Health Dept. | Original | D | 3/8/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1972936 |
City Engr | Original | D | 3/7/2024 | PMORRIS | PMORRIS | same comment: Upload a copy of the Stormwater Enterprise approved Permanent Control Measure (permanent Water Quality Facility) Plan into the electronic building permit set. (ProjectDox# STM-REV22-0399) | | City Engr | 1972343 |
CSU Contract Admin. | Original | D | 3/6/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) was approved 03/06/2024. Payment of applicable utility charges/fees is required. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 1971996 |
Plumbing | Original | D | 3/6/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1971528 |
Electrical | Original | A | 3/5/2024 | DANIELG | DANIELG | | | Electrical | 1971426 |
Electrical | Original | D | 3/5/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1971407 |
CSU Waste Water | Original | A | 3/5/2024 | CSUREVIEW | CSUREVIEW | Comments addressed. CJS | cjsavage | CSU Waste Water | 1971395 |
CSU Water | Original | D | 3/5/2024 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. CJS | cjsavage | CSU Water | 1971391 |
Construction | Original | A | 3/5/2024 | JUSTINL | JUSTINL | Revisions to site plan dimensions, detail pages, doors and windows | | Construction | 1971352 |
Electronic Plan | Original | / | 3/5/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1971119 |
Enumeration | Original | A | 3/5/2024 | BECKYA | BECKYA | | | Enumeration | 1971039 |
Submittal 5 | Original | / | 3/5/2024 | BRIANNAM | BRIANNAM | Submittal #5 | | Submittal 5 | 1971028 |
CSU Contract Admin. | Original | D | 3/27/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form attached; however, it needs to be completed in full and resubmitted. Also requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG | aguerin | CSU Contract Admin. | 1821170 |
City Engr | Original | D | 3/27/2023 | PMORRIS | PMORRIS | same comment: Upload a copy of the Stormwater Enterprise approved Permanent Control Measure (permanent Water Quality Facility) Plan into the electronic building permit set. (ProjectDox# STM-REV22-0399) | | City Engr | 1821163 |
Electrical | Original | D | 3/27/2023 | DANIELG | DANIELG | Provide the SCCR for the condensing units.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1820813 |
Mechanical | Original | A | 3/27/2023 | JUSTINC | JUSTINC | | | Mechanical | 1820772 |
Plumbing | Original | D | 3/27/2023 | SHANEN | SHANEN | P0-203: Adjust water pipe size analysis data to show 5 wsfu for each water closet and re-calculate totals. Per fixture schedule water closets are flush tank type. Sizing does not match sheet P2-113. CSU approved USP plan required to verify building drain to sewer point of connection and water service size/entry locations.Underground DWV piping does not comply with section 706.3 as drawn. BD is not in plumbing legend, clarify. See clouds. P2-103: CSU approved USP plan required to verify building drain to sewer point of connection and water service size/entry locations. Underground DWV piping does not comply with section 706.3 as drawn. BD is not in plumbing legend, clarify. See clouds. P2-113: 3/4" CW is undersized to serve 2 water closets, 2 lavatories, a drinking fountain and a mop sink. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1820726 |
Gas/Elec. Utils | Original | A | 3/24/2023 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. CJS | cjsavage | Gas/Elec. Utils | 1820575 |
CSU Waste Water | Original | D | 3/24/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. CJS | cjsavage | CSU Waste Water | 1820574 |
CSU Water | Original | D | 3/24/2023 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. Call UDS at 719-668-8259 with questions. CJS | cjsavage | CSU Water | 1820573 |
Health Dept. | Original | D | 3/24/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1820549 |
Construction | Original | A | 3/24/2023 | JUSTINL | JUSTINL | | | Construction | 1820543 |
Electronic Plan | Original | / | 3/24/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1820447 |
Enumeration | Original | A | 3/24/2023 | BECKYA | BECKYA | | | Enumeration | 1820443 |
Submittal 4 | Original | / | 3/24/2023 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1820417 |
Zoning/Planning | Original | / | 1/6/2023 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1788667 |
Zoning/Planning | Original | / | 1/6/2023 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1788666 |
Zoning/Planning | Original | / | 1/6/2023 | MHESTER | MHESTER | In Current Review by MHESTER | | Zoning/Planning | 1788665 |
Zoning/Planning | Original | / | 1/6/2023 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1788664 |
Zoning/Planning | Original | / | 1/6/2023 | MHESTER | MHESTER | In Current Review by MHESTER | | Zoning/Planning | 1788663 |
Zoning/Planning | Original | / | 1/6/2023 | MHESTER | MHESTER | In Current Review by MHESTER | | Zoning/Planning | 1788662 |
Zoning/Planning | Original | / | 1/6/2023 | MHESTER | MHESTER | In Current Review by MHESTER | | Zoning/Planning | 1788661 |
Zoning/Planning | Original | / | 1/6/2023 | MHESTER | MHESTER | In Current Review by MHESTER | | Zoning/Planning | 1788660 |
CO Springs DRE | Original | A | 1/6/2023 | MALCURAN | MALCURAN | Approved per plans date stamped 3/17/2022 under CPC CU 21-00097. Please email direct to matthew.alcuran@coloradosprings.gov when the final Zoning inspection is ready. | | CO Springs DRE | 1788503 |
CO Springs Fire | Original | A | 11/18/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | rpeterson | CO Springs Fire | 1773282 |
City Engr | Original | D | 11/14/2022 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the Stormwater Enterprise approved Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV22-0399) | | City Engr | 1770454 |
CSU Contract Admin. | Original | D | 11/10/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form attached; however, it needs to be completed in full and resubmitted. Also requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG | aguerin | CSU Contract Admin. | 1769142 |
Health Dept. | Original | D | 11/10/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KM | kmaldonado | Health Dept. | 1769008 |
Plumbing | Original | D | 11/10/2022 | SHANEN | SHANEN | Incomplete review, plumbing review stopped. Clubhouse plans submitted, provide fitness building plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1768880 |
Electrical | Original | A | 11/10/2022 | SHELBY | SHELBY | | | Electrical | 1768850 |
Electronic Plan | Original | / | 11/10/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1768847 |
Zoning/Planning | Original | / | 11/9/2022 | RSEVIGNY | RSEVIGNY | In Current Review by RSEVIGNY | | Zoning/Planning | 1768716 |
CSU Water | Original | D | 11/9/2022 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1768345 |
CSU Waste Water | Original | D | 11/9/2022 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1768341 |
Gas/Elec. Utils | Original | D | 11/9/2022 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1768329 |
Construction | Original | D | 11/9/2022 | MICHAELA | MICHAELA | You submitted the clubhouse architectural plan instead of the fitness building. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1768179 |
Mechanical | Original | D | 11/9/2022 | JUSTINC | JUSTINC | This is the clubhouse plan. However this permit is for the Fitness building
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1768151 |
Enumeration | Original | A | 11/8/2022 | BECKYA | BECKYA | | | Enumeration | 1768012 |
Submittal 3 | Original | / | 11/8/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1767860 |
CO Springs Fire | Original | A | 9/7/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1738323 |
City Engr | Original | D | 8/26/2022 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Permanent Control Measure (permanent water quality facility) construction plan into the building permit. | | City Engr | 1733994 |
CSU Contract Admin. | Original | D | 8/19/2022 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted. Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
AMS | ASweet | CSU Contract Admin. | 1730835 |
Electrical | Original | D | 8/18/2022 | SHELBY | SHELBY | Please show SCCR at/for the cooling equipment. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf for fault current terms and methodologies. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1729778 |
Electronic Plan | Original | / | 8/18/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1729764 |
Health Dept. | Original | D | 8/17/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1729696 |
CO Springs DRE | Original | D | 8/17/2022 | RSEVIGNY | RSEVIGNY | upload approved development plan with stamp | | CO Springs DRE | 1729591 |
Zoning/Planning | Original | / | 8/17/2022 | RSEVIGNY | RSEVIGNY | In Current Review by RSEVIGNY | | Zoning/Planning | 1729502 |
CSU Water | Original | D | 8/17/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1729142 |
CSU Waste Water | Original | D | 8/17/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Waste Water | 1729140 |
Gas/Elec. Utils | Original | D | 8/17/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1729138 |
Mechanical | Original | A | 8/17/2022 | JUSTINC | JUSTINC | | | Mechanical | 1729106 |
Construction | Original | A | 8/17/2022 | MICHAELA | MICHAELA | | | Construction | 1729078 |
Plumbing | Original | D | 8/16/2022 | SHANEN | SHANEN | P0-203: Schedule EWC-1. Provide a piping materials schedule. P2-103: Sewer and water service locations do not match preliminary utility plan. CSU approved development plan required to verify building drain to sewer point of connection and water service entry locations. P2-113: All required roof drainage information (thru wall scupper opening dimensions, conductor head dimensions, overflow opening dimensions, gpm/square footage served, etc.) is not provided on architectural sheets A2-123 and A7-800. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1728445 |
Enumeration | Original | A | 8/10/2022 | BECKYA | BECKYA | | | Enumeration | 1726300 |
Submittal 2 | Original | / | 8/10/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1726136 |
CO Springs Hazmat | Original | N | 6/2/2022 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 1691426 |
CO Springs Fire | Original | D | 6/2/2022 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | csfdit | CO Springs Fire | 1691425 |
Plumbing | Original | D | 5/31/2022 | TCRIPPEN | TCRIPPEN | Provide square footage or gpm at each roof drain provide sizes for scuppers and down spouts on plumbing pages. Provide CSUs back-flow forum on plan set. provide an water pipe size analysis on plan set. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1689890 |
Health Dept. | Original | D | 5/24/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1687102 |
City Engr | Original | D | 5/24/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV22-0399) | | City Engr | 1687073 |
Mechanical | Original | D | 5/24/2022 | JUSTINC | JUSTINC | Indicate condensate routing on (M) sheets Remove notes not applicable to this permit (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1686966 |
Electronic Plan | Original | / | 5/24/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1686953 |
CO Springs DRE | Original | D | 5/23/2022 | TBRACKIN | TBRACKIN | Development Plan must have approval stamp from Planning / Land Use Review indicating Planning Commission approval. | | CO Springs DRE | 1686789 |
Zoning/Planning | Original | / | 5/23/2022 | TBRACKIN | TBRACKIN | In Current Review by TBRACKIN | | Zoning/Planning | 1686690 |
Electrical | Original | D | 5/23/2022 | SHELBY | SHELBY | 1. Please provide 2015 IECC calculation ( Use comcheck-EZ). 2. Show SCA and SCCR at/for new cooling equipment. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1686636 |
CSU Contract Admin. | Original | D | 5/23/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5 | aguerin | CSU Contract Admin. | 1686631 |
Electronic Plan | Original | / | 5/23/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1686607 |
CSU Water | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1686349 |
CSU Waste Water | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1686348 |
Gas/Elec. Utils | Original | D | 5/23/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1686344 |
Construction | Original | D | 5/23/2022 | MICHAELA | MICHAELA | A0-403 - Indicate worst case common path of travel. Provide a furniture/equipment layout allowing this egress path or revise the route to a rectilinear path. If gym equipment is not being provided revise to an A-3 occupancy and 1:15 OLF. A0-602 - Exterior walls are not fire partitions. Revise description without using language from chapter 7. A3-103 - Right Elevation - A parapet is required on this wall. Show compliance with IBC sec. 705.11. A4-103 - Detail 3 - Provide a detail for the construction of this parapet. It must extend 30" above the roof. The upper 18" must be of non-combustible construction on both sides. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1686328 |
Elevators | Original | N | 5/23/2022 | ERIC | ERIC | No conveyance | | Elevators | 1686125 |
Electronic Plan | Original | / | 5/23/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1686086 |
Enumeration | Original | A | 5/18/2022 | BECKYA | BECKYA | | | Enumeration | 1684003 |
Electronic Plan | Original | / | 5/17/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1683730 |
Floodplain | Original | N | 5/12/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6424101006) | | Floodplain | 1680964 |