CO Springs Fire | Original | A | 7/5/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1708195 |
Electrical | Original | A | 7/5/2022 | SHELBY | SHELBY | | | Electrical | 1708086 |
Electronic Plan | Original | / | 7/5/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1708081 |
Plumbing | Original | A | 6/30/2022 | SHANEN | SHANEN | | | Plumbing | 1706727 |
Plumbing | Original | D | 6/30/2022 | SHANEN | SHANEN | Pending completed drinking fountain alternate - fee must be paid prior to processing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1706615 |
Mechanical | Original | A | 6/24/2022 | JUSTINC | JUSTINC | | | Mechanical | 1703973 |
Construction | Original | A | 6/24/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1703949 |
Electronic Plan | Original | / | 6/24/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1703848 |
Enumeration | Original | A | 6/24/2022 | BECKYA | BECKYA | | | Enumeration | 1703760 |
Submittal 2 | Original | / | 6/23/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1703449 |
CO Springs Hazmat | Original | N | 6/16/2022 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1699358 |
CO Springs Fire | Original | D | 6/16/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1699357 |
Plumbing | Original | D | 6/14/2022 | SHANEN | SHANEN | Provide approved occupant load to verify compliance with section 403.1 Minimum number of fixtures. Per code study form the preliminary occupant load is 23 requiring a service sink and high/low drinking fountain. Provide these required fixtures if occupant load is greater than 15. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1697869 |
CSU Contract Admin. | Original | N | 6/10/2022 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and applicable Development fees/charges paid - master meter configuration. AG | aguerin | CSU Contract Admin. | 1696578 |
CO Springs DRE | Original | A | 6/7/2022 | APAQUETTE | APAQUETTE | Approval of interior finish. No elevation, parking, or other exterior changes. | | CO Springs DRE | 1694015 |
Electrical | Original | A | 6/7/2022 | SHELBY | SHELBY | | | Electrical | 1693855 |
Electronic Plan | Original | / | 6/7/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1693850 |
Mechanical | Original | D | 6/3/2022 | JUSTINC | JUSTINC | Provide refrigeration calculation per 2015 IMC 1103.1 Verify if within allowable limits per table on plan. If over the allowable limits indicate how protecting on plan. Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1692036 |
Electronic Plan | Original | / | 6/3/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1691997 |
Zoning/Planning | Original | / | 6/2/2022 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1691718 |
CSU Water | Original | A | 6/2/2022 | CSUREVIEW | CSUREVIEW | Refer to core and shell permit for approved utility construction drawings. MLW | mlwilliams | CSU Water | 1691569 |
CSU Waste Water | Original | A | 6/2/2022 | CSUREVIEW | CSUREVIEW | Refer to core and shell permit for approved utility construction drawings. MLW | mlwilliams | CSU Waste Water | 1691567 |
Gas/Elec. Utils | Original | A | 6/2/2022 | CSUREVIEW | CSUREVIEW | Refer to core and shell permit for approved utility construction drawings. MLW | mlwilliams | Gas/Elec. Utils | 1691565 |
City Engr | Original | N | 6/2/2022 | JDAGNILLO | JDAGNILLO | | | City Engr | 1691435 |
Construction | Original | D | 6/2/2022 | BPHILLIPS | BPHILLIPS | Appears floor plan labeling may be reversed on Sheet A0. Recalculate occupant load. Waiting area should be 1:15, and the remainder should be 1:100 gross (including the storage closets). Requires 18" clearance for accessibility on pull side of door from Office #3. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1691360 |
Electronic Plan | Original | / | 6/1/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1690665 |
Enumeration | Original | A | 5/25/2022 | BECKYA | BECKYA | Structural Plans were edited to show the correct address, suite number was added to Mechanical and Plumbing plans. If any of these corrected sheets are revised and resubmitted, please be sure to make these corrections on your end before resubmitting the plans. | | Enumeration | 1687737 |
Floodplain | Original | N | 5/23/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6301405021) | | Floodplain | 1686476 |