circuits. Top of hoistway lighting and gfci outlet to be dedicated circuits Means of main disconnect located at top of hoistway to be non-fused. Means of disconnect for cab circuit located at top of hoistway to be fused. See mechanical review notes for hoistway ventilation requirements.
The only fire alarm initiating devices required for this elevator are; Approved heat detector at top of hoistway Approved smoke detectors in elevator lobbies No device required in elevator pit. No fire sprinklers required in elevator hoistway or pit. . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1686011 |
Construction | Original | D | 5/23/2022 | MICHAELA | MICHAELA | A0-401 - Also show compliance with IBC sec 506.2.3 equation 5-2. A0-511 - Common path of travel distance is required. Corridor must be separated from Boiler WSE. Remove chapter 7 description from exterior walls rated for type of construction. Clarify that sprinkler protection will be extended to projection or indicate it will be non-combustible (FRT). Clarify code path for rating these doors and the wall at storage rooms. A0-601 - WE01 - This is not a "fire partition". Remove chapter 7 designation. "Exterior rated bearing wall." WI09 - This assembly is incomplete. The unit walls must be a complete assembly and may not use the shaftwall assembly to complete it. A0-611 - RC02 - Insulation is not shown in the listing. Per GA, to add insulation to this listing you must install an additional layer of sheetrock to the bottom of the assembly. An ICC-ES report for the spray foam is required for it to be used in a listed floor/ceiling assembly. WI17 - This assembly, per the UL listing, is only rated from one side and that is not permitted for a shaft. Revise the listing or show configuration B which would be compliant. A2-511 - Locate compliant draftstopping on roof plan. Specify exceptions being employed as necessary. A5-101 - 2009 ANSI 117.1 does not permit a shower door to swing into the clear floor space for the shower. To have a door provide an Alternate Methods and Materials request form indicating that you want to use the 2017 ANSI 117.1 and that the shower door will be made removable per that code. A5-102 - Minimum opening size for an alternate roll-in shower is 36". The opening must be created compliantly as the shower door removal may not require alteration of the wall. A5-201/ 301 - Indicate Type B option consistently. A5-202/301 - There is an interior 1-hr. rated bearing wall in this unit. Add an appropriate wall type. A6-101 - Canopy is a projection. Indicate that sprinkler protection is being extended to the projection or indicate non-combustible construction (FRT). A6-111 - Tag roof/ceiling assembly. A6-201 - One side of the corridor will require draftstopping. An additional detail will be required. A7-301 - Provide a detail for the other side of the corridor where draftstopping is required. A7-321 - There is an interior bearing wall under the floor framing and must have an independent 1-hr. listed assembly. It and cannot use the masonry wall to complete it. A7-901 - Detail 4 - Provide listing for the wall assembly behind the FE cabinet. A8-411 - Rated wall must be on the unit side. Unit must be separated from concealed space. The hall way is not an R-2 corridor and so does not require a rating. The storage units do not have to be separated from either the hallway of the concealed space. The required rated walls are highlighted according to the included legend. Why is the shaft wall assembly not being incorporated into, and used as, the unit separation wall? ICC has told us that all rated wall assemblies must be complete to themselves and may not use another rated assembly to complete them. And so the unit wall must be a stand alone fire partition, protected from both sides and cannot use the shaft wall as one side of the assembly. A8-421 - 1-hr. assembly required at trash access room. Revise door schedule based on plan review comments. IECC - Provide the RBD IECC commercial form filled out based on this document. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1685967 |
Electronic Plan | Original | / | 5/19/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1684945 |
Enumeration | Original | A | 5/18/2022 | BECKYA | BECKYA | 1 Plan, 2 Permits
Approved Addressing Plan on page A0-300 and the Approved Secondary Addressing plans on pages A2-111, A2-211, A2-311 and A2-411. The secondary addressing has been sent to CSU and USPS. | | Enumeration | 1683924 |
Electronic Plan | Original | / | 5/17/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1683727 |
Floodplain | Original | N | 5/12/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6424101006) | | Floodplain | 1680923 |