Plan Details
Clear
Permits
By Address
By Permit Number
Fee Calculator
Plans
By Address
List of Plans
Links
City PlanTrac
Colorado Springs Utilities
Home
Plan #
  
Type
 
Plan
Owner
Address
620 W COLORADO AVE, COLORADO SPRINGS, CO 80905
Parcel Info
7413126015
Truss P/SF
30 (Elevation: 5,991 Feet)
Project
PANEL CHANGE OUT (
437
)
Type Of Plan
Normal
Review Type
Single Copy
Fire District
COLORADO SPRINGS FIRE DIST
Submit Date
Approval Date
Location
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 3
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Electrical
D
0
E
Electrical
Enumeration
D
0
N
Enumeration
Floodplain
N
W
Floodplain
Log Entries: 10
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
Finished Bin
Original
/
6/7/2022
SCANNING
Location = Finished Bin by SCANNING
Finished Bin
1693880
Plan Coordinator
Original
/
6/3/2022
RICHG
Location = Plan Coordinator by RICHG
Plan Coordinator
1692544
Electrical
Original
D
6/3/2022
RICHG
RICHG
1. Provide panel schedule for all panels and MDP
2. Provide available fault current at each panel.
3. Provide OCPD for each panel.
4. Provide Site plan
5. Provide all conductor size, type, and quantity. ( ex. GEC)
6. Label panels location (ex. Apt # or Suite #)
7. Clearly label which panels are new or existing
8. Comply with 250.122 (G)
9. Provide all identifying info for electrical gear. ( ex. disconnect, amps..)
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.)
Electrical
1692543
Electrical
Original
/
6/3/2022
RICHG
RICHG
In Current Review by RICHG
Electrical
1692005
Electrical
Original
/
5/26/2022
SHELBY
SHELBY
In Current Review by SHELBY
Electrical
1689176
Electrical
Original
/
5/26/2022
SCANNING
Location = Electrical by SCANNING
Electrical
1689024
Plan Coordinator
Original
/
5/26/2022
BECKYA
Location = Plan Coordinator by BECKYA
Plan Coordinator
1688933
Enumeration
Original
D
5/26/2022
BECKYA
BECKYA
Please provide a site plan of the entire lot to include building location, the surrounding streets and north arrow.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.)
Enumeration
1688929
Enumeration
Original
/
5/26/2022
BECKYA
BECKYA
In Current Review by BECKYA
Enumeration
1688917
Floodplain
Original
N
5/24/2022
RBD GIS
RBD GIS
Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7413126015)
Floodplain
1687223